UT-201

UNIVERSAL PROCESS INDICATOR & CONTROLLER

7

‘Configuration Mode’ will shown by pressing        key in the Normal mode..

4.1       Configuration Mode

4.       OPERATIONAL MODES

:  Selected

 YES

:  Not 

  no

DED1

no

CHANNEL:1 DEAD BAND

Operate Relay-1 on two set points

Values  :  

Default Value  :  

no

If set as YES, Only Relay-1 get operated in this 

parameter, relay get active on set point 1[SP1] 

value and deactivate in set point 2[SP2] value. 

Used for Level Control & Fan Operation.

Increase by        key, Decrease by        key.

 

Range / Values

Parameter

pass
0000

CONFIGURATION MODE PASSWORD

Password for Config. Mode Parameters

Display

:  PT-100 (RTD)

:  Linear 0 - 20 mA DC

:  Linear 4 - 20 mA DC

T

TC

S

TC

R

TC

J

TC

:  ‘T’ Type Thermo-Couple

:  ‘S’ Type Thermo-Couple

:  ‘R’ Type Thermo-Couple

:  ‘K’ Type Thermo-Couple

:  ‘J’ Type Thermo-Couple

:  Linear 0 - 10 V DC

Scroll the digit by        key, Increase by        key.

Range  :  Values between 

0000

 to 

9999

Default Input  :  

RtD1

 , It can be change as reqd. 

1nP1
rtd1

CHANNEL:1 INPUT TYPE

Selection of the applied Input.

Change the type Up by        key, Down by        key.

Range  :  Input Type is as follows:

TC

4

RTD1

0-20

4-20

-10v

Default Value  :  

0000

 

tsp1

L on

ALARM 1 RELAY ACTION

Alarm Relay activation direction.

Values  :  

Default Value  :  

L on

:  No decimal      (1234)

0000

:  Active in High

H oN

ON

OFF

PV

SV

ON

OFF

PV

SV

L ON :

:  Active in Low

L oN

H ON :

 

:  One decimal   (123.4)

0001

:  Two decimal   (12.34)

0002

:  Three decimal(1.234)

0003

SV-Hyst

SV+Hyst

Change the value by        key, or by        key.

tsp2

L on

ALARM 2 RELAY ACTION

Alarm Relay activation direction same as AL:1

Values  :  

Default Value  :  

L on

:  Active in High

H oN

:  Active in Low

L oN

Increase by        key, Decrease by        key.

dp1

0001

CHANNEL:1 DECIMAL POINT [LINEAR INPUT]

Decimal Point resolution for display value.

Values  :  

Default Value  :  

0001

NOTE :

 Applicable for Analog Linear input only.

Change the value by        key, or by        key.

 

 

:  PT-100 (RTD)

:  Linear 0 - 20 mA DC

:  Linear 4 - 20 mA DC

T

TC

S

TC

R

TC

J

TC

:  ‘T’ Type Thermo-Couple

:  ‘S’ Type Thermo-Couple

:  ‘R’ Type Thermo-Couple

:  ‘K’ Type Thermo-Couple

:  ‘J’ Type Thermo-Couple

:  Linear 0 - 10 V DC

Default Input  :  

J. TC

 , It can be change as reqd. 

1nP2
rtd1

CHANNEL:2 INPUT TYPE

Selection of the applied Input.

Change the type Up by        key, Down by        key.

Range  :  Input Type is as follows:

TC

4

RTD1

0-20

4-20

-10v

Содержание UT-201

Страница 1: ...utplindia in www Model No UT 201 DUAL CHANNEL UNIVERSAL PROCESS INDICATOR CONTROLLER INSTRUCTION MANUAL M 96 x 96 Flame Proof UT 201 M COM www utplindia in RL 2 RL 1 RL 4 RL 3 201 0 201 0 UT 201 M COM...

Страница 2: ...ts Applying 240V AC to a controller rated for 12 24VDC will severely damage the controller and is a fire and smoke hazard This controller is suitable for connection to 230 15 VAC 50 Hz or 12 24 VDC po...

Страница 3: ...GRAMMING 3 1 OPERATION INTERFACE 3 2 MODE ACCESS FLOW CHART 4 1 CONFIGURATION MODE 4 OPERATIONAL MODES 4 2 SETUP MODE 4 3 CALIBRATION MODE 4 4 CHANGE PASSWORD MODE 4 5 ERROR MESSAGE 5 COMMUNICATION MO...

Страница 4: ...can do any change in the mode Two different configuration levels provide easy access to parameters A4 digit security code perverts una uthorized changes Parameters can also be hidden to user to preve...

Страница 5: ...ND 0 1 of Full Scale Automatic Software based self compensation Cold Junction Comp OPEN or OVER indication on display Sensor Break Info AS per Input Range Table Range Limits 330 K for Voltage mV and T...

Страница 6: ...0 21 B A 4 20mA 0 20mA CURRENT mA 22 21 0 VDC 5 10 V VOLTAGE 21 22 23 3 WIRE 21 22 9 8 T mA Input TPS 24VDC Transmi er TRANSMITTER 2 WIRE 21 22 9 8 T mA Input TPS 24VDC Transmi er TRANSMITTER OUTPUT R...

Страница 7: ...ey allows enter into the Parameter moving from one parameter to another or saving a new value of parameter or a status of parameter Press to change set points in normal view UP KEY UP Key allows incre...

Страница 8: ...technically competent to do so Local regulations regarding electrical safety must be observed FAILURE TO COMPLY WITH THESE INSTRUCTION COULD BE RESULT IN SERIOUS INJURY OR DEATH Default Password will...

Страница 9: ...the applied Input Change the type Up by key Down by key Range Input Type is as follows TC 4 RTD1 0 20 4 20 10v Default Value 0000 tsp1 L on ALARM 1 RELAY ACTION Alarm Relay activation direction Values...

Страница 10: ...key Decrease by key dp2 0001 CHANNEL 2 DECIMAL POINT LINEAR INPUT Decimal Point resolution for display value Values Default Value 0001 NOTE Applicable for Analog Linear input only tsp3 tsp4 ALARM 3 4...

Страница 11: ...ue 000 2 Hys1 000 2 HYSTERESIS ALARM 1 Value Diff between On and Off of Relay 1 Scroll the digit by key Increase by key Range Values between 199 9 to 999 9 Default Value As per User s set Reqd ALARM S...

Страница 12: ...ration Span High at Span High PV Input NOTE After Span Cal press key for next para Apply High signal as per input press key Lop1 Lop2 CALIBRATION LOW RETRANSMISSION OUTPUT Calibration desired Low Outp...

Страница 13: ...ontroller Controller circuit failed Check the power connection Check the supply voltage 4 4 Change Password Mode 4 5 Error Message Range Values Parameter PAsS 0000 CHANGE PASSWORD MODE PASSWORD Passwo...

Страница 14: ...stem schematic DATA The system schematic for RS 485 Modbus protocol are as follows DATA Ethernet RS 232 or RS 485 CONVERTER D D 1 2 UT 201 Device 1 D D 1 2 D D 1 2 D D 1 2 RS 485 BUS ADD 1 ADD 2 ADD 3...

Страница 15: ......

Отзывы: