background image

Installation, Operation and Maintenance Manual

C13-Series

18

Subject to change without notice.

10.20-IM (0818)

Belts

Drive belts should be examined periodically for wear and 

for correct tension� Belts that are too tight cause bearing 

wear while belts that are too loose cause slippage� If the 

midpoint (midway between the blower and motor shaft) of 

the  belt  is  pressed  inward,  there  should  be  about  1/2"  to 

a 1" of deflection when the belt is properly tensioned. Belt 

tension can be adjusted by means of the adjusting bolt, 

which requires loosening of a nut to move the motor and 

change belt position�

Refrigerant Systems

All United CoolAir systems contain a liquid line sightglass� 

If bubbles appear in the sightglass, the system is either 

undercharged with refrigerant or there may be a restriction in 

the liquid line upstream of the sightglass� However, bubbles 

will appear every now and then in units with the hot gas 

bypass option� Bubbles will also appear upon compressor 

start up but normally clear to pure liquid after a few minutes 

of operation�
The sightglass contains a moisture indicator which changes 

color when moisture is present in the system� This indicator 

is the circular dot in the center of the sight glass� If the color 

of this indicator is green, the refrigerant is normal� When 

the indicator is yellow, an abnormal condition exists such 

as moisture within the refrigerant circuit� If an abnormal 

appearance exists, servicing is required� See Figure 10 for 

unit charges�

INFORMATION

NOTE: After installation and during 

equipment start-up, the sight glass may 

appear pink or purple� This occurs during 

prolonged periods of non-operation and 

should turn blue after several hours (up to 

12) of operation�

Evaporator And Air-Cooled 

Condenser Coils

Check semi-monthly the condition of the face of both the 

evaporator and condenser coils�
A dirty condenser coil will cause high condensing pressures, 

resulting in higher power consumption and possibly system 

shut-down by high-pressure
safety control� A dirty evaporator coil will reduce unit capacity 

and eventually will cause shut-down by the low pressure 

safety control�

Minimum Service Access

All Service and Maintenance access is through both sides of 

the unit. 36" clearance is required.

Application Data

208 / 230

460

Voltage Variation

187 / 253

414 / 504

Cooling  

(Air Over Evap.)

DB (Min./Max.)

45 / 120

WB (Min./Max.)

57 / 72

Heat Pump  

(Air Over ID Coil)

DB (Min./Max.)

50 / 80

Water-Cooled

GPM/Ton (Min./Max.)

2.5 / 3.5

Leaving Water Temp. 

(Min./Max.)

60 / 115

Hard Start Kit

A start assist device is utilized on all single-phase units� The 

purpose of this device is to assist the compressor in starting 

under low voltage conditions�
A capacitor in conjunction with a Positive Temperature 

Coefficient  (PTC)  relay  is  installed  across  the  run  and 

start windings of the motor� The PTC device utilizes a 

ceramic element with a predictable thermal response to 

the introduction of electric current� When the compressor is 

called upon to start, the start capacitor provides a voltage 

boost to the start winding of the motor and causes the motor 

to turn� As the starting current is introduced across the start 

windings, the PTC element begins to warm� When the PTC 

device reaches approximately 250°F (corresponding to 0�6-

0�8 seconds), the resistance in the element increases and 

creates an open switch that releases the start winding from 

the circuit and the motor continues to run� If the compressor 

does not start before the device heats to 250°F, it will not 

start until the PTC device cycles through a cool-down 

period (usually 2-3 minutes)� A compressor off-cycle timer is 

included in the electrical circuit for this purpose�
The time delay relay also helps the refrigerant system 

pressures to equalize at the end of the run cycle� This helps 

the compressor during the starting process in that it is not 

attempting to start against a high discharge pressure�

INFORMATION

The installer should verify that this timer is 

set for 3 or more minutes�

Содержание C13-Series

Страница 1: ...C13 Series Installation Operation and Maintenance Manual Effective August 2018 Horizontal Air Cooled Water Cooled Chilled Water and Heat Pump ...

Страница 2: ......

