UT-201

UNIVERSAL PROCESS INDICATOR & CONTROLLER

10

‘Calibration Mode’ Mode will shown by pressing        key, after 

Setp 

Mode display.

4.3       Calibration Mode

0100

 ~ 

0600

0200

 ~ 

1000

0200

 ~ 

1000

0200

 ~ 

1000

0200

 ~ 

1000

0200

 ~ 

1000

7000

 ~ 

8000

7000

 ~ 

8000

7000

 ~ 

8000

7000

 ~ 

8000

7000

 ~ 

8000

7000

 ~ 

8000

INPUT

J - T/C

K - T/C
R - T/C

S - T/C
T - T/C

E - T/C

0 mV
0 mV
0 mV

ZERO VALUE

FEED VALUE

COUNT

SPAN VALUE

FEED VALUE

COUNT

0 mV
0 mV
0 mV

18 mV
18 mV

42 mV

42 mV
42 mV

18 mV

INPUT

ZERO VALUE

FEED VALUE

COUNT

SPAN VALUE

FEED VALUE

COUNT

0100

 ~ 

0600

0100

 ~ 

1000

0100

 ~ 

1000

0100

 ~ 

1000

0900

 ~ 

1500

7000

 ~ 

8000

7000

 ~ 

8000

7000

 ~ 

8000

7000

 ~ 

8000

2000

 ~ 

3000

4 ~ 20mA
0 ~ 20mA

1 ~ 5 VDC

10VDC

PT-100

4 mA
0 mA

1 VDC
0 VDC

20 mA
20 mA

5 VDC

10 VDC

CALIBRATION VALUES :

0°C

[100.0Ω]

100°C

[138.51Ω]

Set Reqd. O/p by      ,      &       key, press        key.

NOTE :

 After output cal. press      key for next mode.

Hop1

Hop2

&

 

Range / Values

Parameter

pass
0000

CALIBRATION MODE PASSWORD

Password for Calibration Mode Parameters

Display

Scroll the digit by        key, Increase by        key.

Range  :  Values between 

0000

 to 

9999

Default Value  :  

0000

zrC1

----

CALIBRATION ZERO or LOW INPUT CH:1

Calibration Zero / Low at Low / Zero PV Input.

NOTE :

 After Zero Cal. press        key for next Para.

Apply Low signal [as per input] & press       key.

 

Range  :  

Default Value  :  

----

According to Input Type

CSP1

----

CALIBRATION SPAN or HIGH INPUT CH:1

Calibration Span / High at Span / High PV Input.

NOTE :

 After Span Cal. press       key for next para.

Apply High signal [as per input] & press       key.

Lop1

Lop2

CALIBRATION LOW [RETRANSMISSION] OUTPUT

Calibration desired Low Output for Both Input.

NOTE :

 After out low cal. press        key for next Para.

Set Reqd. O/p by      ,      &       key, press        key.

Note :

 After Calibration random value

            appeared in display, as per input.

Refer below Table for Cal. values range.

Note :

 After Calibration random value

            appeared in display, as per input.

Refer below Table for Cal. values range.

 

Range  :  

Default Value  :  

----

According to Input Type

Note :

 After Cali. random value should be

            below 

1000

 appeared in display.

 

Range  :  

Default Value  :  

strt  

->    to start cal.

According to Output Type

CALIBRATION HIGH [RETRANSMISSION] OUTPUT

Calibration desired High Output at PV Display.

 

Range  :  

Default Value  :  

strt  

->    to start cal.

According to Output Type

Note :

 After Cali. random value should be

            below 

8000

 appeared in display.

CALa

0032

CALIBRATION AMBIENT [THERMO COUPLE INP.] 

Ambient adjustment for compensation [T/C Inp.]

NOTE :

 After Amb. Cal. press       key for exit.

Set Ambient Temp by      &       key,press       key.

Note :

 After Calibration random value

            appeared in display, as per input.

 

Range  :  

Default Value  :  

0032

As per Ambient Temperature.

 

zrC2

----

CALIBRATION ZERO or LOW INPUT CH:2

Calibration Zero / Low same as Input-1

NOTE :

 After Zero Cal. press        key for next Para.

Range  :  

Default Value  :  

----

According to Input Type

 

CSP1

----

CALIBRATION SPAN or HIGH INPUT CH:2

Calibration Span / High same as Input-1

NOTE :

 After Span Cal. press       key for next para.

 

Range  :  

Default Value  :  

----

According to Input Type

&

Содержание UT-201

Страница 1: ...utplindia in www Model No UT 201 DUAL CHANNEL UNIVERSAL PROCESS INDICATOR CONTROLLER INSTRUCTION MANUAL M 96 x 96 Flame Proof UT 201 M COM www utplindia in RL 2 RL 1 RL 4 RL 3 201 0 201 0 UT 201 M COM...

Страница 2: ...ts Applying 240V AC to a controller rated for 12 24VDC will severely damage the controller and is a fire and smoke hazard This controller is suitable for connection to 230 15 VAC 50 Hz or 12 24 VDC po...

Страница 3: ...GRAMMING 3 1 OPERATION INTERFACE 3 2 MODE ACCESS FLOW CHART 4 1 CONFIGURATION MODE 4 OPERATIONAL MODES 4 2 SETUP MODE 4 3 CALIBRATION MODE 4 4 CHANGE PASSWORD MODE 4 5 ERROR MESSAGE 5 COMMUNICATION MO...

Страница 4: ...can do any change in the mode Two different configuration levels provide easy access to parameters A4 digit security code perverts una uthorized changes Parameters can also be hidden to user to preve...

Страница 5: ...ND 0 1 of Full Scale Automatic Software based self compensation Cold Junction Comp OPEN or OVER indication on display Sensor Break Info AS per Input Range Table Range Limits 330 K for Voltage mV and T...

Страница 6: ...0 21 B A 4 20mA 0 20mA CURRENT mA 22 21 0 VDC 5 10 V VOLTAGE 21 22 23 3 WIRE 21 22 9 8 T mA Input TPS 24VDC Transmi er TRANSMITTER 2 WIRE 21 22 9 8 T mA Input TPS 24VDC Transmi er TRANSMITTER OUTPUT R...

Страница 7: ...ey allows enter into the Parameter moving from one parameter to another or saving a new value of parameter or a status of parameter Press to change set points in normal view UP KEY UP Key allows incre...

Страница 8: ...technically competent to do so Local regulations regarding electrical safety must be observed FAILURE TO COMPLY WITH THESE INSTRUCTION COULD BE RESULT IN SERIOUS INJURY OR DEATH Default Password will...

Страница 9: ...the applied Input Change the type Up by key Down by key Range Input Type is as follows TC 4 RTD1 0 20 4 20 10v Default Value 0000 tsp1 L on ALARM 1 RELAY ACTION Alarm Relay activation direction Values...

Страница 10: ...key Decrease by key dp2 0001 CHANNEL 2 DECIMAL POINT LINEAR INPUT Decimal Point resolution for display value Values Default Value 0001 NOTE Applicable for Analog Linear input only tsp3 tsp4 ALARM 3 4...

Страница 11: ...ue 000 2 Hys1 000 2 HYSTERESIS ALARM 1 Value Diff between On and Off of Relay 1 Scroll the digit by key Increase by key Range Values between 199 9 to 999 9 Default Value As per User s set Reqd ALARM S...

Страница 12: ...ration Span High at Span High PV Input NOTE After Span Cal press key for next para Apply High signal as per input press key Lop1 Lop2 CALIBRATION LOW RETRANSMISSION OUTPUT Calibration desired Low Outp...

Страница 13: ...ontroller Controller circuit failed Check the power connection Check the supply voltage 4 4 Change Password Mode 4 5 Error Message Range Values Parameter PAsS 0000 CHANGE PASSWORD MODE PASSWORD Passwo...

Страница 14: ...stem schematic DATA The system schematic for RS 485 Modbus protocol are as follows DATA Ethernet RS 232 or RS 485 CONVERTER D D 1 2 UT 201 Device 1 D D 1 2 D D 1 2 D D 1 2 RS 485 BUS ADD 1 ADD 2 ADD 3...

Страница 15: ......

Отзывы: