SAGEON PSMC I PRODUCT MANUAL
PM990-2999-00, Rev 5
2-8
required connection to the normally open (
NO
) or normally closed (
NC
) terminals
as required. Refer to the Datasheet for required connections.
2.6.6.4
The other output relays
HVA, LVA, VLA, FA, LVD, RFA, TEMP, CEMF
, and
WD (WATCHDOG)
are generally only used when a remote alarm call-out device
is part of the power plant or with an alarm monitor panel in a large central office.
Make the required connection to the normally open (
NO
) or normally closed (
NC
)
terminals as required. Refer to the Datasheet for required connections.
2.6.6.5
The Control Inhibit (
CTRL INH
) relay is triggered by the Inhibit input, which
causes to PMSC to relinquish control of the power plant. This relay would only be
used in a large power plant where the SAGEON PSMC I was designated as a back up
monitor/controller. This relay would confirm the status of the SAGEON PSMC I.
Contact the Factory for information on implementing master/slave control scheme.
2.6.6.6
The Auxiliary (
AUX
) relay is a user definable relay and can be configured to trigger
of any ONE of any number of alarms. The Auxiliary relay can be triggered from any
(1) of the following: a MAJOR, MINOR, SINGLE RFA, ANY RFA, PLANT
OVER-CURRENT, SINGLE FEED OVER-CURRENT, ANY OVER-CURRENT,
HVSD, CTRL INH, SINGLE FA, STR 2 TEMP DIFF, STR1 TEMP DIFF, LOWN
AMB TEMP, HIGH AMB TEMP, LOW BATT TEMP STR 2, LOW BATT TEMP
STR1, HI BATT TEMP STR 2, HI BATT TEMP STR 1 HI LOAD VOLTAGE,
HIGH VOLTAGE, LOW VOLTAGE, VERY LOW VOLTAGE, EXT LVD, CEMF
1, CEMF 2. When triggered the Auxiliary alarm will flash the
WD
LED on the
display panel.
This completes the Output Relay connections. Stop and verify these connections and update the
Datasheet if necessary. See Programming the Auxiliary Relay and Setting Up Thresholds section after
the installation wiring is complete.
2.7
PRODUCT SUPPORT
Product support can be obtained using the following addresses and telephone numbers.
Corporate office:
UNIPOWER, LLC
210 N University Dr
Coral Springs, FL 33071
United States
Manufacturing facility:
UNIPOWER, LLC
65 Industrial Park Rd
Dunlap, TN 37327
United States
Manufacturing facility:
UNIPOWER Slovakia SRO
ZLATOVSKA 1279
Business Center 22
91105 Trencin, Slovakia
Phone: +1-954-346-2442
Toll Free: 1-800-440-3504
Web site – www.unipowerco.com
When contacting UNIPOWER, please be prepared to provide:
1.
The product model number, spec number, S build number, and serial number - see the equipment
nameplate on the front panel
2.
Your company’s name and address
3.
Your name and title
4.
The reason for the contact
5.
If there is a problem with product operation:
•
Is the problem intermittent or continuous?
•
What revision is the firmware?
•
What actions were being performed prior to the appearance of the problem?
•
What actions have been taken since the problem occurred?