Parameter Name
Units or Options
Range
Description
TC RAMP
0, 30, 45, 60
Ramp rate in
seconds
0 disables ramp function. Ramp is
a sawtooth with ramp from offset
to span and drop back to offset.
TC OFFSET
In F of C scale
depending on
TEMP SCALE
selection
32-5432°F
Or
0-3000°C
This is the minimum value the
ramp function. Default is minimum
of selected TC type. Updated only
when TC type changes.
TC SPAN
In F of C scale
depending on
TEMP SCALE
selection
32-5432°F
Or
0-3000°C
This is the maximum value the
ramp function. Default is
maximum of selected TC type.
Updated only when TC type
changes.
MV RAMP
0, 30, 45, 60
Ramp rate in
seconds
0 disables ramp function. Ramp is
a sawtooth with ramp from offset
to span and drop back to offset.
MV OFFSET
Starting value on
mV signal for ramp
output.
0 – 2000mV
This is the minimum value of the
ramp function. Default for carbon
and dewpoint is 1000mV, 0mV for
oxygen process.
MV SPAN
Maximum value of
ramp
0 – 2000mV
This is the maximum value the
ramp function. Default for carbon
and dewpoint is 1800, 80mV for
oxygen.
Info
General Information with diagnostic information.
Info Menu
Parameter
Name
Units or Options
Range
Description
MILLIVOLT
TEMP IN
MILLIVOLTS
0 to 100
Displays direct mV of
Temperature input. Shows 0 if
mode is set to output.
COLD
JUNCTION
DEG (F OR C)
-20 to 255°F
-29 to 124°C
Displays actual cold junction
temperature
PROB
IMPEDANCE
Kohms
0 to 255
Displays last probe impedance
value.
IMP RECVRY
TIME
SECONDS
0 to 250
Displays last impedance
recovery time.
FIRMWARE
REV
Version number
Refer to this number prior to
service.
SERIAL
NUMBER
Serial Number
Refer to this number when
returning the device for service