UT-201

UNIVERSAL PROCESS INDICATOR & CONTROLLER

9

‘Setup Mode’ Mode will shown by pressing        key, after 

Conf 

Mode display.

4.2       Setup Mode

sp3
sp4

Hys3
Hys4

 

Range / Values

Parameter

pass
0000

SETUP MODE PASSWORD

Password for Setup Mode Parameters

Display

Scroll the digit by        key, Increase by        key.

Range  :  Values between 

0000

 to 

9999

Default Value  :  

0000

ZRC1

000.0

CH:1 ZERO or LOW DISPLAY VALUE [LINEAR I/P]

Display value at Low Input applied.

NOTE :

 Applicable for Analog Linear input only.

Scroll the digit by        key, Increase by        key.

 

Range  :  Values between 

1999

 to 

9999

Default Value  :  

000.0

-

Scroll the digit by        key, Increase by        key.

 

Range  :  Values between 

1999

 to 

9999

Default Value  :  

100.0

-

spC1

100.0

CH:1 SPAN or HIGH DISPLAY VALUE [LINEAR I/P]

Display value at High Input applied.

NOTE :

 Applicable for Analog Linear input only.

Scroll the digit by        key, Increase by        key.

 

Range  :  Values between 

199.9

 to 

999.9

Default Value  :  

030.0

-

sp1

030.0

ALARM SET POINT # 1

Activation value for Alarm Relay-1

Scroll the digit by        key, Increase by        key.

 

Range  :  Values between 

199.9

 to 

999.9

Default Value  :  

000.2

-

Hys1

000.2

HYSTERESIS ALARM # 1

Value Diff. between On and Off of Relay-1

Scroll the digit by        key, Increase by        key.

 

Range  :  Values between 

199.9

 to 

999.9

Default Value  : As per User’s set Reqd.

-

ALARM SET POINT # 3 & 4

Activation value for Alarm Relay-3 & 4

Scroll the digit by        key, Increase by        key.

 

Range  :  Values between 

199.9

 to 

999.9

Default Value  :  

000.2

-

HYSTERESIS ALARM # 3 & 4

Value Diff. between On and Off of Relay-3 & 4

(According to Decimal point)

(According to Decimal point)

(According to Decimal point)

(According to Decimal point)

(According to Decimal point)

(According to Decimal point)

 

HYS2

sp2

Scroll the digit by        key, Increase by        key.

 

Range  :  Values between 

199.9

 to 

999.9

Default Value  : As per User’s set Reqd.

-

ALARM SET POINT & HYSTERESIS # 2

Activation value & Hysteresis for Alarm Relay-2

 

(According to Decimal point)

&

 

ZRC2

000.0

CH:2 ZERO or LOW DISPLAY VALUE [LINEAR I/P]

Display value at Low Input applied.

NOTE :

 Applicable for Analog Linear input only.

Scroll the digit by        key, Increase by        key.

 

Range  :  Values between 

1999

 to 

9999

Default Value  :  

000.0

-

Scroll the digit by        key, Increase by        key.

 

Range  :  Values between 

1999

 to 

9999

Default Value  :  

100.0

-

spC2

100.0

CH:2 SPAN or HIGH DISPLAY VALUE [LINEAR I/P]

Display value at High Input applied.

NOTE :

 Applicable for Analog Linear input only.

(According to Decimal point)

(According to Decimal point)

Содержание UT-201

Страница 1: ...utplindia in www Model No UT 201 DUAL CHANNEL UNIVERSAL PROCESS INDICATOR CONTROLLER INSTRUCTION MANUAL M 96 x 96 Flame Proof UT 201 M COM www utplindia in RL 2 RL 1 RL 4 RL 3 201 0 201 0 UT 201 M COM...

Страница 2: ...ts Applying 240V AC to a controller rated for 12 24VDC will severely damage the controller and is a fire and smoke hazard This controller is suitable for connection to 230 15 VAC 50 Hz or 12 24 VDC po...

Страница 3: ...GRAMMING 3 1 OPERATION INTERFACE 3 2 MODE ACCESS FLOW CHART 4 1 CONFIGURATION MODE 4 OPERATIONAL MODES 4 2 SETUP MODE 4 3 CALIBRATION MODE 4 4 CHANGE PASSWORD MODE 4 5 ERROR MESSAGE 5 COMMUNICATION MO...

Страница 4: ...can do any change in the mode Two different configuration levels provide easy access to parameters A4 digit security code perverts una uthorized changes Parameters can also be hidden to user to preve...

Страница 5: ...ND 0 1 of Full Scale Automatic Software based self compensation Cold Junction Comp OPEN or OVER indication on display Sensor Break Info AS per Input Range Table Range Limits 330 K for Voltage mV and T...

Страница 6: ...0 21 B A 4 20mA 0 20mA CURRENT mA 22 21 0 VDC 5 10 V VOLTAGE 21 22 23 3 WIRE 21 22 9 8 T mA Input TPS 24VDC Transmi er TRANSMITTER 2 WIRE 21 22 9 8 T mA Input TPS 24VDC Transmi er TRANSMITTER OUTPUT R...

Страница 7: ...ey allows enter into the Parameter moving from one parameter to another or saving a new value of parameter or a status of parameter Press to change set points in normal view UP KEY UP Key allows incre...

Страница 8: ...technically competent to do so Local regulations regarding electrical safety must be observed FAILURE TO COMPLY WITH THESE INSTRUCTION COULD BE RESULT IN SERIOUS INJURY OR DEATH Default Password will...

Страница 9: ...the applied Input Change the type Up by key Down by key Range Input Type is as follows TC 4 RTD1 0 20 4 20 10v Default Value 0000 tsp1 L on ALARM 1 RELAY ACTION Alarm Relay activation direction Values...

Страница 10: ...key Decrease by key dp2 0001 CHANNEL 2 DECIMAL POINT LINEAR INPUT Decimal Point resolution for display value Values Default Value 0001 NOTE Applicable for Analog Linear input only tsp3 tsp4 ALARM 3 4...

Страница 11: ...ue 000 2 Hys1 000 2 HYSTERESIS ALARM 1 Value Diff between On and Off of Relay 1 Scroll the digit by key Increase by key Range Values between 199 9 to 999 9 Default Value As per User s set Reqd ALARM S...

Страница 12: ...ration Span High at Span High PV Input NOTE After Span Cal press key for next para Apply High signal as per input press key Lop1 Lop2 CALIBRATION LOW RETRANSMISSION OUTPUT Calibration desired Low Outp...

Страница 13: ...ontroller Controller circuit failed Check the power connection Check the supply voltage 4 4 Change Password Mode 4 5 Error Message Range Values Parameter PAsS 0000 CHANGE PASSWORD MODE PASSWORD Passwo...

Страница 14: ...stem schematic DATA The system schematic for RS 485 Modbus protocol are as follows DATA Ethernet RS 232 or RS 485 CONVERTER D D 1 2 UT 201 Device 1 D D 1 2 D D 1 2 D D 1 2 RS 485 BUS ADD 1 ADD 2 ADD 3...

Страница 15: ......

Отзывы: