3-10
PowerWAVE 9000 DPA UPS - Installation
(Issue 2.1 Oct. 2009)
Figure 3.3: Single Input Block Diagram with Cable and Fuse Sizing
Frame
Power
(kVA)
Single Input
(3 x 400V)
Output
(3x400V, 0.8 pf)
Battery
Fuse A
(A)
Cable A
(mm
2
)
Max Input
with battery
charging
(A)
Cable D
(mm
2
)
Nominal
Current
(A)
Fuse E
(A)
Cable E
(mm
2
)
DPA-25
25
3x63
5x10
34
5x10
36
DC Fuses and cables
are bespoke to the
installation.
DPA-75
75
3x125
5x50
101
5x50
108
DPA-125
125
3x225
5x95
169
5x95
181
DPA-50
80
3x100
5x25
67
5x25
72
DPA-150
150
3x250
5x120 or
5x(2x50)
202
5x120 or
5x(2x50)
218
DPA-250
250
3x400
5x(2x95)
337
5x(2x95)
362
Note:
The above are recommendations only. All fuses and cables must comply with prescribed IEC standards or
local regulations.
Rectifier
Inverter
Static Switch
F1
F2
Rectifier
Inverter
Static Switch
F1
F2
Rectifier
Inverter
Static Switch
F1
F2
IA2-1
IA2-2
IA2-3
Maintenance Bypass IA1
UPS M
o
d
u
le
1
UPS M
o
d
u
le
2
UPS M
o
d
u
le
3
Upgrade
Frame
Fuse E
Load
Cable E
Cable D
Mains
Supply
Fuse A
Cable A
Содержание PowerWAVE 9000 DPA