background image

035-19670-003 Rev. A (1004)

20

Unitary Products Group

DIRECT DRIVE MOTORS

Adjustment of Fan-Off Control Settings

This furnace is equipped with a time-on/time-off heating fan control. The
fan-on is fixed at 30 seconds. The fan-off delay is factory set to 60 sec-
onds; however, it is field-adjustable to 90, 120 or 180 seconds. The fan-
off setting must be long enough to adequately cool the furnace, but not
so long that cold air is blown into the heated space. 

Adjustment of Fan Control Settings

This furnace is equipped with a time-on/time-off heating fan control. The
fan on delay is fixed at 30 seconds. The fan off delay has 4 settings (60,
90, 120 and 180 seconds). The fan off delay is factory set to 120 sec-
onds. The fan-off setting must be long enough to adequately cool the
furnace, but not so long that cold air is blown into the heated space. The
fan-off timing may be adjusted by positioning the jumper on two of the
four pins as shown in Figure 26.

Heating Indoor Fan Off Delay

The jumper pins are located on the main control board. Refer to Figure
30 for the jumper settings to obtain the desired fan OFF delay. The
blower off delay must be long enough to adequately cool the furnace,
but not so long that cold air is blown into the living space.

The blower on delay is fixed at 30 seconds and can not be adjusted.

Continuous Blower Operation

The blower will run continuously whenever the wall thermostat fan
switch is in the "ON" position. The furnace blower will run at the speed
selected on the "FAN SPEED" jumpers on the main control board (HI
COOL, LO COOL, HI HEAT or LO HEAT).

Intermittent Blower Cooling

On cooling/ heating thermostats with a fan switch, when the fan switch
is set in the auto position and the thermostat calls for cooling, a circuit is
completed between the R, Y and G terminals. The motor is energized
through the Y1 cool terminal and runs on the speed selected on the
board. The fan off setting is fixed at 60 seconds for maximum cooling
efficiency furnace control.

Intermittent Blower Heating

On cooling/ heating thermostats with a fan switch, when the fan switch 
is set in the auto position and the thermostat calls for heating, a circuit is 
completed between the R and W terminals. The indoor fan motor is 
energized through the W1 heat terminal and runs on the speed selected 
on the furnace control board.

ADJUSTMENT OF TEMPERATURE RISE

The temperature rise, or temperature difference between the return air
and the heated supply air from the furnace, must be within the range
shown on the furnace rating plate and within the application limitations

The manifold pressure must be checked with the screw-off cap for
the gas valve pressure regulator in place. If not, the manifold pres-
sure setting could result in an over-fire condition. A high manifold
pressure will cause an over-fire condition, which could cause pre-
mature heat exchanger failure. If the manifold pressure is too low,
sooting and eventual clogging of the heat exchanger could occur.
Be sure that gas valve regulator cap is in place and burner box to
gas valve pressure reference hose is connected.

MAINFOLD PRESSURE “U” TUBE CONNECTION

 FIGURE 28:  

Reading Gas Pressure

Do not energize more than one motor speed at a time or damage to
the motor will result.

U-TUBE
MANOMETER

3.5 IN
WATER
COLUMN
GAS
PRESSURE
SHOWN

GAS
BURNERS

OUTLET
PRESSURE TAP

GAS VALVE

FLAME
SENSOR

1/4” TUBING

MAINIFOLD
PIPE

 FIGURE 29:  

Furnace Control Board

The temperature rise, or temperature difference between the return
air and the supply (heated) air from the furnace, must be within the
range shown on the furnace rating plate and within the application
limitations shown in Table 8 “ELECTRICAL AND PERFORMANCE
DATA”.
The supply air temperature cannot exceed the “Maximum Supply
Air Temperature”
 specified in these instructions and on the fur-
nace rating plate. Under NO circumstances can the furnace be
allowed to operate above the Maximum Supply Air Temperature.
Operating the furnace above the Maximum Supply Air Temperature
will cause premature heat exchanger failure, high levels of Carbon
Monoxide, a fire hazard, personal injury, property damage, and/or
death.

Y1

Y2

Y

W1

W

W2

R

G

C

Содержание PT8

Страница 1: ...ETY 1 DUCTWORK 3 FILTERS 6 GAS PIPING 7 ELECTRICAL POWER 9 VENT SYSTEM 11 SAFETY CONTROLS 16 START UP AND ADJUSTMENTS 16 WIRING DIAGRAM 24 LIST OF FIGURES Dimensions 5 Furnace Base Rectangular Blockof...

Страница 2: ...ailure to carefully read and follow all instructions in this manual can result in furnace malfunction death personal injury and or property damage Furnaces for installation on combustible flooring sha...

