SAGEON PSMC I PRODUCT MANUAL
PM990-2999-00, Rev 5
3-10
3.5 ENABLING CHANNELS
The “
Enable Channels
” menu lets the user select only the channels needed for their application.
Removing unused channels allows the SAGEON PSMC I to scan at a higher rate and the user to
access information faster without scanning through unused channels and thresholds. When Enable
Channels is “
Selected
”, the “
Next
” key scrolls through the channels in this order:
Enable Channel Table
1. Plant Voltage
11.
Shunt 9
21. RFA 2
31. RFA 12
2. Plant Current
12.
Load Voltage
22. RFA 3
32. RFA 13
3. Shunt 1
13.
Str 1 Bat Temp
23. RFA 4
33. RFA 14
4. Shunt 2
14. Str 2 Bat Temp
24. RFA 5
34. RFA 15
5. Shunt 3
15. Amb Temp
25. RFA 6
35. RFA 16
6. Shunt 4
16. Charge Fuse
26. RFA 7
36. Ctrl Inhibit
7. Shunt 5
17. Discharge Fuse
27. RFA 8
37. CEMF 1
8. Shunt 6
18. Sense/Control Fuse
28. RFA 9
38. CEMF 2
9. Shunt 7
19. Battery Fuse
29. RFA 10
39. Spare Fuse
10. Shunt 8
20. RFA 1
30. RFA 11
40. LVD
Enter the “
Enable Channels
” menu from the Configure menu by pressing “
Select
”, then press
“
Next
” until the “
Enable Channels
” menu appears, then press “
Select
” again to access the first
channel. Use the “
Next
” key to walk through the channels as shown above, pressing “
Select
” to
disable the unneeded Channels. When completed, press “
Escape
” to return to the initial “
Enabling
Channels
” menu. Use “
next
” or “
Previous
” to reach other Configure sub-menus, or “
Escape
” again
to return to the top Configure menu.
Channel Enable factory defaults
Channels Name
Default State
PLANT VOLTAGE
PERMANENTLY ENABLED
PLANT CURRENT
PERMANENTLY ENABLED
FEEDER CURRENT 1
DISABLED
FEEDER CURRENT 2
DISABLED
FEEDER CURRENT 3
DISABLED
FEEDER CURRENT 4
DISABLED
FEEDER CURRENT 5
DISABLED
FEEDER CURRENT 6
DISABLED
FEEDER CURRENT 7
DISABLED
FEEDER CURRENT 8
DISABLED
FEEDER CURRENT 9
DISABLED
LOAD VOLTAGE
DISABLED
TEMP STRING 1
DISABLED
TEMP STRING 2
DISABLED
AMBIENT TEMP
DISABLED
SENSE FUSE
ENABLED
CHARGE FUSE
ENABLED
DISCHARGE FUSE
ENABLED
BATTERY FUSE
DISABLED
SPARE FUSE
DISABLED