13
Use the cursor key
to select the next page and confirm this with Enter
Page 2 of inputs
1
Digital inputs pictogram
2
Jump to next page
3
Oil pressure min present [no] – terminal X05
4
Gas pressure min present [yes] – terminal X05
5
Air pressure min present [yes] – terminal X08
Use the cursor key
to select the next page and confirm this with Enter
Page 3 of inputs
1
Digital inputs pictogram
2
Jump to previous page
3
Jump to next page
4
Safety interlock chain oil closed [no] – terminal X06
5
Safety interlock chain gas closed [no]
6
Safety interlock chain boiler closed [no]
The signals in points 4 and 5 in Page 2 of inputs menu are "logical" signals, not "physical". The BT3xx supports either oil
or gas operation, but cannot be switched. There‐fore there are no separate signals for the oil or gas safety interlock
chain. The signal on terminal X06 is thus generally known as "safety interlock chain burner".