PART III: OPERATION
22
Start-up procedure
1
Turn the burner on.
2
the LMV control box starts the system test cycle: the AZL display shows the
System Test
message; at the end of the test, it shows
the main page and the system stops (the safety chain is open) waiting for the startup enabling signal (standby - Program phase no.
12)
Main page
3
check the fan motor rotation (see related paragraph).
4
make the safety chain enabling the system to start up
5
the combustion cycle starts: the system will show the operating stages
- Prepurging
(program phase no.30)
- Driving to ignition position
(program phase no.36)
- Ignition position
(program phase no.38)
- Fuel
(the fuel solenoid valves open)
- Flame
(the flame lights up)
- Driving to low flame
(the actuator drives to low flame).
NOTE:
the
C
and
A
, on the .
Once the ignition cycle ends, the main page is shown:
Main page
Set point:
temperature set-point
Act value:
actual temperature value
Load:
load percentage (burner output)
Flame:
percentage of flame detection current.
By pressing the ENTER key the display shows the second page:
Second page
Fuel
: it shows (in degrees) the fuel actuator position.
Air
: it shows (in degrees) the air actuator position.
Ax1..3
: auxiliaries.
VSD
: % value on the inverter maximum frequency
O2
: oxygen percentage
Ld
: load percentage (burner output).
Press the ENTER key to go back to the main page.
To access the
main menu
, from the main page, press the ESC key tiwce:
Setpoint
80°C
Act.value
78°C
Fuel
GAS
Standby
12
Setpoint
80°C
Act.value
78°C
Load
24%
Flame
60%
Fuel
0.0
Air
1.8
Ax
VSD
0.0
Ax
O2
Ax
Ld.
0.0
Содержание URB40