SAGEON PSMC I PRODUCT MANUAL 

PM990-2999-00, Rev 5 

3-17 

 

or both.  The user can also set the ACO cut-off time to: 30, 60, 90 minutes, or Off.  In the Off 
mode the audible alarm will continually sound until the alarm condition is corrected.  If the 
30, 60, or 90 minute ACO time is selected, the user can disable the audible alarm from the 
Main Alarm menu. It will remain off for the selected time unless another alarm occurs.   
While in ACO the yellow ACO LED will be on and the Major and Minor LED’s will blink.

 

The user presses the “

Select

” key to toggle the 

On/Off

 for a major alarm.  Then press “

Next”

 

to reach the Minor alarm, which is also toggled 

On/Off

 with the “

Select

” key.  Pressing 

Next

” again allows the user to use the “

Select

” key to toggle between 30, 60, 90, or Off for 

the ACO time.  Once the selections are made pressing “

Escape

” returns the user to the 

Audible Alarm

 menu. 

Note:

 The audible alarm transducer is rated at 85 DBA @ 10cm which is loud enough for a 

small office or CEV.  Offices where the operator may be more the 25 ft. away or there 
is a high level of back ground noise should use a separate audible alarm panel operated 
by an output relay.  (See Aux. Relay 3.7.10) 

 

3.8.7   System Voltage Sub-Menu 

This menu selects the operating voltage for the SAGEON PSMC I.  The user selects 

24v

 or 

48v

 with any 103-2999-XX model (The default is for a 48V plant).  The “

Select

” key toggles 

between the choices and resets alarm thresholds to the default thresholds for the new voltage 
setting.  

Note:

 Changing the plant voltage will load factory defaults for all thresholds and enabled 

channels. 

Use the “

Next

” key to access the next menu 

3.8.8   Equalize Sub-Menu 

This menu allows the user to choose an Equalize mode.  Use the “

Next

” (up) / “

Prev

” (down) 

keys to scroll through the options of “Timer” and “Auto Eq.”.  Press the “

Select

” key to 

enable the desired mode (s).  Both of these modes can be enabled simultaneously.    

The Timer and Auto Eq. modes will terminate prematurely should a High Temperature “TA” 
alarm occur for Ambient, and if enabled Temp String 1 or Temp String 2.  Timer and Auto 
Eq. equalize modes will terminate in the presence of a Controller Inhibit signal. 

Selecting 

TIMER 

enables the manual equalize mode.  This causes the “Manual Eq Time” 

menu to appear at the top of the Configure menu.  Here the user can configure the duration of 
a manual equalize cycle from 1-255 hours.  Also a top-level “Manual Equalize” menu is 
added where the user can press the “

Select

” key to initiate an equalize cycle.  The PSMC will 

display the number of equalize hours elapsed out of the total number of Eq hours. 

 

Pressing select under the 

AUTO EQ

 menu when disabled will enable it, and when enabled 

will disable it.  When enabled the PSMC displays the Auto Eq. sub-menu.  Here the user 
chooses the Auto-Eq ON threshold; which is the voltage level that the plant must fall below 

Содержание Sageon PSMC I

Страница 1: ...CONTROLLER FOR POWER PLANTS PRODUCT MANUAL FOR 103 2999 XX 24 48 Vdc Model PM990 2999 00 Rev 5 UNIPOWER LLC 65 Industrial Park Rd Dunlap TN 37327 Phone 1 954 346 2442 Toll Free 1 800 440 3504 Web sit...

Страница 2: ...l arrow has turned even partially blue this means the freight has been tipped in transport Make sure the carrier notes this on your receipt before you sign for the freight 2 EQUIPMENT INSPECTION 2 1 W...

Страница 3: ...efer to this number in all correspondence with UNIPOWER LLC 5 INITIAL SETTINGS All equipment is shipped from our production area fully checked and adjusted Do not make any adjustments until you have r...

Страница 4: ...nor does it make UNIPOWER LLC responsible for any damage that might occur during the installation use or maintenance of the equipment described in this manual UNIPOWER LLC also does not guarantee that...

Страница 5: ...INSTALLATION PROCEDURE OUTLINE 2 2 5 INSTALLATION GUIDELINES 3 2 6 WIRING THE SAGEON PSMC I 4 2 6 1 Plant Ground 4 2 6 2 Battery 4 2 6 3 Analog Inputs 5 2 6 4 Binary Inputs 5 2 6 5 Control Relays 6 2...

Страница 6: ...OUTPUT RELAYS 2 4 5 LED TEST MODE 2 4 6 LCD TEST MODE 3 4 7 ALERT TEST MODE 3 CHAPTER FIVE MAINTENANCE 1 CHAPTER SIX SPARING ACCESSORIES OPTIONAL PARTS 1 CHAPTER SEVEN APPENDIX LISTINGS 1 7 1 FLOW CHA...

Страница 7: ...VA high voltage alarm HVSD high voltage shutdown IEC International Electrical Commission IEEE Institute of Electrical and Electronic Engineers LED light emitting diode LSD least significant digit LVA...

Страница 8: ...ications Equipment Engineering Standards December 1984 PUB 77350 U S West Telecommunications Equipment Installation Removal Guidelines June 1990 PE 7 1985 Communications Type Battery Chargers NEMA ANS...

Страница 9: ...isconnect status Controller inhibit input making the SAGEON PSMC I a secondary controller The SAGEON PSMC I has the following alarm and control output relays all relay contacts rated 60W 62 5VA Dual F...

Страница 10: ...2999 19A or 103 2999 23A respectively Height 1 75 1RU Depth 11 0 Weight 10 0 lbs 1 3 2 Environmental Specifications Operating temperature 0 C to 50 C 32 F to 122 F Storage temperature 40 C to 85 C 40...

Страница 11: ...current and the number of active alarms When the Load Voltage channel has been enabled the front panel will change to show the plant voltage load voltage current and the number of active alarms If an...

Страница 12: ...source and where applicable the alarm input requirement FRONT PANEL ALARM INDICATIONS Major Alarm MAJ Fuse Alarm FA Very Low Voltage VLVA Low Voltage Disconnect LVD High Voltage Shutdown HVSD Watchdo...

Страница 13: ...rm LVA High voltage alarm HVA Audible Cut off Status ACO Yellow LED LVA alarm indicator Triggered by user defined voltage threshold see Set Thresholds Section 3 4 Yellow LED HVA alarm indicator Trigge...

Страница 14: ...alarms An auxiliary relay AUX is provided that the user can define as a major minor equalize audible alarm or any specific analog or binary input channel alarm If triggered the WD LED will flash A WAT...

Страница 15: ...procedure assumes a custom SAGEON PSMC I installation in an existing power plant 2 2 1 The SAGEON PSMC I should be mounted at eye level for easy access and display viewing The unit requires only one...

Страница 16: ...e SAGEON PSMC I internal ground to the power plant ground reducing noise levels and providing a convenient plant ground connection point for ground closures on output relays 2 4 4 A list of connection...

Страница 17: ...ed ring lugs to be connected with battery strap hardware Sensor detection circuits are isolated from battery potential Sensors come with 30 ft leads which can be extended with butt splices if necessar...

Страница 18: ...ng Take care to properly insert and seat the terminal blocks after wiring If front access is required be sure to leave enough cable length 3 4 ft to remove the PSMC from the rack without disconnecting...

Страница 19: ...extended refer to the Datasheet for proper connections See Fig 8 of PN drawing WARNING Improper temperature sensor connection may damage the sensors Always verify proper connections and avoid shortin...

Страница 20: ...is connected to each input 2 6 4 5 The Control Inhibit INH input requires a ground closure input The Control Inhibit INH input relinquishes control functions from the SAGEON PSMC I When triggered the...

Страница 21: ...he Auxiliary Relay section of this manual The relays requiring ground closures should have been jumpered to PLANT GRD at the beginning of the wiring process based on the Datasheet requirements Refer t...

Страница 22: ...MP DIFF STR1 TEMP DIFF LOWN AMB TEMP HIGH AMB TEMP LOW BATT TEMP STR 2 LOW BATT TEMP STR1 HI BATT TEMP STR 2 HI BATT TEMP STR 1 HI LOAD VOLTAGE HIGH VOLTAGE LOW VOLTAGE VERY LOW VOLTAGE EXT LVD CEMF 1...

Страница 23: ...ut and default to the idle screen from any sub menu within 5 minutes The default idle screen always displays plant voltage Vb and number of alarms A configuration option allows the screen to also disp...

Страница 24: ...on menu provides sub menus organized for functionality in custom configuring the SAGEON PSMC I for the user s application It also provides menus for calibrating analog input channels setting alarm thr...

Страница 25: ...lue From the idle display menu pressing Select Next or Previous brings the user to the Status menu From the Status menu the Next and Previous keys can be used to access any of the main menus Once the...

Страница 26: ...the user which specific fuse type and rectifier is in alarm Pressing Escape when completed will return the user to the main Select Mode Menu Configure The Configure menu provides all of the sub menus...

Страница 27: ...nnels menu Calibrate Zero Part of analog channel calibration eliminates measurement errors due to sense lead length and noise This menu requires the user to short the measurement leads at the actual s...

Страница 28: ...ting Up Equalize section of manual Aux Relay Sets up Auxiliary Relay parameters See Setting up Auxiliary Relay section of manual Backlight Usage Toggles between having the Backlight turn on with any k...

Страница 29: ...ear when the user first enters some menus Use the following table of Factory settings to determine the initial status for these menus Configuration Defaults Channels Name Default State PASSWORD OFF NE...

Страница 30: ...8 9 AUXILIARY RELAY SUB MENU for setting up the Aux relay The table below lists the SAGEON PSMC I s default thresholds for 24V 48V operation Enter the Set Thresholds menu from the Configure menu by p...

Страница 31: ...p Ambient 0 F 200 F 95 0 F Low Temp Ambient 0 F 200 F 32 0 F String 1 Temp Diff 0 F 200 F 20 0 F String 2 Temp Diff 0 F 200 F 20 0 F 24V PLANT ALARM THRES FROM TO DEFAULT High Voltage Shutdwn 25 0 V 3...

Страница 32: ...e Fuse 10 Shunt 8 20 RFA 1 30 RFA 11 40 LVD Enter the Enable Channels menu from the Configure menu by pressing Select then press Next until the Enable Channels menu appears then press Select again to...

Страница 33: ...completed the SAGEON PSMC I should only require a yearly verification of the measurement accuracy 3 6 1 Calibrate Zero The Calibrate Zero menu provides a fast and simple means to null out the analog...

Страница 34: ...s to toggle the input to YES 5 Press Select again and the SAGEON PSMC I will zero the channel and return to the initial display showing the offset as zero PLANT VOLTAGE READING 0 00 6 Only those analo...

Страница 35: ...e sensor test jack voltage outputs for calibration See sections 3 6 3 and 3 6 4 before calibrating the gain of shunt and temperature inputs To maximize the accuracy of the shunt input calibrations cer...

Страница 36: ...ne the shunts full scale rating such as 600A 50mV full scale Then multiply the measured value by the full scale rating and divide the result by 50 to get the actual current value This calculated value...

Страница 37: ...t display polarity for positive or negative readings 4 Setting temperature display for F or C display 5 Setting idle display for current or current ambient temperature toggle 6 Setting up the audible...

Страница 38: ...his menu Simply set the polarity to match the plant current polarity using the Select key to toggle the Negative amps Yes to No for a positive polarity on current readings The setting affects all curr...

Страница 39: ...el The default is for a 48V plant The Select key toggles between the choices and resets alarm thresholds to the default thresholds for the new voltage setting Note Changing the plant voltage will load...

Страница 40: ...o De Energize FAIL SAFE MODE when an alarm occurs Pressing Select third time will disable the Aux relay When the selection is Energize or De Energize all previous selections are disabled Pressing Sele...

Страница 41: ...CHANNELS Press Select when the Analog Channels menu appears to enter the analog test mode The first enabled analog channel will appear with its current value displayed and updated continuously The use...

Страница 42: ...m monitor will send false nuisance alarm status if toggled while in the output relay test mode Warning Turning the control relays for Equalize or HVSD on in the test mode will result in the power plan...

Страница 43: ...t again Note Any LCD segment or pixel that is not illuminated indicates a SAGEON PSMC I internal circuitry failure requiring a service call to repair When completed press Next or Previous to access ot...

Страница 44: ...require any regular maintenance Once a year the analog channel calibration should be verified against actual measurements On a 2 to 5 year basis a complete system test should take place that checks al...

Страница 45: ...s screw terminal block Optional equipment Temperature Sensor Kit 385 5627 11 30ft cable Direct Connect to PSMC Measurement of ambient or battery string temperatures Longer cable lengths available cont...

Страница 46: ...IX LISTINGS 7 1 FLOW CHARTS FOR SAGEON PSMC I MENU STRUCTURES Appendix A Main Menus Appendix B Configuration Menu Appendix C Enable Channels Menu Appendix D Enable Thresholds Menu Appendix E Set Thres...

Страница 47: ...SAGEON PSMC I PRODUCT MANUAL PM990 2999 00 Rev 5 7 2 Appendix H Set Shunt Scales Menu Appendix I System Options Menu Appendix J Auxiliary Relay Menu Appendix K Test Menu...

Страница 48: ...e The SEL key toggles equalize on or off Main Menu Status submenu Description STATUS Plant Voltage Voltage reading of the Battery or Plant Ambient Temp Temperature reading from the ambient temperature...

Страница 49: ...e shunt inputs CALIBRATE ZEROS Allows setting zeros for analog inputs CALIBRATE GAINS Allows setting gains for analog inputs ENABLE CHANNELS Allows enabling disabling reading analog and binary inputs...

Страница 50: ...ier failure 7 input RECT FAIL 8 Enables or disables the rectifier failure 8 input RECT FAIL 9 Enables or disables the rectifier failure 9 input RECT FAIL 10 Enables or disables the rectifier failure 1...

Страница 51: ...disables the high battery string 2 temperature threshold HI LOAD VOLTAGE Enables disables the high load voltage threshold PLANT CURRENT Enables disables the plant over current threshold SHUNT 1 CURRE...

Страница 52: ...S2 Changes the High Battery String 2 Temperature alarm threshold HI LOAD VOLTAGE Changes the High Load Voltage alarm threshold PLANT CURRENT Changes the Plant over Current alarm threshold SHUNT 1 CURR...

Страница 53: ...EMP STRING 2 analog input LOAD VOLTAGE Remove offset from the LOAD VOLTAGE analog input SHUNT CURRENT 1 Remove offset from the SHUNT 1 analog input SHUNT CURRENT 2 Remove offset from the SHUNT 2 analo...

Страница 54: ...LOAD VOLTAGE Adjust gain of the LOAD VOLTAGE analog input SHUNT CURRENT 1 Adjust gain of the SHUNT CURRENT 1 analog input SHUNT CURRENT 2 Adjust gain of the SHUNT CURRENT 2 analog input SHUNT CURRENT...

Страница 55: ...of the feeder shunt 9 APPENDIX I SYSTEM OPTIONS MENU Configure Menu Submenu Description PASSWORD This menu allows turning the system password protection on or off ABOUT PSMC Shows the software version...

Страница 56: ...iliary relay maps to any rectifier failure alarm SPARE FUSE The auxiliary relay maps to the spare fuse alarm BATTERY FUSE The auxiliary relay maps to the battery fuse alarm SENSE FUSE The auxiliary re...

Страница 57: ...G CHANNEL PLANT VOLTAGE Analog input relays select the Plant battery voltage continuously AMBIENT TEMP Analog input relays select the ambient temperature input continuously TEMP STRING Analog input re...

Страница 58: ...ALL x Indicates if all alarm relays are energized Note x Represents either CLOSED energized or OPEN de energized The state of the output relay will toggle when the select key is pressed Test Menu Sub...

Страница 59: ...SAGEON PSMC I PRODUCT MANUAL PM990 2999 00 Rev 5 7 14 7 2 PROGRAMMING DATA WORK SHEET Sageon PSMC I Datasheet 7 3 REFERENCE DRAWINGS PN 103 2999 Power System Monitor Controller SAGEON PSMC I...

Страница 60: ......

Страница 61: ......

Страница 62: ......

Страница 63: ......

Страница 64: ......

Отзывы: