UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
11
Revision 2.05
Of 107
6.1.3. Access Level 3
Accessible for personnel trained and authorized for:
−
Reconfiguration of specific data – of the protected site or of the fire control panel – saved
in the memory;
−
Maintenance of the fire control panel.
This level has two sublevels of access - 3A and 3B.
Level 3, sublevel 3A, is accessed through a password entered at Access level 2. At this sublevel
the functions for reconfiguration of specific data for the protected site or the fire control panel are
accessible (see section 13).
Level 3, sublevel 3B is accessed when the fire control panel is opened. The following features are
accessible:
−
Replacing a burnt fuse;
−
Connecting fire alarm loops and executive devices.
6.1.4. Access Level 4
Accessible for personnel trained and authorized by the Producer to repair the fire control panel
and to modify the software. Special means are required to enter this level.
6.2. Indications and buttons for control
Table 1 gives detail description of the indications for each status, Table 2 presents the basic
means for control. Appendix 1 shows the front panel of IFS7002.
Table 1
Conditions of the fire control panel
Indication
All conditions -
The fire control panel is power supplied
Indicator
Power supply
–
continuous green light
Fire condition
Common indicator
Fire condition
–
flashing red light
Fault condition -
All faults except for
Battery Low
Common indicator
Fault condition
– flashing yellow light
Fault condition – System error
Indicator
System error
- continuous
yellow light
Fault condition -
Fault in mains supply
Indicator
Fault in mains supply -
flashing yellow light
Disabled component -
Disabled zone, addressable device or monitored
output
Indicator
Disabled component
-
continuous yellow light
Test condition
Indicator
Test
–
continuous yellow light
Fire condition
Local sounder – discontinuous signal: 0.5 s
sound, followed by 0.5s break
Fault condition - All faults except for
Battery Low
Local sounder – discontinuous signal: 1 s
sound, followed by 1 s break
Fault condition -
Low battery
Local sounder – discontinuous signal: 1 s
sound, followed by 3 s break