PART IV: MAINTENANCE
32
Removing the combustion head
Check the gas lances positioning on their reference, in order to re-establish the same positioning later
Close the manual valves (MV) at the gas flexible hoses inlet
Remove the gas pilot (GP) after having disconnected the flexible hoses.
Remove the gas lances (GL) after having disconnected the flexible hoses
Remove all the electrical connections.
Remove the flame detector out of its holder (FSH)
Loosen the (V) screws that fasten the top plate P
Remove the top plate (P) and the gas pilot (the operation is simplified by the internal support with guide)
Clean the combustion head by means of a vacuum cleaner; scrape off the scale by means of a metallic brush.
To assemble the combustion head, reverse the operations described bove
GP
GP
FSH
GL
GP
GL
FSH
V
P
MV
H
Keys
FSH
flame scanner holder
GP
Gas pilot
GL
Gas lances
MV
manual valve
P
top plate
V
screws
H
lance reference ring