5 Adjustments
Q3 1000-2000A
25
D
is
p
la
y
s
+
BTB signal - Drive ready
BTB signal
X3:25
>+5V
Error
X3:25
<+5V
Error
Voltage error
24V, 15V, 5V
saved
Phase error, rotating field
saved
Defective input fuse
saved
Over-temperature
saved
In case of errors or failure the power section is immediately internally disabled
without delay.
To clear the saved error re-enable the drive (switch off/on or reset key)
Measurements
Measurement advice
Measuring instruments:
multimeters for current and voltage
shunt or clamp-on ammeter
Measuring faults:
mean value > actual value
acc. to the form factor
approx. 1 to 5%
Measured values
with a positive command value
Voltage:
X10:10 positive
X10:13 negative
max 1.15 x power supply
For 400V
~
>>
460V=
Current: ammeter in the motor circuit
5s 200%, continuously 110% type current
Measured values across REG4
(selectable, see Manual REG4)
Speed
X2:109
±
5V or
±
10V
for
±
100% speed
Current
X2:111
±
5V or
±
10V
for
±
200% current
GND
X2:104