9.EXTERNAL INPUT/OUTPUT SIGNALS (CONTROL CONNECTOR)
112
9-2. Equivalent Circuit (Input)
A signal is inputted to the signal input circuit by short-circuiting or opening the input terminal and
the COM terminal. Short-circuiting is effected by means of a contact (such as a relay or a switch) or
a noncontact (such as a transistor or an open-collector TTL).
9-3. Equivalent Circuit (Output)
The signal output circuit is open-collecter output of a transistor.
Vcc
F701-C
Inside
approx.
COM
Transistor
+12V
Push
Toggle Switch
Relay
IN
IN
Open
OFF
Short
ON
- Do not apply external voltage to the signal input circuit.
- The external element is required to withstand Ic=10mA.
- Leakage from the external element is required to be 100
μ
A or below.
Switch
IC=6mA
TTL Open Collector
(ON when IN is HI)
Spark killer
Load
Spark killer
DC Power
Varistor
Load
AC power
Relay
Vext
Output data
Tr
0
OFF
1
ON
F701-C
Inside
Vcc
+12V
COM
Vceo=30V(max)
Ic =120mA (max)
- Use external power source (up to DC30V) for driving relay
(Vext).
- Do not short-circuit the load, such as a coil of relay, that will
break the output transistor.
- Connect a surge absorber or a speark killer to the relay
circuit as shown in the draft so that to reduce noise trouble
and extend the life of relay.
Noise trouble can be reduced, and the relay’s life can be
extended.
- Transistor status
Содержание F701-C