Страница 3: ...es shall take precedence over clear ances for combustible materials where accessibility clearances are greater Installation in a residential garage 1 A gas fired furnace for installation in a resident...

Страница 4: ...mined by adding the Supply Duct Static Pressure reading to the Return Duct Static Pressure reading and adding the pressure drop across any applied a coil Tables 2 3 is to be used as a guide only to he...

Страница 5: ...quired service accessibility IMPORTANT If an external mounted filter rack is being used see the instructions provided with that accessory for proper hole cut size HORIZONTAL MODELS The supply air temp...

Страница 6: ...duct flanges This is typi cally through the use of S cleat material when a metal plenum is used The use of an approved flexible duct connector is recommended on all installations The connection of th...

Страница 7: ...pproved for this furnace only use those approved gases The instal lation of a drip leg and ground union is required Refer to Figures 9 or 10 TABLE 5 Filter Sizes Cabinet Size Side in Side cm Bottom in...

Страница 8: ...he gas valve when installing piping A wrench must be placed on the octa gon hub located on the gas inlet side of the valve Placing a wrench to the body of the gas valve will damage the valve causing i...

Страница 9: ...OLARITY Ignition Control If the power supply polarity is reversed the control board will flash 9 times The furnace will not operate until the polarity is corrected LOW VOLTAGE CONTROL WIRING CONNECTIO...

Страница 10: ...1 0 amp maximum during circulating blower opera tion HUMIDIFIER CONNECTION Two 1 4 0 64 cm spade terminals EAC and NEUTRAL for humidifier connections are located on the control board The terminals pr...

Страница 11: ...codes and standards listed in these instructions Approved Modular Homes must be vented with an approved roof jack and may not be common vented with other appliances VENTING Category I venting consists...

Страница 12: ...etails provided by the manufacturer of the power vent VENT PIPING ASSEMBLY The final assembly procedure for the vent piping is as follows 1 Cut piping to the proper length beginning at the furnace 2 D...

Страница 13: ...ent sagging The vent system may be supported by the use of clamps or hangers secured to a permanent part of the structure every 4 ft 1 22 m FAN ASSISTED COMBUSTION SYSTEM An appliance equipped with an...

Страница 14: ...r a grille or screen shall have no dimen sion smaller than 0 25 6 4 mm 3 A manually operated damper or manually adjustable louvers are not permitted for use 4 A automatically operated damper or automa...

Страница 15: ...NACE 1 An opening may be used in lieu of a duct to provide to provide the outside air supply to an appliance unless otherwise permitted by the authority having jurisdiction The opening shall be locate...

Страница 16: ...RBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monxide poisoning or dea...

Страница 17: ...cm tee 1 5 16 0 8 cm x 1 8 3 175 mm reducing coupling 1 1 8 0 3 cm adapter There is a accessory kit 1PK0602 available from Source 1 which has the following items 12 30 cm length x 1 8 0 3 cm diameter...

Страница 18: ...ivided by the time it took to measure 2 cubic ft 0 0566 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 14 times 0 00283 m3 of gas measured at...

Страница 19: ...low adjustment seal screw and tighten securely Cycle the valve several times to verify regulator setting 7 Remove manometer and replace the outlet pressure tap plug Low Outlet Pressure Adjustment 1 T...

Страница 20: ...urnace control Intermittent Blower Heating On cooling heating thermostats with a fan switch when the fan switch is set in the auto position and the thermostat calls for heating a circuit is completed...

Страница 21: ...ps Obtain the airflow values at 0 50 w c 125 Pa 0 60 w c 150 Pa ESP Airflow 0 50 2125 CFM 60 17 m3 min Airflow 0 60 2035 CFM 57 62 m3 min Subtract the airflow 0 50 w c 125 Pa from the airflow 0 60 w c...

Страница 22: ...0 1150 41 6 41 1 40 8 40 5 39 4 38 5 37 1 36 0 34 5 32 6 Low 1260 1260 1260 1260 1250 1200 1150 1110 1070 1010 35 7 35 7 35 7 35 7 35 4 34 0 32 6 31 4 30 3 28 6 100 1200 B High 1700 1620 1560 1480 139...

Страница 23: ...1430 1410 1370 1340 1280 1220 1140 1040 890 730 40 5 39 9 38 8 37 9 36 2 34 5 32 3 29 4 25 2 20 7 Medium Low 1140 1170 1150 1120 1080 1040 970 890 760 630 32 3 33 1 32 6 31 7 30 6 29 4 27 5 25 2 21 5...

Страница 24: ...d in U S A 035 19670 003 Rev A 1004 Copyright by York International Corp 2004 All rights reserved Supersedes 035 19670 002 Rev A 0704 Unitary 5005 Norman Product York OK Group Drive 73069 SECTION IX W...

Отзывы: