10.INTERFACE
145
Example
When setting is as follows:
D/A Output Mode .................... 01
D/A Zero Output Weight.......... 00500
D/A Full Scale.......................... 02500
10-4-4. About D/A Resolution
The resolution of the D/A converter is 1/10000 with respect to 4 ~ 20mA.
That is, the minimum unit of current is as follows:
(20 ~ 4mA) × 1/10000 = 1.6
μ
A
Also, the minimum unit of weight value is as follows:
(D/A Full Scale setting value) × 1/10000
Current
(mA)
20
4
D/A Zero Output Weight setting
Resolution 1/10000
D/A Full Scale setting
Net
500
2000
2500
Net
Current (mA)
480
500
1000
1500
2500
2520
3.84
4.00
8.00
12.00
20.00
20.16
Zero
Full scale