32
431
ucPin2Test
Pin short circuit test detected an error!Short-circuit between
pins, pull-up of input stage defective or pin is externally stuck
at 0
440
0
sIO.sIn.uiTestSignalTimeout expired
450
0
Main power relay (K2) does not switch correctly to off when
out of power.
451
ucRelay
Relay does not switch correctly, when relay power is
enabled (for details see enum teRelais)
460
uiFaultParam
Failure of relais power switching or readback of relay coils of
K1 or K2Param2: Bit 0 is set if readback line of K1 is
erroneous, Bit 1 is set if readback line of K2 is erroneous
461
uiFaultParam
Readback status of relay K1 or K2 differs from desired
switching status, relay propably defect.Param2:Bit 0: nominal
state of K1Bit 1: nominal state of K2Bit 8: state of readback line
of K1Bit 9: state of readback line of K2
500
0
Timeout while waiting for end of write cycle
501
0
SLA+W has been transmitted; NO ACK has been received
502
0
SLA+R has been transmitted; NO ACK has been received
503
0
Data byte has been transmitted; NO ACK has been received
504
0
BUS error due to an illegal START or STOP condition
505
0
Arbitration lost in SLA+R/W or Data bytes
510
ulI2CStat
Unknown/invalid state!
600
sSRCtrl.uiOffset
Correction of defective triple in Safety RAM structure failed
610
(ulong32)pucDst
Invalid destination address
620
(ulong32)puiDst
Invalid destination address
630
(ulong32)pulDst
Invalid destination address
700
0
CPU selftest failed
701
sSelftest.sMngr.eState
state-event-machine failed with AC_ERR
710
sSelftest.sWD.eErrorState
Watchdog selftest failed
711
sSelftest.sWD.eState
Invalid default case
720
Selftest.sVM.ucTest2Perform
Invalid default case
721
Selftest.sVM.eErrorState
Supply voltage monitor selftest failed
722
Selftest.sVM.eState
Invalid default case
730
sSelftest.sRR.eErrorState
Relay release circuit selftest failed
731
sSelftest.sRR.eState
Invalid default case
740
sSelftest.sRPW.eErrorState
Relay PWR release circuit selftest failed
741
sSelftest.sRPW.eState
Invalid default case
750
0: USR-Stack, 1: IRQ-Stack
Stack overflow detected
751
0
Stackaddress is NULL-Pointer
752
0
Stackaddress is NULL-Pointer
800
sWDog.ulReleasePtrn1
Trigger release patterns are invalid!
810
eFeedIndex
Invalid Feed Index
820
eTriggerCtrl
Invalid Trigger Mode
830
0
No valid watchdog trigger received (frequency or duty cycle
invalid)
900
uiErrorCode
Fault from LPC_API error handler
920
0
Invalid entry in iStoerResRam
930
uiMaskedFaultCode
uiMaskedFaultCode out of range!
1200
0
Flame signal doesn't disappear during self-test
1210
sIFD.eTestState
Invalid default case
1220
sIFD.uiClock
UP is missing test impulses
1221
sIFD.uiClock
Test signal duration too short
1222
sIFD.uiClock
Test signal duration too short
1240
0
Detected short circuit of LDR
1250
uiADValue
Circuit selftest failed, A/D value out of expected range
1260
sLDR.eTestState
Invalid default case
1270
sLDR.uiClock
Test interval too long
1271
sLDR.uiClock
HP released test pin too late
1272
sLDR.uiClock
HP released test pin too early
Содержание LAMTEC BT3 Series
Страница 46: ...PART IV MAINTENANCE 46...
Страница 47: ......
Страница 98: ......
Страница 99: ......
Страница 100: ......
Страница 114: ......
Страница 123: ......
Страница 124: ......
Страница 125: ...WB1 QF A QF B...
Страница 126: ......
Страница 127: ......
Страница 129: ......
Страница 130: ......
Страница 131: ...INTERFACE...
Страница 132: ...R1 R2 POT...
Страница 135: ......
Страница 136: ......
Страница 137: ......