10-4
PowerWAVE 9000 DPA UPS - Specifications
(Issue 2.1 Oct. 2009)
10.4 Output
Module Range
MD
MX
Module Type
DPA
10
DPA
15
DPA
20
DPA
25
DPA
30
DPA
40
DPA
50
Output Rated Power per Module
kVA
10
15
20
25
30
40
45 1)
Output Rated Power per Module
KW
8
12
16
20
24
32
40
Output Current In @ cos
Φ
1.0 (400 V)
A 11.6 17.4 23.2 29 35 46.5 58
Output Rated Voltage
V
3x380/220V or 3x400/230V or 3x415/240V
Output Voltage Stability
%
Static: < +/- 1% Dynamic
(Step load 0%-100% or 100%-0%) < +/- 4%
Output Voltage Distortion
%
With Linear Load < +/- 2% With Non-linear Load
(EN62040-3:2001) < +/- 4%
Output Frequency
Hz
50 Hz or 60 Hz
Output Frequency Tolerance
%
Synchronized with mains < +/- 2 % (selectable) or
< +/- 4 % Free r/- 0.1 %
Bypass operation
At Nominal Input voltage of 3x400 V +/- 15 % or
190 V to 264 V ph-N
Permissible Unbalanced Load
(All 3 phases regulated independently)
% 100%
Phase Angle Tolerance
(With 100 % Unbalanced load)
Deg.
+/- 0 deg.
Overload Capability on Inverter
%
125 % load 10 min. 150 % load 60 sec.
Output short capability (RMS)
A
Inverter: 2 x In during 250 ms
Bypass: 10 x In during 10 ms
Crest - Factor
3 : 1
1) On Inverter mode 50 KVA/40kW on Bypass mode 45 KVA/40kW