Страница 3: ...Operation Other Than Heat Pump 19 Heat Pump Heating Sequence Of Operation 20 Options 20 Condensate Pump 20 Thermostat 21 Checking Hot Gas Bypass Valve 21 Adjustment Of Hot Gas Bypass Valve 22 Microprocessor Controller 22 Humidifier 22 Electric Heat 22 Electric Reheat 22 Steam Coil 22 Hot Water Coils 23 Flooded Condenser 23 Buck Boost Transformer 23 Chilled Water Valves Or Hot Water Valves 24 Head ...

Страница 4: ...oll to the footer section or Home industry resources enter your serial number in the Serial Search field and press return to retrieve your product wiring diagram Your serial number is a combination of the year month and sequential order of build date This action will return the Model number Job Number and the wiring diagram for viewing as well as downloading NOTE Only units shipped since November ...

Страница 5: ... minor or moderate injury if not avoided The information icon indicates a situation that may result in equipment or property damage The information provided alerts the reader to relevant facts and or conditions ELECTRICAL HAZARD WARNING CAUTION INFORMATION This publication includes warnings cautions and information icons that point out safety related issues or conditions as well as other pertinent...

Страница 6: ...ap Supply Air Cond Air Out Elect Box Coil Access Panel Coil Access Panel Motor Blower Access Panel Motor Blower Access Panel Elect Box Condensing Section Service Clearance All Sizes Left Side 36 Right Side 36 Tons A B C D E F G H J K L M N P Q R S T V W X Y Z AA AB AC AD 2 3 78 56 22 44 34 119 16 20 1 59 7 25 1011 16 91 16 3 57 40 1 30 91 16 3 24 35 16 13 119 16 7 111 16 19 4 5 86 64 25 46 40 13 9...

Страница 7: ...Control Wiring Evap Return Air Evap Supply Air Elect Box Elect Box Coil Access Panel Motor Blower Access Panel Compressor Access Panel Cond Section Service Clearance All Sizes Left Side 36 Right Side 36 Tons B C E F G H J K L M N P Q R S T W AE AF AG AH AJ AK Water Piping In Out 2 3 56 22 34 119 16 20 1 59 7 25 1011 16 91 16 3 57 40 1 30 3 50 16 12 6 91 8 13 Ø 4 5 64 25 40 13 9 16 25 0 67 81 16 31...

Страница 8: ...he unit to accommodate maintenance and servicing This minimum clearance must be 36 for all units Attention must also be given to floor ceiling or wall load limitations See Figure 2 Location should also provide for condensate removal trapping and disposal Discharge Air from condenser coil should be deflected away from supply air to condenser to prevent recirculation See also Condensing Section Outd...

Страница 9: ...rounded using the ground lug provided in the electrical box Metal conduit is not an acceptable ground h Run the low voltage wiring from the thermostat to the unit Connect to low voltage terminal block supplied See Thermostat under Options page 20 Wire Size1 AWG Gauge 22 20 19 18 16 40 120 150 190 305 Maximum Wire Length2 Feet Note 1 Solid Class II copper wire 2 Based on a voltage drop of 1 2 volts...

Страница 10: ...e rails attached to the unit mounting rails on each side of the unit 7 Carefully pull the evaporator section away from the condensing section 8 Verify that the self sealing couplings are completely disengaged and not leaking refrigerant The sections may now be moved to their individual locations for installation either floor mounted or hung Interconnecting Refrigerant Tubing After the separated se...

Страница 11: ...lied The interconnect kit also contains four 4 Schrader fittings The installer can place at least one in each refrigerant line or at the end of the refrigerant line These enable the refrigerant line to be evacuated and charged as needed based on size and length In some situations the desired refrigerant line size may differ from the self sealing fitting size provided The line size should be reduce...

Страница 12: ... components 6 Install the Schrader valve fittings into the tubing before brazing the couplings onto the ends of the tubing Use a 1 4 hole to mount the valve Clean and debur the tubing before doing any brazing to ensure that no chips or debris are left in the refrigerant circuit Remove the Schrader valve cap and core before doing any brazing 7 Leak check line sets with nitrogen at 500 psig After br...

Страница 13: ...experienced Duct Connection It is recommended to use a flex collar or other means to isolate any unit vibration from being transmitted to the duct or structure Ductwork and plenums shall be insulated in accordance with applicable ASHRAE standards or local codes Pressure Switches High Pressure This switch shuts the unit down in the event of excessive high pressure in the discharge line A manual res...

Страница 14: ...not use for brackish water or salt water unless appropriate condenser has been installed as an option Condensate Drain Connection Units are equipped with two 3 4 IPS drains one for the evaporator condensate one for the condensing section All units require evaporator section drains to be installed Heat pumps and water cooled condensing units also always require the installation of a condensing sect...

Страница 15: ... However there are several other commercially available environmentally safe products on the market that will do an excellent job Contact your local wholesaler for availability Follow all safety guidelines published by the cleaner manufacturer There is a safety concern whenever using any chemical cleaner at elevated temperatures The cleaner manufacturers recommend using the cleaners at 120 F or lo...

Страница 16: ...es and tank from heat exchanger 13 Flush entire water system with water 14 Return heat exchanger and system components to service Check all valves and fitting connections 15 Record performance values Before After Pressure Drop_____________Psig ____________ Psig Entering Temp _____________ F ____________ F Leaving Temp ______________ F ____________ F Blowers Disconnect power and lockout service bef...

Страница 17: ... air flow may result in excessive condensation at air outlets short cycling or total unit shutdown due to evaporator coil icing INFORMATION Verify that the motor current draw does not exceed the motor nameplate current by more than 10 Blower Motor Lubrication Motor manufacturers indicate that motors never need re lubrication but if units run continuously it is recommended that they be re lubricate...

Страница 18: ...igh condensing pressures resulting in higher power consumption and possibly system shut down by high pressure safety control A dirty evaporator coil will reduce unit capacity and eventually will cause shut down by the low pressure safety control Minimum Service Access All Service and Maintenance access is through both sides of the unit 36 clearance is required Application Data 208 230 460 Voltage ...

Страница 19: ...red the second compressor should then start g Set room thermostat at desired space temperature and the Fan switch to AUTO or ON The unit will cycle as required to maintain conditions 4 Chilled water sequence is the same as above except compressor activation is replaced by the chilled water valve function 5 Heat pump cooling sequence is the same as above except the reversing valve will also be acti...

Страница 20: ... at desired space temperature Set the Fan switch to AUTO or ON The unit will cycle as required to maintain conditions Options Condensate Pump If an optional condensate pump is to be used it will be mounted external to the unit The pump incorporates mounting tabs for securing the pump in a suitable location If the unit is an air source heat pump the unit drains from the evaporator and the condensin...

Страница 21: ...he suction line 3 Connect a high pressure refrigerant gauge to the liquid line 4 Operate air conditioner in the cooling mode until system is stabilized Approximately 15 minutes 5 If the high side pressure is not at or above 400 psig block off the condenser inlet air stream until the pressure is above this threshold This will simulate a system performance level close to the design condition of 95 F...

Страница 22: ...unctions on the electrode principle As water fills the plastic steam generator it immerses metal electrodes which then permits electrical current flow through the water This current flow produces heat which then boils the water into steam This steam is then injected on the downstream side of the cooling coil to provide humidification for the area being served by the unit Water is replenished throu...

Страница 23: ...the condenser This raises the condenser pressure Since it is the receiver pressure that is being maintained the valve will then start to throttle open the discharge port when the differential between the condensing pressure and the receiver pressure exceeds 20 psi The hot discharge gas serves to heat up the cold liquid being passed from the condenser to the receiver Thus the liquid reaches the rec...

Страница 24: ... located in the space being conditioned and if the enthalpy conditions are satisfied as sensed by the economizer module the outdoor air provided for cooling the space could be from a small portion up to 100 total air flow of outdoor air The determination of how much outdoor air to use for cooling is determined by additional sensors that monitor mixed and discharge air temperatures These additional...

Страница 25: ...on REAR LEFT RIGHT Refrigerant Quick Connects Field Installation Power Control Wiring Elect Box Motor Blower Access Panel Clearance Hole for Hanging Rod Typ 8 Pls Optional HGR Optional HGR Suction Optional HGR Liquid Suction Optional HGR Liquid Service Clearance All Sizes Left Side 36 Right Side 36 Optional HGR Optional HGR Suction Optional HGR Liquid Optional HGR Optional HGR Suction Optional HGR...

Страница 26: ...ndensing section for location in small spaces Evaporator discharge air is available through the front or top for easy duct installation INFORMATION NOTE For other sheet metal arrangements contact your local sales office A rigid frame system supports the evaporator and provides vibration free operation Quick connect couplings allow the unit to be split in the field if needed for installation The in...

Страница 27: ... Field Installation Power Control Wiring RIGHT LEFT Clearance Hole for Hanging Rod Typ 8 Pls Service Clearance All Sizes Left Side 36 Right Side 36 TONS B C D E F G H J K L M N P 2 3 56 22 44 34 115 16 20 1 59 7 25 1011 16 91 16 3 4 5 64 25 46 40 139 16 25 0 67 81 16 31 12 91 16 3 6 8 70 32 63 45 18 31 73 65 8 39 161 16 613 16 15 8 TONS Q R S T V X Y Z AA AB AC AD AM 2 3 57 40 1 30 91 16 24 35 16 ...

Страница 28: ... recharge refrigerant system Check condenser for obstructions and remove Check for the required water flow through the water regulating valve and the condenser coil Manually reset thermostat With Marvel turn off alarm and reset Wait for PTCR to cool off Compressor should start in 3 5 minutes Stop unit and troubleshoot power supply and compressor circuit for low voltage Please note that it may take...

Страница 29: ...d compressor bearings Liquid slugging Excessive head pressure Ensure thermal expansion valve bulb is tight on suction line Con firm that bulb is located properly on suction line Check operation and superheat Replace compressor Replace compressor System overcharged Reclaim excess refrigerant from the high side of the system Reduce head pressure see item 8 below 7 System short of capacity Flash gas ...

Страница 30: ...d 10 Suction pressure too low Flash gas in liquid line bubbles in sight glass due to a leak Obstructed expansion valve Loss of fluid within expansion valve bulb Clogged filter drier Ice or dirt on evaporator coil Evaporator blower running backwards Repair leak and recharge Repair or replace valve Replace power head and valve Replace with new filter drier Defrost and clean evaporator coil and repla...

Страница 31: ...e freely Dirt or algae not allowing float to activate pump Locate and repair electrical connection problem Clean pump and float Clean pump and float 15 Condensate Pump runs with no discharge Tubing blocked or kinked Check valve blocked Inpeller blocked Tubing elevation or run exceeds head capability Inspect clean or straighten as necessary Clean check valve Remove debris from pump impeller Verify ...

Страница 32: ...de of condenser and evaporator 9 Damages resulting from I freezing of condenser water or condensate II use of corrosive water III fouling or restriction of the air water circuit by foreign material or like causes 10 Damages resulting from operation with inadequate or interrupted supply of air or water 11 Damages resulting from use of components or accessories not approved by United CoolAir 12 This...

Страница 33: ...or like causes 10 Damages resulting from operation with inadequate or interrupted supply of air or water 11 Damages resulting from use of components or accessories not approved by United CoolAir 12 This warranty does not apply to the installation plumbing and wiring not integral to the product 13 Damages resulting from improper application or sizing This warranty is in lieu of all other warranties...

Страница 34: ...ir 12 This warranty does not apply to the installation plumbing and wiring not integral to the product 13 Damages resulting from improper application or sizing of unit 14 In the event that the refrigerant type is changed as a result of a compressor failure and the same type of compressor is not available any subsequent refrigerant circuit component failures will not be covered under the Limited Wa...

Страница 35: ...sories not approved by United CoolAir 12 This warranty does not apply to the installation plumbing and wiring not integral to the product 13 Damages resulting from improper application or sizing 14 Discharge air temperature control if not provided by the factory will void the compressor Limited Warranty 15 In the event that the refrigerant type is changed as a result of a compressor failure and th...

Страница 36: ...ooded condenser option the scroll compressors will have crankcase heaters If the outdoor ambient is 70 F or lower let the compressors sit for approximately 24 hours before proceeding 12 Record the voltage at the unit terminals 13 If possible with the thermostat provided switch the evaporator blower to the RUN position Verify that the evaporator blower is activated 14 Verify that the evaporator blo...

Страница 37: ...ressures on each compressor circuit are within the proper limits i 290 550 Discharge ii 100 140 psig Suction b Compressor Amperage is below the RLA Amps listed on the unit data tag i The maximum compressor operating current amps at start up depends a lot on the system loading The lower the load the less the current The higher the load the higher the current c The blower motor FLA values should nev...

Страница 38: ...act the Distributor Is the Circuit Protection the correct type and does it meet the unit data tag requirements Yes ____________ No ____________ If not correct describe what action s have been taken to correct Unit controller wiring verified Yes ____________ No ____________ C Terminal hooked up if necessary Yes ____________ No ____________ Unit leak checked OK Yes ____________ No ____________ If le...

Страница 39: ..._______ F_________ F_________ F_________ Sub cooling _________ _________ Electrical Evap Motor Amps L1_____________ L2____________ L3_____________ Compressor 1 Amps L1_____________ L2____________ L3_____________ Compressor 2 Amps L1_____________ L2____________ L3_____________ Cond Motor Amps L1_____________ L2____________ L3_____________ Heating Mode Optional System Air Temperatures Return F _____...

Страница 40: ...for approximately 24 hours before proceeding 12 Record the voltage at the unit terminals 13 If possible with the thermostat provided switch the evaporator blower to the RUN or ON position Verify that the evaporator blower is activated 14 Verify that the evaporator blower is rotating in the correct direction three phase units only Note If the evaporator blower motor runs backwards shut off all powe...

Страница 41: ...ding to the liquid line pressure 32 Calculate and record the liquid sub cooling for each circuit by taking the difference between the liquid line temperature and the saturation temperature corresponding to the liquid line pressure 33 Record the Amps for the evaporator blower motor and each compressor If the system is single phase use L1 and L2 only a Make sure the pressures on each compressor circ...

Страница 42: ... Is the Circuit Protection the correct type and does it meet the unit data tag requirements Yes ____________ No ____________ If not correct describe what action s have been taken to correct Unit controller wiring verified Yes ____________ No ____________ C Terminal hooked up if necessary Yes ____________ No ____________ Unit leak checked OK Yes ____________ No ____________ If leak was located desc...

Страница 43: ...sor 2 Suction Pressure Suction Line Temperature psi________ F_________ psi________ F_________ Saturation Temperature F_________ F_________ Suction Superheat _________ _________ Liquid Line Pressure psi________ psi________ Saturation Temperature Liquid Line Temperature F_________ F_________ F_________ F_________ Sub cooling _________ _________ Electrical Evap Motor Amps L1_____________ L2__________...

Страница 44: ...nit 2 thru 8 Tons MW Water Cooled MagnaCool Unit 2 thru 8 Tons CCW Chilled Water Unit 2 thru 8 Tons E Evaporator Section only of the unit 2 thru 8 Tons can be a prefix for some of the above B Condensing Section only of the unit 2 thru 8 Tons BC Condenser Section only of the unit 2 thru 8 Tons b 2 3 4 5 6 8 Nominal Cooling Capacity in Tons c G Common to all d 1 3 4 or 5 Indicates Voltage 1 208 230V...

Страница 45: ... on the compressor labor not included Maintenance items such as filters and belts are excluded under this limited warranty FACTORY TESTED All units are functionally run tested before shipment to ensure a trouble free start up and unit commissioning Industry proven components are used throughout to enhance system reliability and peace of mind VertiCool Classic Vertical 3 30 Ton VertiCool Aurora Ver...

Отзывы: