CONDENSATE DRAIN PIPING

Horizontal Units - The 3/4 FPT drain connection on the 
unit is NOT internally trapped. The cooling coil com-
partment and drain pan are under negative pressure 
when the blower is running, therefore a P trap MUST 
be used in the drain line.

It is recommended that a ¾ inch drain line be sloped 
(¼ inch/foot) all the way to an open drain. Each unit 
must be installed with its own individual trap, and have 
the means to flush out the condensate line if neces-
sary. If it is not possible to reach an open drain by grav-
ity flow, a pump kit, which is available as an accessory, 
can be mounted close to the unit.

Vertical Units - Each unit utilizes a flexible hose inside 
the cabinet as a trapping loop. An external P-trap is not 
necessary.

WATER REGULATING VALVE – INSTALLATION

The water regulating valve is to be installed in the 
water outlet line, as close as possible to the unit cabi-
net (maximum 18 inches distance). The capillary tube 
from the sensing bellows on the valve(s) must be con-
nected to the ¼ inch male flare connection, which is on 
the refrigerant liquid line in the condenser compart-
ment. Connect the capillary tube flare nut directly to the 
unit male flare fitting.  When one is making this connec-
tion, it is normal for some refrigerant to escape as the 
schrader valve core is being opened and the nut is 
being tightened.  Complete the tightening of the nut as 
soon as possible to minimize the loss of refrigerant.  Do 
not over-tighten.

START-UP AND OPERATION

NOTE:

The services of a qualified Refrigeration Service

Mechanic should be employed in the start-up and
commissioning of these systems.

After completing the installation, and before energizing 
the power supply to the unit, the following checks 
should be made -

Verify that the electrical supply to the unit is of the 
correct voltage, and rated for sufficient amperage 
in accordance with the nameplate values.

Verify that the low voltage wiring between the unit 
and the thermostat is correct.

Confirm that the water piping is complete and free 
of leaks.

Check that the water flow rate is correct, and adjust 
as necessary.

Confirm that the blower wheel rotates freely.

All service access panels are in place and properly 
secured.

A room thermostat should be used to cycle the unit on 
and off automatically as required to maintain the room 
temperature at the set point of the thermostat.  The air 

TABLE 5: UNIT WATER PRESSURE DROP

UNIT MODEL

EWT

o

F

007

009

012

018

024

030

036

048

060

GPM

WPD

(psi)

GPM

WPD

(psi)

GPM

WPD

(psi)

GPM

WPD

(psi)

GPM

WPD

(psi)

GPM

WPD

(psi)

GPM

WPD

(psi)

GPM

WPD

(psi)

GPM

WPD

(psi)

50

1.0

0.8

1.35

1.4

1.8

2.1

2.75

2.3

3.5

3.3

4.5

3.6

5.5

2.9

7.5

3.9

9.0

3.6

1.5

2.0

2.25

3.5

3.0

5.3

4.50

5.7

6.0

8.0

7.5

9.0

9.0

7.0

12.0

9.6

15.0

8.8

60

1.0

0.7

1.35

1.4

1.8

2.0

2.75

2.2

3.5

3.2

4.5

3.5

5.5

2.8

7.5

3.7

9.0

3.5

1.5

1.9

2.25

3.4

3.0

5.1

4.50

5.5

6.0

7.7

7.5

8.7

9.0

6.8

12.0

9.2

15.0

8.5

70

1.0

0.7

1.35

1.3

1.8

1.9

2.75

2.1

3.5

3.0

4.5

3.3

5.5

2.6

7.5

3.5

9.0

3.3

1.5

1.8

2.25

3.2

3.0

4.8

4.50

5.2

6.0

7.3

7.5

8.2

9.0

6.4

12.0

8.7

15.0

8

85

1.0

0.7

1.35

1.2

1.8

1.8

2.75

2.0

3.5

2.9

4.5

3.1

5.5

2.5

7.5

3.3

9.0

3.1

1.5

1.7

2.25

3.0

3.0

4.6

4.50

4.9

6.0

6.9

7.5

7.8

9.0

6.1

12.0

8.3

15.0

7.6

100

1.0

0.6

1.35

1.2

1.8

1.7

2.75

1.9

3.5

2.7

4.5

3.0

5.5

2.4

7.5

3.2

9.0

3.0

1.5

1.6

2.25

2.9

3.0

4.4

4.50

4.7

6.0

6.6

7.5

7.5

9.0

5.8

12.0

7.9

15.0

7.3

Lock all electrical power supply switches in the off
position before installing the unit. failure to discon-
nect power supply may result in electrical shock or
even death.

Содержание RP007 Series

Страница 1: ...TENANCE 11 Complete Table of Contents on following pages NOTES CAUTIONS AND WARNINGS Installer should pay particular attention to the words NOTE CAUTION and WARNING Notes are intended to clarify or ma...

Страница 2: ...PIPING 10 WATER REGULATING VALVE INSTALLATION 10 START UP AND OPERATION 10 START UP 11 WATER REGULATING VALVE ADJUSTMENT 11 MAINTENANCE 11 STANDARD PRODUCT WARRANTY 17 LIST OF FIGURES Fig Pg 1 UNIT MO...

Страница 3: ...available as field installed acces sories All units are completely factory wired with all necessary operating controls A 24 volt control circuit with over size transformer is provided for field conne...

Страница 4: ...ING INSTALLATION Location To ensure unit operates at maximum effi ciencies choose a dry indoor area where the tempera ture is controlled between 40 F and 115 F Consideration of surrounding areas shoul...

Страница 5: ...ber Used 1 1 1 1 1 1 1 1 1 Air Coil Type Enhanced Copper Tubes Enhanced Aluminum Fins Face Area sq ft 1 00 1 00 1 00 1 51 2 56 2 56 2 88 4 38 5 00 Rows FPI 2 14 2 14 3 14 3 14 3 14 3 14 3 14 3 14 3 14...

Страница 6: ...he blower outlet flange Allowance must be made in the supply duct for removal of the first duct section adja cent to the unit for the servicing of the blower and motor assembly Return air may be ducte...

Страница 7: ...dered as an optional accessory for delivery with the units if desired TABLE 3 ELECTRICAL DATA MODEL SERIES SUPPLY VOLTAGE COMPRESSOR BLOWER MIN CCT AMPACITY MAX FUSE CCT BKR AMP QTY RLA LRA HP FLA 007...

Страница 8: ...0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 007 High 270 235 195 150 Med 260 240 210 175 Low 225 215 200 180 150 009 High 380 360 330 290 240 Med 350 340 325 300 270 235 Low 285 275 260 240 210 012 High 495 475...

Страница 9: ...ept if the inlet water temperature is constant and the flow rate can be pre set and turned on and off by some other means such as a dedicated pump circuit or solenoid valve Automatic water flow regula...

Страница 10: ...the installation and before energizing the power supply to the unit the following checks should be made Verify that the electrical supply to the unit is of the correct voltage and rated for sufficient...

Страница 11: ...ng the adjust ing screw counter clockwise will raise the opening pressure and raise the condensing pressure being maintained Turning the adjusting screw clockwise will lower the opening point and lowe...

Страница 12: ...icient water flow rates excessive water temperatures air flow rates dirty filters and air temperatures TABLE 6 R 22 REFRIGERANT CHARGE UNIT SIZE CAPACITY TONS HORIZONTAL VERTICAL 060 5 0 5 lbs 8 oz 5...

Страница 13: ...036 21521 001 A 0103 Unitary Products Group 13 FIGURE 2 TYPICAL SINGLE PHASE WIRING DIAGRAM APPLIES TO ALL 208 230 1 60 SINGLE PHASE MODELS Note Solenoid Valve SV used on Heat Pump version only...

Страница 14: ...036 21521 001 A 0103 14 Unitary Products Group FIGURE 3 TYPICAL THREE PHASE WIRING DIAGRAM APPLIES TO MODELS RP030 RP036 RP048 RP060 NOTE Solenoid Valve SV used on Heat Pump version only...

Страница 15: ...0 19 00 15 00 32 25 21 50 2 56 15 00 2 00 12 00 5 75 6 81 10 31 3 75 018 40 00 21 00 16 00 37 75 23 50 2 56 18 00 1 00 14 00 6 50 8 25 10 31 3 75 024 45 00 21 00 18 00 42 75 23 50 2 25 25 00 1 00 16 0...

Страница 16: ...50 1 25 N A N A 009 22 50 22 50 33 00 6 81 10 31 2 00 7 81 14 88 12 50 1 25 N A N A 012 22 50 22 50 33 00 6 81 10 31 2 00 7 81 14 88 12 50 1 25 11 50 12 00 018 22 50 22 50 35 00 8 25 10 31 2 00 7 13...

Отзывы: