SAGEON PSMC I PRODUCT MANUAL
PM990-2999-00, Rev 5
3-15
Enter the “
Set Shunt Scales
” menu from the main Configure menu by pressing “
Select
”, then press
“
Next
” or “
Previous
” until the “
Set Shunt Scales
” menu appears. Pressing “
Select
” again enters the
menu with the display showing:
Plant Shunt Scale
Set at
:
600A
Press “
Select
” again to modify the current setting and the display changes to:
Plant Shunt Scale
Modify
:
600A
Press the “
Next
” key to raise the value, or the “
Previous
” key to lower the value, in 100A increments.
When the desired shunt value is reached press “
Select
” again to enter the value. The display will return
the “
Set at
” display with the selected value shown. The user can then use the “
Next
” or “
Previous
” keys
to select any of the other nine shunt feeder channels to change the scaling as needed in the same manner.
When all the channels have been set press “
Escape
” one or more times to return to the Configure menu or
to main default screen.
3.8 SYSTEM OPTIONS MENU
The system options menu provides eleven sub-menus that include:
1.
Enabling a password for access
2.
Setting the voltage display polarity for positive or negative readings
3.
Setting the current display polarity for positive or negative readings
4.
Setting temperature display for °F or °C display
5.
Setting idle display for current or current / ambient temperature toggle
6.
Setting up the audible alarm
7.
Setting the system operation voltage 24V / 48V
8.
Setting the Equalize mode for Manual timed or AutoEq.
9.
Setting up the Auxiliary relay mode
10.
Setting the Backlight to turn on by KEY-PRESS, remain ON constantly, or
OFF always
11.
Display the Software revision level
Enter the “
System Options
” menu from the main Configure menu by pressing “
Select
”, then use
the “
Next
” or
Previous
” keys to locate the
System Options
menu. Press “
Select
” again when the
“
System Options
” menu appears to access the first sub-menu
System Password
. Use the “
Next
”
key to walk through the menus in the order shown above. The following procedures assume a new
installation and a sequential procedure through each sub-menu.
3.8.1 System Password Sub-Menu
The system password prevents a user from accessing any of the Configure or Output Relay
Test menus thereby protecting the system configuration from an unauthorized change or
unauthorized trigger of nuisance alarms. When the System Password sub-menu appears, press
the “
Select
” key to turn the password
On
or
Off
.
System Password is: 09191
The system password does not take affect until after 5min. of idle time (without key-presses)