27
4
LIST OF FAULT CODES
To see the "historical lock‐out" see paragraph 3.1.4
Fault Code
D1
D2
Description
0
Unknown fault (internal error)
1
Pre-ventilation signal is still active.
2
Parasitic light detected
3
Flame blow-off during ignition
4
Flame blow-off during operation
5
Flame signal does not appear during the first safety time
6
Flame signal extinguishes during stabilization time
7
Flame signal extinguishes during first safety time
8
Flame signal extinguishes during the second safety time
9
Flame signal does not appear during the safety time
10
Flame signal extinguishes during the safety time
11
Monitoring for parasitic light does not last the required 5 seconds
13
Main flame appears during ignition
103
Miscellaneous data invalid
105
Curve data are invalid or not available.
Curve set / Fuel number
106
Parameters between both controllers are inconsistent Possible cause Parameter No.
107
Configuration is not valid see chapter 3 Assignment of
120
Different operation modes on both controllers
121
Correction is out of range
Channel (x)
141
Channel feedback changes too fast
Channel (x)
151
Recirculation damper is deactivated
Channel (x)
170
Short circuit of LDR flame detector
191
First monitoring band exceeded for to long
Channel (x)
201
First monitoring band fall short for to long
Channel (x)
211
Second monitoringband exceeded for to long
Channel (x)
221
Second monitoring band fall short for to long
Channel (x)
231
Fuel/air ratio control is blocked
Channel (x)
241
Actuator doesn´t move, i.e. no position feedback
Channel
0 = backward, 1 = forward
251
Actuator cannot find reference position
Channel
261
Actuator returns invalid position (difference to target position too Channel
271
Actuator position changes too fast, e.g. slip
Channel
281
Actuator feedback not correct
Channel
320
Open broken wire at firing rate input
321
Open broken wire at feedback channel
Channel (x)
351
Invalid fuel change while burner is running
352
Invalid combination of fuel signals (no signals)
353
Invalid combination of fuel signals (several signals)
362
Fault shut-down due to a missing bruner maintenance
363
Smallest valid O2 value deceeded
371
Outpout for internal firing-rate is defective
372
Difference of the burner firing-rate values between main processor
381
Deviation between main processor an watchdog controller too Correction channel
391
Curve set has changed during programming
393
Emergency shut-down activated
394
Burner ON/OFF signal from the user interface turned off
451
Being operating mode for ignition not all channels are in ignition Channel
600
Program monitoring time (FAT) exceeded
601
Failure during leakage test: gas pressure still active
602
Failure during leakage test: no gas pressure detected
603
Manual venting of the gas line required!
Содержание LAMTEC BT3 Series
Страница 46: ...PART IV MAINTENANCE 46...
Страница 47: ......
Страница 98: ......
Страница 99: ......
Страница 100: ......
Страница 114: ......
Страница 123: ......
Страница 124: ......
Страница 125: ...WB1 QF A QF B...
Страница 126: ......
Страница 127: ......
Страница 129: ......
Страница 130: ......
Страница 131: ...INTERFACE...
Страница 132: ...R1 R2 POT...
Страница 135: ......
Страница 136: ......
Страница 137: ......