background image

Page 3

DPU1U SERIES

INSTALLATION & OPERATING MANUAL

P O W E R I N G   T E C H N O L O G Y

Document Number: DPU1U-MAN Rev. 4

dpu1u-man-rev1-0719.indd

FIGURES

Figure 1. DPU1U Alternative Combinations ...................................................................................4
Figure 2. Distribution Block Diagram ..............................................................................................7
Figure 3. LVD Block Diagram .........................................................................................................7
Figure 4. Distribution Section Front Panel View .............................................................................9
Figure 5. GMT Fuse Section Front Panel View ...............................................................................9
Figure 6. LVD Front Panel View ......................................................................................................9
Figure 7. Center Section Front Panel View ......................................................................................9
Figure 8. Back Panel View with LVD ............................................................................................10
Figure 9. Back Panel View with Dual Distribution ........................................................................11
Figure 10.  Input Bus Bar Detail ....................................................................................................11
Figure 11.  Output Barrier Strip Detail ...........................................................................................12
Figure 12.  Alarm Contact & Ground Detail ..................................................................................12

TABLES

Table 1.  LED State Definitions

 .......................................................................................................8

Table 2.  Available Combinations ....................................................................................................8
Table 3.  GMT Fuse Values ............................................................................................................10
Table 4.  Input Cable Lug Sizes & Types ......................................................................................11
Table 5.  Alarm Relay Contacts .....................................................................................................13

Table 6.  Relay State Definitions

 ...................................................................................................13

Содержание UNIFLEX DRU1U Series

Страница 1: ...y can be mounted from the front of the rack with offsets every quarter inch from front to back to align with existing rack mounted equipment FEATURES One Mounting Position High 1 75 19 or 23 Inch Rack...

Страница 2: ...w voltage disconnect specified by L 2 A bypass switch must also be designated YES or NO 3 For a breaker panel each breaker must be specified with highest current in position 1 down to lowest current i...

Страница 3: ...N PANELS Document Number DPU1U MAN Rev 4 UNIPOWER LLC 65 Industrial Park Rd Dunlap TN 37327 Phone 1 954 346 2442 Toll Free 1 800 440 3504 Web site www unipowerco com 2019 UNIPOWER LLC All Rights Reser...

Страница 4: ...TRODUCTION 4 2 0 FEATURES 5 3 0 PRODUCT DESCRIPTION 5 4 0 SAFETY INDUSTRY STANDARDS 6 5 0 WARRANTY summary 6 6 0 DESCRIPTION OF OPERATION 7 7 0 SPECIFICATIONS 8 8 0 FRONT PANEL DESCRIPTION 9 9 0 BACK...

Страница 5: ...MT Fuse Section Front Panel View 9 Figure 6 LVD Front Panel View 9 Figure 7 Center Section Front Panel View 9 Figure 8 Back Panel View with LVD 10 Figure 9 Back Panel View with Dual Distribution 11 Fi...

Страница 6: ...ng rackmounted equipment DPU1U Series provides a combination of circuit breaker or fuse distribution on the A side with an LVD or distribution on the B side Figure 1 shown the three possible combinati...

Страница 7: ...GMT Fuses or Magnetic Circuit Breakers LVD Protection 70A Magnetic Circuit Breaker with Bypass Option Independent and Isolated Loads Input Connections Crimp Type Lugs Output Connections Barrier Termi...

Страница 8: ...operating these combination anels the chassis ground terminal must be connected to the system frame ground or other proper safety ground for the protection of personnel 4 5 All connections to these co...

Страница 9: ...S OPTION Figure 2 Distribution Block Diagram 6 2 LVD Circuits Figure 3 shows a simplified diagram of the LVD circuit The LVD is connected to a rectifier bus battery and distribution panel The contact...

Страница 10: ...Alarm Indicator LED on Each Side LED Status Fuse Breaker Sections Green Normal Red Alarm Off No Power LVD Section Red LVD Contactor or Battery Breaker Open Off Normal Alarm Connections Fuse Breaker Tw...

Страница 11: ...F O ON I 15 17 12 434 9 REAR VIEW FRONT VIEW Cas Figure 4 Distribution Section Front Panel View The front panel of the GMT fuse distribution section shown in Figure 5 below can each accommodate up to...

Страница 12: ...Red 3 401 1500 0060 Blue 401 1500 0020 Brown 5 401 1500 0070 Green 1 401 1500 0030 Gray 10 401 1500 0080 Red White 11 3 401 1500 0040 White 12 401 1500 0090 Green Yellow 2 401 1500 0050 Orange DUMMY...

Страница 13: ...o spring clamp terminal blocks for the Form C relay contact outputs Below these is a chassis ground terminal 9 2 Input Connections also Output Connections for LVD See Figure 10 The DC power inputs to...

Страница 14: ...mum of two high current breakers is allowed 1 2 3 4 5 6 7 8 9 10 40 50A LOADS 10 32 1A to 30A LOADS 6 32 0 75 19 1 0 5 12 7 0 378 9 60 Figure 11 Output Barrier Strip Detail 9 5 Form C Relay Contact Ou...

Страница 15: ...is either loss of input power one or more circuit breakers trip or the relay is de energized the normally open contacts close and the normally closed contacts open See table 6 RELAY STATE MEANINGS Rel...

Страница 16: ...Mount it from the front of the rack using the correct offsets to align with existing rack mounted equipment The bracket offsets are every quarter inch from front to back 11 2 Power Connections Input c...

Страница 17: ...asure the resistance between C and N O This which should read open Measure the resistance between C and N C This should read short Replace the blown fuse with a good one or reset the circuit breaker 1...

Страница 18: ...d application 12 4 If the combination panel did not operate properly in the above tests go back and double check the connections and the polarity of the input source to make sure it is correct Please...