Sequence Of Operation
Cooling Sequence Of Operation
1�
Before starting the unit, make sure electrical power
has been turned on for a minimum of 24 hours� This
assures that any liquid refrigerant is “driven” out of the
crankcase�
2�
For water-cooled units, make sure condenser water is
available� Open all shut off valves and make sure all
air is purged from the water circuit� Verify that cooling
tower is functioning, if this is the source of condensing
water supply� Start circulating the water to the water
condenser�
3�
The following sequence is based on the unit being
controlled by a room thermostat� If another control
type is being utilized, reference the instructions for that
device may be required�
a�
Raise thermostat setpoint to highest level�
b�
Set System switch to “OFF” position�
c�
Set Fan switch to the “AUTO” position�
d�
Moving the Fan switch to the “ON” position should
cause the evaporator blower motor to run� Moving
the Fan Switch back to “AUTO” should stop the
blower�
e�
Move the System switch to the “COOL” position�
Slowly lower the thermostat setting to call for
cooling� The evaporator blower should start
(assuming the Fan switch is set to “AUTO”) and the
System No� 1 compressor should start�
f�
On those units with multiple compressors, if the
thermostat setpoint continues to be lowered, the
second compressor should then start�
g�
Set room thermostat at desired space temperature
and the Fan switch to “AUTO” or “ON”� The unit will
cycle as required to maintain conditions�
4�
Chilled water sequence is the same as above, except
compressor activation is replaced by the chilled water
valve function�
5�
Heat pump cooling sequence is the same as above,
except the reversing valve will also be activated when
the compressor cycle is started�
Heating Sequence Of Operation
(Other Than Heat Pump)
1�
The following sequence is based on the unit being
controlled by a room thermostat� If another control
type is being utilized, reference the instructions for that
device may be required�
a�
Lower thermostat setpoint to the lowest level�
b�
Set System switch to “OFF” position�
c�
Set Fan switch to “AUTO” position�
d�
Moving the Fan switch to the “ON” position should
cause the evaporator blower motor to run� Moving
the Fan switch back to “AUTO” should stop the
blower�
e�
Move the System switch to the “HEAT” position�
Slowly raise the thermostat setting to call for
heating� The evaporator blower should start
(assuming the Fan switch is set to “AUTO”) and the
electric heating element will be activated�
f�
On those units with a second stage of electric heat,
if the thermostat setpoint continues to be raised,
the second stage of electric heat should then be
activated�
INFORMATION
NOTE: Units with more than one stage
of electric heat require a two stage heat
thermostat�
g�
Set room thermostat at desired space temperature
and set the Fan switch to “AUTO” or “ON”� The unit
will cycle as required to maintain conditions