background image

036-21521-001-A-0103

Unitary Products Group

11

circulating fan will cycle on and off with the compressor.  
If desired, the air circulating fan can be run continu-
ously.

The units have a lock out relay that will prevent the unit 
from cycling on the low pressure cut out or the high 
pressure cut out.  If either of these safety devices open, 
the compressor will not restart when the safety device 
resets.  To restart the compressor after a safety lock 
out, it will be necessary to interrupt the power to the 
control circuit.  This can be done at the thermostat or at 
the disconnect switch.

START-UP

1. Set the thermostat to the highest setting.

2. Set the fan switch to the 'AUTO' position, and the 

thermostat system switch to 'COOL'.

3. Reduce the thermostat setting to approximately 5 

degrees below room temperature.

4. The compressor, and the supply air blower, will 

start. Simultaneously the reversing valve will be 
energized.

5. After five minutes, verify cooling mode operation by 

checking for cool air discharge at the supply air 
outlet.

6. Set the thermostat system switch to the 'OFF' posi-

tion. The unit will stop running, and the reversing 
valve will de-energize.

7. Allow approximately five minutes to allow for sys-

tem pressures to equalize.

8. Set the thermostat to its lowest temperature set-

ting.

9. Move the thermostat system switch to 'HEAT'.

10. Increase the thermostat setting approximately 5 

degrees above room temperature.

11. After five minutes, verify heating mode operation 

by checking for warm air discharge at the supply 
air outlet.

12. Adjust the thermostat to maintain the desired 

space temperature.

13. Check the unit for unusual vibrations, noises, 

leaks, etc.

WATER REGULATING VALVE - ADJUSTMENT

The water regulating valve needs to be adjusted to 
maintain a condensing pressure of 170 to 220 PSIG.  
The valve is adjusted by turning the ¼ inch square 
shaft on top of the spring housing.  Turning the adjust-
ing screw counter clockwise will raise the opening 
pressure and raise the condensing pressure being 
maintained.  Turning the adjusting screw clockwise will 
lower the opening point and lower the condensing 
pressure being maintained.  If mains water is being 
used, make sure the valve closes soon after the com-
pressor stops.  If the flow does not stop after a few min-
utes, raise the opening pressure by turning the 
adjusting shaft counter clockwise until the flow stops.

If the unit is running on mains water, we recommend 
adjusting the water regulating valve to give 100ºF leav-
ing water temperature or 220 PSIG condensing tem-
perature.  This will give the best compromise between 
low water flow and high operating efficiency.  If the con-
denser water is being re-circulated through a cooling 
tower or a chilled water system, it is recommended that 
the water regulating valve be set for a lower condens-
ing temperature.  This will provide higher efficiency, 
lower operating cost and a lower sound level.  The min-
imum condensing pressure required for satisfactory 
expansion valve operation is 170 PSIG.

MAINTENANCE

The air circulating fan motor has bearings that are fac-
tory lubricated and sealed for long life.  No further lubri-
cation is required.  The compressor is part of a sealed 
refrigeration system that does not require any addi-
tional lubrication.

Filter changes are required at regular intervals. It is 
suggested that the filter be checked at 60-day intervals 
for the first year of operation, until field experience is 
acquired. If light cannot be seen through the filter, it 
should be changed. Always replace the filter with the 
same size of 1-inch thick disposable type of fiberglass 
filter. (See General Data for listing of required filter 
sizes.)

The condensate drain pan should be checked annually, 
and cleaned and flushed as required.

Recording of reference operating parameters is recom-
mended (volts, amp draw, water temperature differ-
ences, etc.). A comparison of logged data with start-up 
and annual data is useful as an indicator of general 
equipment condition.

Содержание RP007 Series

Страница 1: ...TENANCE 11 Complete Table of Contents on following pages NOTES CAUTIONS AND WARNINGS Installer should pay particular attention to the words NOTE CAUTION and WARNING Notes are intended to clarify or ma...

Страница 2: ...PIPING 10 WATER REGULATING VALVE INSTALLATION 10 START UP AND OPERATION 10 START UP 11 WATER REGULATING VALVE ADJUSTMENT 11 MAINTENANCE 11 STANDARD PRODUCT WARRANTY 17 LIST OF FIGURES Fig Pg 1 UNIT MO...

Страница 3: ...available as field installed acces sories All units are completely factory wired with all necessary operating controls A 24 volt control circuit with over size transformer is provided for field conne...

Страница 4: ...ING INSTALLATION Location To ensure unit operates at maximum effi ciencies choose a dry indoor area where the tempera ture is controlled between 40 F and 115 F Consideration of surrounding areas shoul...

Страница 5: ...ber Used 1 1 1 1 1 1 1 1 1 Air Coil Type Enhanced Copper Tubes Enhanced Aluminum Fins Face Area sq ft 1 00 1 00 1 00 1 51 2 56 2 56 2 88 4 38 5 00 Rows FPI 2 14 2 14 3 14 3 14 3 14 3 14 3 14 3 14 3 14...

Страница 6: ...he blower outlet flange Allowance must be made in the supply duct for removal of the first duct section adja cent to the unit for the servicing of the blower and motor assembly Return air may be ducte...

Страница 7: ...dered as an optional accessory for delivery with the units if desired TABLE 3 ELECTRICAL DATA MODEL SERIES SUPPLY VOLTAGE COMPRESSOR BLOWER MIN CCT AMPACITY MAX FUSE CCT BKR AMP QTY RLA LRA HP FLA 007...

Страница 8: ...0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 007 High 270 235 195 150 Med 260 240 210 175 Low 225 215 200 180 150 009 High 380 360 330 290 240 Med 350 340 325 300 270 235 Low 285 275 260 240 210 012 High 495 475...

Страница 9: ...ept if the inlet water temperature is constant and the flow rate can be pre set and turned on and off by some other means such as a dedicated pump circuit or solenoid valve Automatic water flow regula...

Страница 10: ...the installation and before energizing the power supply to the unit the following checks should be made Verify that the electrical supply to the unit is of the correct voltage and rated for sufficient...

Страница 11: ...ng the adjust ing screw counter clockwise will raise the opening pressure and raise the condensing pressure being maintained Turning the adjusting screw clockwise will lower the opening point and lowe...

Страница 12: ...icient water flow rates excessive water temperatures air flow rates dirty filters and air temperatures TABLE 6 R 22 REFRIGERANT CHARGE UNIT SIZE CAPACITY TONS HORIZONTAL VERTICAL 060 5 0 5 lbs 8 oz 5...

Страница 13: ...036 21521 001 A 0103 Unitary Products Group 13 FIGURE 2 TYPICAL SINGLE PHASE WIRING DIAGRAM APPLIES TO ALL 208 230 1 60 SINGLE PHASE MODELS Note Solenoid Valve SV used on Heat Pump version only...

Страница 14: ...036 21521 001 A 0103 14 Unitary Products Group FIGURE 3 TYPICAL THREE PHASE WIRING DIAGRAM APPLIES TO MODELS RP030 RP036 RP048 RP060 NOTE Solenoid Valve SV used on Heat Pump version only...

Страница 15: ...0 19 00 15 00 32 25 21 50 2 56 15 00 2 00 12 00 5 75 6 81 10 31 3 75 018 40 00 21 00 16 00 37 75 23 50 2 56 18 00 1 00 14 00 6 50 8 25 10 31 3 75 024 45 00 21 00 18 00 42 75 23 50 2 25 25 00 1 00 16 0...

Страница 16: ...50 1 25 N A N A 009 22 50 22 50 33 00 6 81 10 31 2 00 7 81 14 88 12 50 1 25 N A N A 012 22 50 22 50 33 00 6 81 10 31 2 00 7 81 14 88 12 50 1 25 11 50 12 00 018 22 50 22 50 35 00 8 25 10 31 2 00 7 13...

Отзывы: