PART IV: MAINTENANCE
41
Electrodes Adjustment
Important Note: Check the ignition and detection electrodes after removing/adjusting the combustion head.
Adjust the electrodes position according to the electrodes type installed on the burner. Follow the quotes shown on the next picture.
ATTENTION: avoid the ignition and detection electrodes to contact metallic parts (blast tube, head, etc.), other-
wise the boiler’s operation would be compromised. Check the electrodes position after any intervention on the
combustion head.
electrodes - type
- RX92-FGR, RX92R-FGR
the gap between ignition electrode
E
and grounded electrode
M
must be
3,6 mm
. Ignition electrod must be positioned over
the
G
hole.
Electrodes lean out from the diffuser about
F = 6 mm
F
F = 6 mm
E
M
G
electrodes - type
- RX512-FGR, RX512R-FGR
electrodes - type
- RX515-FGR