background image

13

95-8723

3.4

U5015 MODEL MATRIX

MODEL DESCRIPTION

U5015

Explosion Proof Smoke Detector

TYPE

MATERIAL

A

Aluminum (AL)

TYPE

# OF PORTS

1

1 Port

2

2 Port

3

3 Port

4

4 Port

TYPE

THREAD TYPE

N

3/4" NPT

M

M25

TYPE

OUTPUTS

12

0-20 mA, Relay, Non-Latching

13

0-20 mA, Relay, Latching

TYPE

APPROVAL

A

FM/IECEx/CSA

C

CSA

F

FM/IECEx

R

VNIIFTRI (Russia)

DEVICE REPAIR AND RETURN 

The detector is not designed to be repaired in 

the field. If it is determined that the problem is 

caused by an electronic defect, the device must 

be returned to the factory for repair. The sensor 

module is field replaceable in case of dirtiness, 

damage, or failures incurred in the field.

Prior to returning devices, contact the nearest 

local Det-Tronics office so that a Return 

Material Authorization (RMA) number can be 

assigned.  

A written statement describing the 

malfunction must accompany the returned 
device or component to assist and expedite 
finding the root cause of the failure.

Pack the unit properly. Always use sufficient 

packing material. Where applicable, use an 

antistatic bag as protection from electrostatic 

discharge.

NOTE

Det-Tronics reserves the right to apply a 
service charge for repairing returned 
product damaged as a result of improper 
packaging.

Return all equipment via transportation prepaid to 

the factory in Minneapolis.

ORDERING INFORMATION

When ordering, please specify:
U5015 Explosion Proof Smoke Detector
Refer to the U5015 Model Matrix for details 

SPARE PARTS

U5015 Replacement Sensor Module   104286-001

ACCESSORIES

Canned Smoke      

   

000119-008

  

  

       

000119-046

Grease (silicone-free)     

005003-001

Magnet 

       

                  102740-002

Magnet with Extension Pole 

 007739-001

Stop Plug, 3/4" NPT, AL                    101197-001

Stop Plug, M25, AL 

   

 101197-005

Q5016-1 Duct Mount w/ 1 ft. tube  013901-001

Q5016-3 Duct Mount w/ 3 ft. tube  013901-003

Q5016-6 Duct Mount w/ 6 ft. tube  013901-006

Q5016-10 Duct Mt. w/ 10 ft. tube  013901-010

Содержание DET-TRONICS SmokeWatch U5015

Страница 1: ...3 4 95 8723 Instructions Det Tronics SmokeWatch Explosion Proof Smoke Detector U5015...

Страница 2: ...ocations 5 Protection Against Moisture Damage 6 Power Supply Requirements 6 Transport Cover 6 Mounting Location Options 6 Mount the Detector 7 Wiring Cable Requirements 7 Jumper 7 Wiring Procedure 8 M...

Страница 3: ...e and allows live maintenance while under power without de classifying the hazardous area The integrated junction box is available in a variety of port configurations for simplified wiring and install...

Страница 4: ...ally open normally closed contacts and normally de energized operation TEMPERATURE RANGE Operating 20 C to 65 C 4 F to 149 F Storage 55 C to 70 C 67 F to 158 F HUMIDITY RANGE 5 to 95 relative humidity...

Страница 5: ...set of terminals and normally open normally closed contacts and normally de energized operation IMPORTANT The auxiliary relay functions as pre alarm 0 to 20 mA Output The U5015 provides a 0 to 20 mA d...

Страница 6: ...passed If the test fails a critical fault will occur If degradation is present and approaching critical levels an advisory fault will occur MANUAL SELF TEST The Manual Self Test function will immedia...

Страница 7: ...n Sulfide and Chlorine are normally present INSTALLATION WARNING All entries must contain appropriately rated plugs or fittings It is required that each plug or fitting be wrench tightened to an appro...

Страница 8: ...e capability for the calculated load Ensure that the selected power supply provides sufficient regulated and filtered output power for the entire system If a back up power system is required a float t...

Страница 9: ...o U5015 is 2000 feet When the U5015 Smoke Detector is mounted remotely using an STB termination box maximum cable length from U5015 to STB is 500 feet WARNING For field connections use wires cables th...

Страница 10: ...4 inch adapter When installing the junction box use care not to damage the wires and refrain from twisting them 3 Connect the external wiring to the appropriate terminals Figure 9 shows the wiring te...

Страница 11: ...the user in the field ROUTINE INSPECTION Regularly scheduled maintenance is not required however the U5015 cover and smoke chamber should be inspected periodically when detectors are located in abnor...

Страница 12: ...M NC ALARM COM FAULT NO FAULT 1 2 3 4 5 6 7 8 Figure 12 Single Detector Wiring 0 20 mA used Relays not used POWER 2 WIRE CLASS B RECEIVING ZONE CHASSIS GROUND GROUND LUG B2685 Control Panel JUMPERS EO...

Страница 13: ...P5 NO AUX COM AUX NC AUX NO ALARM COM ALARM NC ALARM COM FAULT NO FAULT 1 2 3 4 5 6 7 8 RELAY OUTPUTS mA Vin Vin Vin Vin 5 4 3 2 1 POWER SUPPLY 0 20 mA OUTPUT P11 P5 NO AUX COM AUX NC AUX NO ALARM CO...

Страница 14: ...COM AUX NC AUX NO ALARM COM ALARM NC ALARM COM FAULT NO FAULT 1 2 3 4 5 6 7 8 RELAY OUTPUTS mA Vin Vin Vin Vin 5 4 3 2 1 POWER SUPPLY 0 20 mA OUTPUT P11 P5 NO AUX COM AUX NC AUX NO ALARM COM ALARM NC...

Страница 15: ...nction must accompany the returned device or component to assist and expedite finding the root cause of the failure Pack the unit properly Always use sufficient packing material Where applicable use a...

Страница 16: ...alarm signaling Special Conditions For Safe Use X 1 The U5015 is to be installed in locations where the risk of mechanical damage is low 2 Potential electrostatic charging hazard please see instructi...

Страница 17: ...0 General Requirements C22 2 No 60079 1 2016 Explosive atmospheres Part 1 Equipment protection by flameproof enclosures d C22 2 No 60079 11 2014 Electrical apparatus for explosive gas atmospheres Part...

Страница 18: ...ospheres Equip protection by Intrinsic Safety Special Conditions For Safe Use X 1 The U5015 is to be installed in locations where the risk of mechanical damage is low 2 Potential electrostatic chargin...

Страница 19: ...ICATE OF CONFORMITY TO TP TC 012 2011 No TC RU C US BH02 B 00239 1Exd ia IICT4 IP44 T4 Tamb 20 C to 65 C Declaration of Conformity to TP TC 020 2011 EMC EA C No RU US PA01 B 50006 RUSSIA VNIIPO CERTIF...

Страница 20: ...95 8723 Corporate Office 6901 West 110th Street Minneapolis MN 55438 USA www det tronics com All trademarks are the property of their respective owners 2019 Detector Electronics Corporation All rights...

Отзывы: