background image

035-19670-003 Rev. A (1004)

Unitary Products Group

19

IMPORTANT: 

The inlet gas pressure operating range table specifies

what the minimum and maximum gas line pressures must be for the fur-
nace to operate safely. The gas line pressure 

MUST BE

7” W.C. (1.74 kPA) for Natural Gas

11” W.C. (2.74 kPA) for Propane (LP) Gas

in order to obtain the BTU input specified on the rating plate and/or the
nominal manifold pressure specified in these instructions and on the
rating plate.

ADJUSTMENT OF MANIFOLD GAS PRESSURE

Manifold gas pressure may be measured by connecting the “U” tube
manometer to the gas valve with a piece of tubing and on an adapter.
Follow the appropriate section in the instructions below. Refer to Figure
29 for a drawing of the locations of the pressure ports on the gas valve.

Turn gas off at the ball valve or gas cock on gas supply line 
before the gas valve. Find the pressure ports on the gas 
valve marked Out Pressure Tap and Inlet Pressure Tap.

1.

The manifold pressure must be taken at the port marked OUT
Pressure Tap. 

2.

The gas line pressure must be taken at the port marked Inlet Pres-
sure Tap.

Using a screw driver, remove the cap that covers the manifold pressure
set screw.

Read the inlet gas pressure

Connect the positive side of the manometer to the adapter previously
installed in the Out pressure Tap on the gas valve. Do not connect any
tubing to the negative side of the manometer, as it will reference atmo-
spheric pressure. Refer to Figure 30 for connection details.

IMPORTANT: 

The cap for the pressure regulator must be removed

entirely to gain access to the adjustment screw. Loosening or tightening
the cap does not adjust the flow of gas.

NOTE: 

The regulated outlet pressures, both low and high, have been

calibrated at the factory. Additional pressure adjustment should
not be necessary. If adjustment is necessary, set to the following
specifications. After adjustment, check for gas leakage.

.

High Outlet Pressure Adjustment

1.

Turn off all electrical power to the system at main fuse or circuit
breaker.

2.

Attach a manometer to the outlet pressure tap of the valve.

3.

Turn on power and energize main and redundant (P.M.) solenoids
as well as the HI terminal.

4.

Remove high adjustment seal screw to expose the 3/32”. See Fig-
ure 29.

5.

To increase outlet pressure, turn the 3/32” set screw clockwise. To
decrease outlet pressure, turn the set screw counterclockwise.
Adjust regulator until pressure shown on manometer matches the
pressure specified on the appliance rating plate.

6.

Replace low adjustment seal screw and tighten securely. Cycle the
valve several times to verify regulator setting.

7.

Remove manometer and replace the outlet pressure tap plug.

Low Outlet Pressure Adjustment

1.

Turn off all electrical power to the system at main fuse or circuit
breaker.

2.

Attach a manometer to the outlet pressure tap of the valve.

3.

Turn on power and energize main and redundant (P.M.) solenoids.
Do not energize HI terminal.

4.

Remove low adjustment seal screw. See Figure 29.

5.

To increase outlet pressure, turn the 3/32” (0.24 cm) set screw
below the low adjustment seal screw clockwise. To decrease outlet
pressure, turn the set screw counterclockwise. Adjust regulator
until pressure shown on manometer matches the pressure speci-
fied on the appliance rating plate.

6.

Replace high adjustment seal screw and tighten securely. Cycle
the valve two and three times to verify regulator setting.

7.

Remove manometer and replace the outlet pressure tap.

IMPORTANT: 

If gas valve regulator is turned in (clockwise), manifold

pressure is increased. If screw is turned out (counterclockwise), mani-
fold pressure will decrease.

8.

After the manifold pressure has been adjusted, re-calculate the
furnace input to make sure you have not exceeded the specified
input on the rating plate. Refer to “CALCULATING THE FURNACE
INPUT (NATURAL GAS)”.

9.

Once the correct BTU (kW) input has been established, turn the
gas valve to OFF and turn the electrical supply switch to OFF; then
remove the flexible tubing and fittings from the gas valve pressure
tap and re-install the plug in the Out Pressure Port using a com-
pound (on the threads) resistant to the action of LP gases.
Replace the burner box front cover (if it was removed) and replace
the pressure reference hose.

10. Turn the electrical and gas supplies back on, and with the burners

in operation, check for gas leakage around the gas valve pressure
port for leakage using an approved non-corrosive gas leak detec-
tion fluid, or other non-flammable leak detection methods.

Be sure to relight any gas appliances that were turned off at the
start of this input check.

TABLE 14: 

Inlet Gas Pressure Range

INLET GAS PRESSURE RANGE

Natural Gas

Propane (LP)

Minimum

4.5” W.C. (1.12 kPa)

8.0” W.C. (1.99 kPa)

Maximum

10.5” W.C. (2.61 kPa)

13.0” (3.24 kPa) W.C.

TABLE 15: 

Nominal Manifold Pressure

NOMINAL MANIFOLD PRESSURE

Natural Gas (High Fire)

3.5" w.c. (0.87 kPa)

Natural Gas (Low Fire)

1.6" w.c. (0.40 kPa)

Propane (LP) Gas (High Fire)

10.0" w.c. (2.488 kPa)

Propane (LP) Gas (Low Fire)

4.0" w.c. (0.99 kPa)

 FIGURE 27:  

Gas Valve

R

E

P

L

A

C

E

R

E

P

L

A

C

E

SCRE

W

SCRE

W

INLET

OUTLET

ON / OFF SWITCH

WRENCH
BOSS

LOW FIRE
REGULATOR
ADJUSTMENT
SEAL SCREW

HIGH FIRE
REGULATOR
ADJUSTMENT
SEAL SCREW

HI ADJUST

LO

ADJUST

PM

C
HI

O
F
F

ON

Содержание PT8

Страница 1: ...ETY 1 DUCTWORK 3 FILTERS 6 GAS PIPING 7 ELECTRICAL POWER 9 VENT SYSTEM 11 SAFETY CONTROLS 16 START UP AND ADJUSTMENTS 16 WIRING DIAGRAM 24 LIST OF FIGURES Dimensions 5 Furnace Base Rectangular Blockof...

Страница 2: ...ailure to carefully read and follow all instructions in this manual can result in furnace malfunction death personal injury and or property damage Furnaces for installation on combustible flooring sha...

Страница 3: ...es shall take precedence over clear ances for combustible materials where accessibility clearances are greater Installation in a residential garage 1 A gas fired furnace for installation in a resident...

Страница 4: ...mined by adding the Supply Duct Static Pressure reading to the Return Duct Static Pressure reading and adding the pressure drop across any applied a coil Tables 2 3 is to be used as a guide only to he...

Страница 5: ...quired service accessibility IMPORTANT If an external mounted filter rack is being used see the instructions provided with that accessory for proper hole cut size HORIZONTAL MODELS The supply air temp...

Страница 6: ...duct flanges This is typi cally through the use of S cleat material when a metal plenum is used The use of an approved flexible duct connector is recommended on all installations The connection of th...

Страница 7: ...pproved for this furnace only use those approved gases The instal lation of a drip leg and ground union is required Refer to Figures 9 or 10 TABLE 5 Filter Sizes Cabinet Size Side in Side cm Bottom in...

Страница 8: ...he gas valve when installing piping A wrench must be placed on the octa gon hub located on the gas inlet side of the valve Placing a wrench to the body of the gas valve will damage the valve causing i...

Страница 9: ...OLARITY Ignition Control If the power supply polarity is reversed the control board will flash 9 times The furnace will not operate until the polarity is corrected LOW VOLTAGE CONTROL WIRING CONNECTIO...

Страница 10: ...1 0 amp maximum during circulating blower opera tion HUMIDIFIER CONNECTION Two 1 4 0 64 cm spade terminals EAC and NEUTRAL for humidifier connections are located on the control board The terminals pr...

Страница 11: ...codes and standards listed in these instructions Approved Modular Homes must be vented with an approved roof jack and may not be common vented with other appliances VENTING Category I venting consists...

Страница 12: ...etails provided by the manufacturer of the power vent VENT PIPING ASSEMBLY The final assembly procedure for the vent piping is as follows 1 Cut piping to the proper length beginning at the furnace 2 D...

Страница 13: ...ent sagging The vent system may be supported by the use of clamps or hangers secured to a permanent part of the structure every 4 ft 1 22 m FAN ASSISTED COMBUSTION SYSTEM An appliance equipped with an...

Страница 14: ...r a grille or screen shall have no dimen sion smaller than 0 25 6 4 mm 3 A manually operated damper or manually adjustable louvers are not permitted for use 4 A automatically operated damper or automa...

Страница 15: ...NACE 1 An opening may be used in lieu of a duct to provide to provide the outside air supply to an appliance unless otherwise permitted by the authority having jurisdiction The opening shall be locate...

Страница 16: ...RBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monxide poisoning or dea...

Страница 17: ...cm tee 1 5 16 0 8 cm x 1 8 3 175 mm reducing coupling 1 1 8 0 3 cm adapter There is a accessory kit 1PK0602 available from Source 1 which has the following items 12 30 cm length x 1 8 0 3 cm diameter...

Страница 18: ...ivided by the time it took to measure 2 cubic ft 0 0566 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 14 times 0 00283 m3 of gas measured at...

Страница 19: ...low adjustment seal screw and tighten securely Cycle the valve several times to verify regulator setting 7 Remove manometer and replace the outlet pressure tap plug Low Outlet Pressure Adjustment 1 T...

Страница 20: ...urnace control Intermittent Blower Heating On cooling heating thermostats with a fan switch when the fan switch is set in the auto position and the thermostat calls for heating a circuit is completed...

Страница 21: ...ps Obtain the airflow values at 0 50 w c 125 Pa 0 60 w c 150 Pa ESP Airflow 0 50 2125 CFM 60 17 m3 min Airflow 0 60 2035 CFM 57 62 m3 min Subtract the airflow 0 50 w c 125 Pa from the airflow 0 60 w c...

Страница 22: ...0 1150 41 6 41 1 40 8 40 5 39 4 38 5 37 1 36 0 34 5 32 6 Low 1260 1260 1260 1260 1250 1200 1150 1110 1070 1010 35 7 35 7 35 7 35 7 35 4 34 0 32 6 31 4 30 3 28 6 100 1200 B High 1700 1620 1560 1480 139...

Страница 23: ...1430 1410 1370 1340 1280 1220 1140 1040 890 730 40 5 39 9 38 8 37 9 36 2 34 5 32 3 29 4 25 2 20 7 Medium Low 1140 1170 1150 1120 1080 1040 970 890 760 630 32 3 33 1 32 6 31 7 30 6 29 4 27 5 25 2 21 5...

Страница 24: ...d in U S A 035 19670 003 Rev A 1004 Copyright by York International Corp 2004 All rights reserved Supersedes 035 19670 002 Rev A 0704 Unitary 5005 Norman Product York OK Group Drive 73069 SECTION IX W...

Отзывы: