WARNING

Be sure to read and understand the entire 
instruction manual before installing or 
operating the smoke detection system.  Any 
deviation from the recommendations in this 
manual may impair system performance 
and compromise safety.

OVERVIEW

The Det-Tronics

®

 SmokeWatch

 U5015 Explosion 

Proof Smoke Detector has Division and Zone 

explosion-proof ratings and is suitable for industrial 

and commercial applications. The detector is 

designed to operate effectively with smoldering 

and rapidly growing fires and contains the ability to 

annunciate fault ensuring no undisclosed failures.  

The SmokeWatch

 

U5015 Smoke Detector outputs 

include 0-20 mA, a localized LED, and relays.  

Typical applications that use the U5015 include:

 

– Combustible storage facilities

 

– Munitions manufacturing

 

– Volatile chemical storage

 

– Chemical processing plants

 

– Petroleum refineries

 

– Turbine enclosures

 

– Battery rooms

 

– HVAC applications

The hot-swappable sensor module is intrinsically 

safe and allows live maintenance while under 

power, without de-classifying the hazardous area.

The integrated junction box is available in a 

variety of port configurations for simplified wiring 

and installation. See Figure 1 for all the U5015 

Smoke Detector components.

FEATURES

• 

FM Approved for use in Class I, Division 1 

hazardous locations

• 

FM Approved for smoke detection performance

• 

IECEx Zone approved

• 

Trouble-free photoelectric operation

• 

0-20 mA output for DCS integration

• 

Self-checking circuitry ensures reliable smoke 

detection

• 

Alarm, Auxiliary, and Fault relays for controlling 

annunciating devices or fire panel interface

• 

LED provides a visual indication that an alarm 

has occurred

• 

IP44 ingress protection level suitable for 

onshore or offshore requirements

BENEFITS

• 

Ideally suited for classified areas in the 

petrochemical, oil, and gas industry

• 

DCS, PLC, integration with milliamp or relay 

outputs

• 

Rugged design for environmental extremes

• 

Visual confirmation of detector alarm

• 

Detects smoldering fires

• 

No undisclosed failures

INSTRUCTIONS

Det-Tronics

®

 SmokeWatch

 

Explosion Proof Smoke Detector

U5015

©Detector Electronics Corporation 2019

Last Manual Update: 5/30/19 

Содержание DET-TRONICS SmokeWatch U5015

Страница 1: ...3 4 95 8723 Instructions Det Tronics SmokeWatch Explosion Proof Smoke Detector U5015...

Страница 2: ...ocations 5 Protection Against Moisture Damage 6 Power Supply Requirements 6 Transport Cover 6 Mounting Location Options 6 Mount the Detector 7 Wiring Cable Requirements 7 Jumper 7 Wiring Procedure 8 M...

Страница 3: ...e and allows live maintenance while under power without de classifying the hazardous area The integrated junction box is available in a variety of port configurations for simplified wiring and install...

Страница 4: ...ally open normally closed contacts and normally de energized operation TEMPERATURE RANGE Operating 20 C to 65 C 4 F to 149 F Storage 55 C to 70 C 67 F to 158 F HUMIDITY RANGE 5 to 95 relative humidity...

Страница 5: ...set of terminals and normally open normally closed contacts and normally de energized operation IMPORTANT The auxiliary relay functions as pre alarm 0 to 20 mA Output The U5015 provides a 0 to 20 mA d...

Страница 6: ...passed If the test fails a critical fault will occur If degradation is present and approaching critical levels an advisory fault will occur MANUAL SELF TEST The Manual Self Test function will immedia...

Страница 7: ...n Sulfide and Chlorine are normally present INSTALLATION WARNING All entries must contain appropriately rated plugs or fittings It is required that each plug or fitting be wrench tightened to an appro...

Страница 8: ...e capability for the calculated load Ensure that the selected power supply provides sufficient regulated and filtered output power for the entire system If a back up power system is required a float t...

Страница 9: ...o U5015 is 2000 feet When the U5015 Smoke Detector is mounted remotely using an STB termination box maximum cable length from U5015 to STB is 500 feet WARNING For field connections use wires cables th...

Страница 10: ...4 inch adapter When installing the junction box use care not to damage the wires and refrain from twisting them 3 Connect the external wiring to the appropriate terminals Figure 9 shows the wiring te...

Страница 11: ...the user in the field ROUTINE INSPECTION Regularly scheduled maintenance is not required however the U5015 cover and smoke chamber should be inspected periodically when detectors are located in abnor...

Страница 12: ...M NC ALARM COM FAULT NO FAULT 1 2 3 4 5 6 7 8 Figure 12 Single Detector Wiring 0 20 mA used Relays not used POWER 2 WIRE CLASS B RECEIVING ZONE CHASSIS GROUND GROUND LUG B2685 Control Panel JUMPERS EO...

Страница 13: ...P5 NO AUX COM AUX NC AUX NO ALARM COM ALARM NC ALARM COM FAULT NO FAULT 1 2 3 4 5 6 7 8 RELAY OUTPUTS mA Vin Vin Vin Vin 5 4 3 2 1 POWER SUPPLY 0 20 mA OUTPUT P11 P5 NO AUX COM AUX NC AUX NO ALARM CO...

Страница 14: ...COM AUX NC AUX NO ALARM COM ALARM NC ALARM COM FAULT NO FAULT 1 2 3 4 5 6 7 8 RELAY OUTPUTS mA Vin Vin Vin Vin 5 4 3 2 1 POWER SUPPLY 0 20 mA OUTPUT P11 P5 NO AUX COM AUX NC AUX NO ALARM COM ALARM NC...

Страница 15: ...nction must accompany the returned device or component to assist and expedite finding the root cause of the failure Pack the unit properly Always use sufficient packing material Where applicable use a...

Страница 16: ...alarm signaling Special Conditions For Safe Use X 1 The U5015 is to be installed in locations where the risk of mechanical damage is low 2 Potential electrostatic charging hazard please see instructi...

Страница 17: ...0 General Requirements C22 2 No 60079 1 2016 Explosive atmospheres Part 1 Equipment protection by flameproof enclosures d C22 2 No 60079 11 2014 Electrical apparatus for explosive gas atmospheres Part...

Страница 18: ...ospheres Equip protection by Intrinsic Safety Special Conditions For Safe Use X 1 The U5015 is to be installed in locations where the risk of mechanical damage is low 2 Potential electrostatic chargin...

Страница 19: ...ICATE OF CONFORMITY TO TP TC 012 2011 No TC RU C US BH02 B 00239 1Exd ia IICT4 IP44 T4 Tamb 20 C to 65 C Declaration of Conformity to TP TC 020 2011 EMC EA C No RU US PA01 B 50006 RUSSIA VNIIPO CERTIF...

Страница 20: ...95 8723 Corporate Office 6901 West 110th Street Minneapolis MN 55438 USA www det tronics com All trademarks are the property of their respective owners 2019 Detector Electronics Corporation All rights...

Отзывы: