95-8723

8

3.4

WIRING PROCEDURE

Ensure that all cables are terminated properly.  

Conductor insulation should be stripped off 

with a bare conductor length of 0.2 inch (5 mm) 

minimum and 0.7 inch (18 mm) maximum.  Ensure 

that cable shield is properly terminated and that 

bare shield wire is not allowed to accidentally 

contact the metal housing or any other wire.

Use the following instructions when wiring the 

U5015 detector:
1.  Slightly loosen the three setscrews located 

on the retaining ring (see Figure 7).

2.  Unscrew the retaining ring to gain access 

to the wiring terminals (see Figure 8), and 

complete the installation of the system 

conduit. Feed the external wiring through 

the remaining junction box entry or M25 

to 3/4 inch adapter. When installing the 

junction box, use care not to damage the 

wires and refrain from twisting them.

3.  Connect the external wiring to the 

appropriate terminals. 

 

– Figure 9 shows the wiring terminals.

 

– Figure 10 shows the ground lug 

locations.

 

– Figures 12 and 13 show wiring for single 

detector configurations. 

 

– Figures 14 and 15 show wiring for multiple 

detector configurations. 

4.  Re-install the assembly. Use the alignment 

guide (see Figure 11) to align the retaining 

ring with the junction box.

5.  Screw the retaining ring on to the junction 

box and re-tighten the three setscrews.

RELAY

OUTPUTS

A2683

– mA

– Vin

+ Vin

– Vin

+ Vin

5

4

3

2

1

POWER

SUPPLY &

0-20 mA OUTPUT

P11

P5

NO AUX

COM AUX

NC AUX

NO ALARM

COM ALARM

NC ALARM

COM FAULT

NO FAULT

1

2

3

4

5

6

7

8

Figure 7—Setscrew Location

SET SCREWS (3)

RETAINING RING

Figure 9—U5015 Wiring Terminals

Figure 8—Location of Wiring Terminals

RETAINING RING

WIRING

TERMINALS

Содержание DET-TRONICS SmokeWatch U5015

Страница 1: ...3 4 95 8723 Instructions Det Tronics SmokeWatch Explosion Proof Smoke Detector U5015...

Страница 2: ...ocations 5 Protection Against Moisture Damage 6 Power Supply Requirements 6 Transport Cover 6 Mounting Location Options 6 Mount the Detector 7 Wiring Cable Requirements 7 Jumper 7 Wiring Procedure 8 M...

Страница 3: ...e and allows live maintenance while under power without de classifying the hazardous area The integrated junction box is available in a variety of port configurations for simplified wiring and install...

Страница 4: ...ally open normally closed contacts and normally de energized operation TEMPERATURE RANGE Operating 20 C to 65 C 4 F to 149 F Storage 55 C to 70 C 67 F to 158 F HUMIDITY RANGE 5 to 95 relative humidity...

Страница 5: ...set of terminals and normally open normally closed contacts and normally de energized operation IMPORTANT The auxiliary relay functions as pre alarm 0 to 20 mA Output The U5015 provides a 0 to 20 mA d...

Страница 6: ...passed If the test fails a critical fault will occur If degradation is present and approaching critical levels an advisory fault will occur MANUAL SELF TEST The Manual Self Test function will immedia...

Страница 7: ...n Sulfide and Chlorine are normally present INSTALLATION WARNING All entries must contain appropriately rated plugs or fittings It is required that each plug or fitting be wrench tightened to an appro...

Страница 8: ...e capability for the calculated load Ensure that the selected power supply provides sufficient regulated and filtered output power for the entire system If a back up power system is required a float t...

Страница 9: ...o U5015 is 2000 feet When the U5015 Smoke Detector is mounted remotely using an STB termination box maximum cable length from U5015 to STB is 500 feet WARNING For field connections use wires cables th...

Страница 10: ...4 inch adapter When installing the junction box use care not to damage the wires and refrain from twisting them 3 Connect the external wiring to the appropriate terminals Figure 9 shows the wiring te...

Страница 11: ...the user in the field ROUTINE INSPECTION Regularly scheduled maintenance is not required however the U5015 cover and smoke chamber should be inspected periodically when detectors are located in abnor...

Страница 12: ...M NC ALARM COM FAULT NO FAULT 1 2 3 4 5 6 7 8 Figure 12 Single Detector Wiring 0 20 mA used Relays not used POWER 2 WIRE CLASS B RECEIVING ZONE CHASSIS GROUND GROUND LUG B2685 Control Panel JUMPERS EO...

Страница 13: ...P5 NO AUX COM AUX NC AUX NO ALARM COM ALARM NC ALARM COM FAULT NO FAULT 1 2 3 4 5 6 7 8 RELAY OUTPUTS mA Vin Vin Vin Vin 5 4 3 2 1 POWER SUPPLY 0 20 mA OUTPUT P11 P5 NO AUX COM AUX NC AUX NO ALARM CO...

Страница 14: ...COM AUX NC AUX NO ALARM COM ALARM NC ALARM COM FAULT NO FAULT 1 2 3 4 5 6 7 8 RELAY OUTPUTS mA Vin Vin Vin Vin 5 4 3 2 1 POWER SUPPLY 0 20 mA OUTPUT P11 P5 NO AUX COM AUX NC AUX NO ALARM COM ALARM NC...

Страница 15: ...nction must accompany the returned device or component to assist and expedite finding the root cause of the failure Pack the unit properly Always use sufficient packing material Where applicable use a...

Страница 16: ...alarm signaling Special Conditions For Safe Use X 1 The U5015 is to be installed in locations where the risk of mechanical damage is low 2 Potential electrostatic charging hazard please see instructi...

Страница 17: ...0 General Requirements C22 2 No 60079 1 2016 Explosive atmospheres Part 1 Equipment protection by flameproof enclosures d C22 2 No 60079 11 2014 Electrical apparatus for explosive gas atmospheres Part...

Страница 18: ...ospheres Equip protection by Intrinsic Safety Special Conditions For Safe Use X 1 The U5015 is to be installed in locations where the risk of mechanical damage is low 2 Potential electrostatic chargin...

Страница 19: ...ICATE OF CONFORMITY TO TP TC 012 2011 No TC RU C US BH02 B 00239 1Exd ia IICT4 IP44 T4 Tamb 20 C to 65 C Declaration of Conformity to TP TC 020 2011 EMC EA C No RU US PA01 B 50006 RUSSIA VNIIPO CERTIF...

Страница 20: ...95 8723 Corporate Office 6901 West 110th Street Minneapolis MN 55438 USA www det tronics com All trademarks are the property of their respective owners 2019 Detector Electronics Corporation All rights...

Отзывы: