background image

3

95-8723

3.4

Appendix A - FM

Appendix B - CSA

Appendix C - IECEx

Appendix D - Additional Approvals

OPERATION

WARM UP

When the detector is initially powered up, a warm-

up period of one – two seconds is allotted for 

internal checks and communication. During this 

time, the LED is off and the current level is 3 mA. 

After the checks are completed, normal operation 

will be indicated by the LED flashing every four 

seconds (current level is 4 mA). 

If the detector is unable to reach the normal 

operating mode, the warm-up period may extend 

to five seconds, followed by a critical fault or an 

advisory fault (see Table 1 for all current levels).   

If the problem persists, check for any loose wiring 

connections, ensure that the voltage supply is 

sufficient, and cycle power if necessary.

OUTPUTS
Relays

The U5015 detector is furnished with smoke 

alarm, fault, and auxiliary relays.  All three 

relays are rated to 5 amperes at 30 Vdc.

The smoke alarm relay has a single set of 

terminals and normally open / normally closed  

contacts, and normally de-energized operation.

The fault relay has a single set of terminals 

and normally open contacts, and normally 

energized operation.

The auxiliary relay has a single set of terminals 

and normally open  / normally closed  contacts, 

and normally de-energized operation.

IMPORTANT

The auxiliary relay functions as pre-alarm.

0 to 20 mA Output

The U5015 provides a 0 to 20 mA dc current for 

transmitting detector status information to other 

devices. The circuit is wired in a non-isolated 

configuration and can drive a maximum loop 

resistance of 300 ohms from 12 to 17.9 Vdc, 500 

ohms from 18 to 19.9 Vdc, and 600 ohms from 

20 to 30 Vdc. Table 1 defines the current levels 

and corresponding detector status. The output 

is calibrated at the factory, with no need for field 

calibration. 

NOTE

The output of the 0 to 20 mA current loop 
is monitored by the fault detection circuitry 
of the U5015. Therefore, an open circuit on 
the loop will cause the fault relay to change 
state.

An alarm will normally over-ride a fault, unless 

the nature of the fault impairs the ability of 

the detector to generate or maintain an alarm 

output (i.e., loss of operating power).

Figure 2—U5015 Dimensions in Inches (cm)

4.99 (12.67)

B2680

7.55 (19.18)

2X 3.80 (9.65)

6X R0.19

2X 1.75

(4.44)

2X 2.25 (5.71)

3.75 (9.52)

4X 1.29 (3.27)

2X 2.50 (6.35)

7.55 (19.18)

Table 1—Detector Status Conditions Indicated by Current Level

Current Level (±0.3 mA)

Detector Status

0 mA

Power Fault

1 mA

Critical Fault

2 mA

Power Advisory (<12 Vdc)

3 mA

Warm up

4 mA

Normal

6 mA

Advisory Fault

16 mA

Pre-Alarm

20 mA

Smoke Alarm

Содержание DET-TRONICS SmokeWatch U5015

Страница 1: ...3 4 95 8723 Instructions Det Tronics SmokeWatch Explosion Proof Smoke Detector U5015...

Страница 2: ...ocations 5 Protection Against Moisture Damage 6 Power Supply Requirements 6 Transport Cover 6 Mounting Location Options 6 Mount the Detector 7 Wiring Cable Requirements 7 Jumper 7 Wiring Procedure 8 M...

Страница 3: ...e and allows live maintenance while under power without de classifying the hazardous area The integrated junction box is available in a variety of port configurations for simplified wiring and install...

Страница 4: ...ally open normally closed contacts and normally de energized operation TEMPERATURE RANGE Operating 20 C to 65 C 4 F to 149 F Storage 55 C to 70 C 67 F to 158 F HUMIDITY RANGE 5 to 95 relative humidity...

Страница 5: ...set of terminals and normally open normally closed contacts and normally de energized operation IMPORTANT The auxiliary relay functions as pre alarm 0 to 20 mA Output The U5015 provides a 0 to 20 mA d...

Страница 6: ...passed If the test fails a critical fault will occur If degradation is present and approaching critical levels an advisory fault will occur MANUAL SELF TEST The Manual Self Test function will immedia...

Страница 7: ...n Sulfide and Chlorine are normally present INSTALLATION WARNING All entries must contain appropriately rated plugs or fittings It is required that each plug or fitting be wrench tightened to an appro...

Страница 8: ...e capability for the calculated load Ensure that the selected power supply provides sufficient regulated and filtered output power for the entire system If a back up power system is required a float t...

Страница 9: ...o U5015 is 2000 feet When the U5015 Smoke Detector is mounted remotely using an STB termination box maximum cable length from U5015 to STB is 500 feet WARNING For field connections use wires cables th...

Страница 10: ...4 inch adapter When installing the junction box use care not to damage the wires and refrain from twisting them 3 Connect the external wiring to the appropriate terminals Figure 9 shows the wiring te...

Страница 11: ...the user in the field ROUTINE INSPECTION Regularly scheduled maintenance is not required however the U5015 cover and smoke chamber should be inspected periodically when detectors are located in abnor...

Страница 12: ...M NC ALARM COM FAULT NO FAULT 1 2 3 4 5 6 7 8 Figure 12 Single Detector Wiring 0 20 mA used Relays not used POWER 2 WIRE CLASS B RECEIVING ZONE CHASSIS GROUND GROUND LUG B2685 Control Panel JUMPERS EO...

Страница 13: ...P5 NO AUX COM AUX NC AUX NO ALARM COM ALARM NC ALARM COM FAULT NO FAULT 1 2 3 4 5 6 7 8 RELAY OUTPUTS mA Vin Vin Vin Vin 5 4 3 2 1 POWER SUPPLY 0 20 mA OUTPUT P11 P5 NO AUX COM AUX NC AUX NO ALARM CO...

Страница 14: ...COM AUX NC AUX NO ALARM COM ALARM NC ALARM COM FAULT NO FAULT 1 2 3 4 5 6 7 8 RELAY OUTPUTS mA Vin Vin Vin Vin 5 4 3 2 1 POWER SUPPLY 0 20 mA OUTPUT P11 P5 NO AUX COM AUX NC AUX NO ALARM COM ALARM NC...

Страница 15: ...nction must accompany the returned device or component to assist and expedite finding the root cause of the failure Pack the unit properly Always use sufficient packing material Where applicable use a...

Страница 16: ...alarm signaling Special Conditions For Safe Use X 1 The U5015 is to be installed in locations where the risk of mechanical damage is low 2 Potential electrostatic charging hazard please see instructi...

Страница 17: ...0 General Requirements C22 2 No 60079 1 2016 Explosive atmospheres Part 1 Equipment protection by flameproof enclosures d C22 2 No 60079 11 2014 Electrical apparatus for explosive gas atmospheres Part...

Страница 18: ...ospheres Equip protection by Intrinsic Safety Special Conditions For Safe Use X 1 The U5015 is to be installed in locations where the risk of mechanical damage is low 2 Potential electrostatic chargin...

Страница 19: ...ICATE OF CONFORMITY TO TP TC 012 2011 No TC RU C US BH02 B 00239 1Exd ia IICT4 IP44 T4 Tamb 20 C to 65 C Declaration of Conformity to TP TC 020 2011 EMC EA C No RU US PA01 B 50006 RUSSIA VNIIPO CERTIF...

Страница 20: ...95 8723 Corporate Office 6901 West 110th Street Minneapolis MN 55438 USA www det tronics com All trademarks are the property of their respective owners 2019 Detector Electronics Corporation All rights...

Отзывы: