background image

036-21521-001-A-0103

Unitary Products Group

9

LOOP WATER SUPPLY AND PIPING 
CONNECTIONS

The recommended circulating water supply for 

heat 

pump 

systems is a closed-water loop, utilizing a cool-

ing tower and boiler to maintain the loop temperature 
within acceptable temperature limits. Typically, the 
closed loop temperature is maintained above 60° F and 
below 90° F. All units function independently, either 
adding heat to the loop (cooling mode) or removing 
heat from the loop (heating mode).

When utilizing an open cooling tower (evaporative 
type), chemical treatment is mandatory to ensure that 
the loop water is free of corrosive minerals. A second-
ary heat exchanger between the open cooling tower 
and the closed water loop may also be used. It is 
imperative that all air is purged from the closed loop 
side to prevent condenser fouling.

Dual acting water regulating valves should be used 
when there is potential for low fluid flow and/or low fluid 
temperature or high fluid temperature conditions to 
exist. These water regulating valve assemblies consist 
of a direct acting valve parallel coupled to a reverse 
acting valve. The direct acting valve opens in response 
to an increase in discharge pressure during cooling 
mode. The reverse acting valve opens in response to a 
decrease in suction pressure during heating mode.

The heat rejection water source for 

cooling-only 

units 

may be from a municipal supply main, a cooling tower, 
or a chilled water system. An automatic water flow reg-
ulating valve is normally required, except if the inlet 
water temperature is constant and the flow rate can be 
pre-set and turned on and off by some other means, 
such as a dedicated pump circuit or solenoid valve.

Automatic water flow regulating valves, for both heat 
pump and cooling-only applications, are available as 
field installed accessories. The valves are installed on 
the water outlet connection from the unit. Schrader 
type refrigerant pressure access fittings are included 
as standard in all units.

SUPPLY/RETURN PIPING

Supply and return piping should be as large as the unit 
connection sizes (larger on long pipe runs). Never use 
flexible hoses of a smaller inside diameter than that of 
the nominal water pipe size. Both supply and return 
water lines will sweat if subjected to low water tempera-
tures. Insulate these lines as necessary to prevent con-
densation damage.

Flexible hoses should be used between the unit and 
rigidly mounted piping to avoid vibration transmission. 
Teflon tape thread sealant is recommended. Do not 
overtighten threaded connections. Ball valves should 
be installed in the supply and return lines for unit isola-
tion and water flow balancing. Before final connection 
to the unit, the supply and return hoses should be con-
nected together and the piping system flushed to 
remove any dirt or foreign material.

Pressure and temperature ports are recommended in 
both the supply and return lines for system flow balanc-
ing. The water flow can be accurately set by measuring 
the water-side pressure drop through the unit. See the 
flow versus pressure drop specification table for appli-
cation information. 

Do not exceed the recommended 

water flow rates. Damage due to erosion of

 

the 

water-to-refrigerant heat exchanger could occur.

Содержание RP007 Series

Страница 1: ...TENANCE 11 Complete Table of Contents on following pages NOTES CAUTIONS AND WARNINGS Installer should pay particular attention to the words NOTE CAUTION and WARNING Notes are intended to clarify or ma...

Страница 2: ...PIPING 10 WATER REGULATING VALVE INSTALLATION 10 START UP AND OPERATION 10 START UP 11 WATER REGULATING VALVE ADJUSTMENT 11 MAINTENANCE 11 STANDARD PRODUCT WARRANTY 17 LIST OF FIGURES Fig Pg 1 UNIT MO...

Страница 3: ...available as field installed acces sories All units are completely factory wired with all necessary operating controls A 24 volt control circuit with over size transformer is provided for field conne...

Страница 4: ...ING INSTALLATION Location To ensure unit operates at maximum effi ciencies choose a dry indoor area where the tempera ture is controlled between 40 F and 115 F Consideration of surrounding areas shoul...

Страница 5: ...ber Used 1 1 1 1 1 1 1 1 1 Air Coil Type Enhanced Copper Tubes Enhanced Aluminum Fins Face Area sq ft 1 00 1 00 1 00 1 51 2 56 2 56 2 88 4 38 5 00 Rows FPI 2 14 2 14 3 14 3 14 3 14 3 14 3 14 3 14 3 14...

Страница 6: ...he blower outlet flange Allowance must be made in the supply duct for removal of the first duct section adja cent to the unit for the servicing of the blower and motor assembly Return air may be ducte...

Страница 7: ...dered as an optional accessory for delivery with the units if desired TABLE 3 ELECTRICAL DATA MODEL SERIES SUPPLY VOLTAGE COMPRESSOR BLOWER MIN CCT AMPACITY MAX FUSE CCT BKR AMP QTY RLA LRA HP FLA 007...

Страница 8: ...0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 007 High 270 235 195 150 Med 260 240 210 175 Low 225 215 200 180 150 009 High 380 360 330 290 240 Med 350 340 325 300 270 235 Low 285 275 260 240 210 012 High 495 475...

Страница 9: ...ept if the inlet water temperature is constant and the flow rate can be pre set and turned on and off by some other means such as a dedicated pump circuit or solenoid valve Automatic water flow regula...

Страница 10: ...the installation and before energizing the power supply to the unit the following checks should be made Verify that the electrical supply to the unit is of the correct voltage and rated for sufficient...

Страница 11: ...ng the adjust ing screw counter clockwise will raise the opening pressure and raise the condensing pressure being maintained Turning the adjusting screw clockwise will lower the opening point and lowe...

Страница 12: ...icient water flow rates excessive water temperatures air flow rates dirty filters and air temperatures TABLE 6 R 22 REFRIGERANT CHARGE UNIT SIZE CAPACITY TONS HORIZONTAL VERTICAL 060 5 0 5 lbs 8 oz 5...

Страница 13: ...036 21521 001 A 0103 Unitary Products Group 13 FIGURE 2 TYPICAL SINGLE PHASE WIRING DIAGRAM APPLIES TO ALL 208 230 1 60 SINGLE PHASE MODELS Note Solenoid Valve SV used on Heat Pump version only...

Страница 14: ...036 21521 001 A 0103 14 Unitary Products Group FIGURE 3 TYPICAL THREE PHASE WIRING DIAGRAM APPLIES TO MODELS RP030 RP036 RP048 RP060 NOTE Solenoid Valve SV used on Heat Pump version only...

Страница 15: ...0 19 00 15 00 32 25 21 50 2 56 15 00 2 00 12 00 5 75 6 81 10 31 3 75 018 40 00 21 00 16 00 37 75 23 50 2 56 18 00 1 00 14 00 6 50 8 25 10 31 3 75 024 45 00 21 00 18 00 42 75 23 50 2 25 25 00 1 00 16 0...

Страница 16: ...50 1 25 N A N A 009 22 50 22 50 33 00 6 81 10 31 2 00 7 81 14 88 12 50 1 25 N A N A 012 22 50 22 50 33 00 6 81 10 31 2 00 7 81 14 88 12 50 1 25 11 50 12 00 018 22 50 22 50 35 00 8 25 10 31 2 00 7 13...

Отзывы: