24
The display shows the curve setting menu ".
Curve setting menu
1
Ignition position firing‐rate point
2
Set‐point channel 1, air
3
Actual value channel 1, air
4
Set‐point channel 2, combustible
5
Actual value channel 2, combustible
6
Set‐point channel 3, (off, air or actuator FGR)
7
Actual value channel 3 (off, air or actuator FGR)
8
Curve data for this firing‐rate point already exists
Use the cursor keys
to set the firing‐rate point and confrm with Enter
Set‐point channel
1 is chosen (displayed in reverse).
Use the cursor keys
to set the channel’s actuator position.
Use the cursor keys
to switch to the next channel.
Use the cursor keys
to set actuator’s position in the selected firing‐rate point.
Set the position of the actuator at the desired combustion point with the cursor key.
The actuators run to the adjusted position immediatelly after adjusting it.
The fan motor must run to adjust channel 4.
“Accept or discard the entry!”
The display changes to the firing‐rate selection menu.
T
he following firing rate point are available:
Ignition point
, 200, 250, 300, 400, 500, 600, 700, 800, 900, 999
Set your firing rate points as described above and confirm it with Enter
If you keep key
pressed for more than 2 seconds the menue "Curve setting of actuating drives" you
will cause a fault shut‐down.
AIR
GAS FGR
Содержание LAMTEC BT3 Series
Страница 46: ...PART IV MAINTENANCE 46...
Страница 47: ......
Страница 98: ......
Страница 99: ......
Страница 100: ......
Страница 114: ......
Страница 123: ......
Страница 124: ......
Страница 125: ...WB1 QF A QF B...
Страница 126: ......
Страница 127: ......
Страница 129: ......
Страница 130: ......
Страница 131: ...INTERFACE...
Страница 132: ...R1 R2 POT...
Страница 135: ......
Страница 136: ......
Страница 137: ......