background image

35

MAINTENANCE

5

5.1 - GENERAL RULES

Before effecting any operation of cleaning or
maintenance, disconnect the boiler from the
electrical supply acting on the main switch
onto the panel board.
In case of failure or bad operation of the boiler,
switch it off, abstaining your self from any
attempt of reparation or direct intervention.
Exclusively address to professionally qualified
personnel.
The possible reparation of the boiler must be
effected by an authorized service center
using only original spare parts.

The non respect of the above can jeopardize
the safety of the boiler.
To guarantee the efficiency of the boiler and
for its correct operation it is essential to submit
the boiler to an annual maintenance, through
a professionally qualified technician, according
to the indications of the manufacturer.
When it is decided not to use the boiler
anymore, the parts which can be potential
sources of danger shall be made harmless.
After a month of boiler operation, open the
front door and ascertain the smoke pipes are
clean.

In case of a heavy dirtiness:
-

Remove the turbulators from smoke pipes.

-

Clean all the smoke pipes using the brush
delivered with the boiler.

-

Open the two cleaning doors on the sides
of the smoke chamber and remove, with
a vacuum cleaner all the soot.

-

Relocate the two cleaning doors and the
turbulators; then close the boiler front door
and check for soundness all around the
sealing rope.

-   Then adjust the burner.
Note: With a burner properly adjusted only a
cleanup at the season end is necessary.

5.2 - ORDINARY

MAINTENANCE

The boiler operating condition are very different
from one case to the other and depend on
the fuel used, on the adjustment of the burner,
on the number of starting, on the C.H. system
characteristics, etc. and for that reason it is
not possible to establish, in advance, the
frequency of the maintenances.
It is, then, necessary that the technician, who
performs the first cleaning, esthablish the
cleaning frequency on the base of the boiler
status.
Generally, we suggest the following frequency,
according to the fuel used:
-   Gas fired boilers: once a year.
-

Oil fired boilers: twice a year or more often
if there is reason to doubte of  their
adjustment.

In any case the local rules in force have to
complied with.
We suggest to shake the turbulators, without
removing them from the smoke tubes, at least
once an month of operation, not to allow the
soot blocking them and making them extremely
difficult to be removed.
During the operations of ordinary maintenance
it will be necessary to brush the tube bundle

- after the removal of the turbulators - and
the furnace and collect the soots through the
cleaning doors on the smoke chamber.
Besides it will be necessary to verify the good
operation of the protection and control
devices (thermostats, thermometers) of the
boiler and of the plant (manometers, flow
and pressure switches, expansion vessels)
and all the safety devices.
In this occasion it will be necessary to notice
the quantity of reinstatement water used and
decide, also in base to its hardness, an
intervention of preventive descaling.
It must be considered that the calcium and
magnesium salts dissolved in the raw water,
with repeated reinstatements, can cause
deposits in the boiler that hinder the inner
circulation and subsequent overheating of
the wall plates with possible serious damages
that cannot be attributed to the constructive
geometry and/or to the materials used and
to the constructive technique and, therefore,
they are not covered by guarantee.
On the occasion of the ordinary maintenance
it is useful to perform a small discharge from
the boiler to verify if sludges escape.
In affirmative case, it will be necessary to

prolong the discharge up to get clear water.
At the end of the drainage it will be necessary
to reestablish the level of the water in the
system.
At the end of the smoke circuit cleaning, to
the next restart check around the burner plate
and the smoke chamber for smoke leaks. In
the case some smoke leaks were noticed,
first of all tighten the nuts fitting the smoke
chamber and, not getting result, it will be
necessary to replace the sealing gasket.
Similarly it will be necessary to act on the
front door, increasing at first the tightening
of the nuts (after having loosened the inner
counternuts) and then, if necessary, by
replacing the whole gasket.
If it was necessary to center the sealing
gaskets on the sealing ring of the door it is
possible to adjust the door position by acting
as suggested on the paragraph 2.6.
At the end check and, if necessary, restore
the sealing of the connection of the chimney
and of the burner with the door.
The performed operations must be recorded
on the log book of C.H. system.

5.3 - EXTRAORDINARY

MAINTENANCE

Extraordinary maintenance of end season
or for long periods of inactivity.
It will be necessary to perform all the operations
described in the preceding chapter and
besides:
-

Check the state of consumption of the
turbulators to replace them in time.

-

To facilitate the extraction of the turbulators,
with the TRIOPREX-N boilers a special
extractor is supplied.

-

After the cleaning of the smoke circuit  it
is convenient to pass in the smoke pipes
and in the furnace with a rag soaked of

diluted solution of caustic soda.
After having let to dry cross again all the
surfaces with a rag soaked of oil.
Perfectly close the the burner air intake
to avoid a continuous passage of damp air
through the boiler recalled by the chimney
it self.
It is advisable to put inside the furnace
some alive mortar that has an hygroscopic
action.

-

Do not empty the C.H. system and the
boiler.

-

Protect the screws with graphitized fat,
nuts and pivots of the door.

-

Show all the operations that must be
perform to the following put into operation

particularly the operation of the shunt
pump must be checked.

Содержание TRIOPREX N Series

Страница 1: ...26743 11 08 rev 2 TRIOPREX N INSTALLATION USE AND SERVICING INSTRUCTION to be kept by the user ...

Страница 2: ...sibility of the installer to fulfil all the regulations concerning the boiler house the safety devices the chimney the fuel supply lines the electrical installations and all the other local requirements and safety instructions Approvals The UNICAL boilers TRIOPREX N range have been tested and CE certified for the gas operation by TECHNIGAS BELGIUM who has recognised to these boilers the conformity...

Страница 3: ...systems BS 5546 Installation of gas hot water supplies for domestic purposes 2nd Family Gases BS 6644 Ventilation for gas appliances of rated input exceeding 60 kW HEALTH SAFETY DOCUMENT No 635 The Electricity at Work Regulations 1989 The manufacturer s notes must NOT be taken in any way as overriding statutory obligations IMPORTANT These appliances are CE certificated for safety and performance I...

Страница 4: ... to the burner via a cooling line page 14 2 9 Casing assembly page 15 STANDARD PANEL BOARD page 24 3 1 Panel board type 21056 21057 functions description page 24 3 2 Electrical wiring diagram for single phase burner pump page 24 3 3 Introduction of the electronic panel board type 30688 page 25 3 4 Panel board type 30688 description of functions page 25 3 5 Electrical wiring diagram for single phas...

Страница 5: ...affected by the flame temperature the time during which the combustion gases stay in a high temperature zone oxygen partial pressure and its concentration The provisions to be adopted for the NOx reduction are then reduction of combustion temperature reduction of the specific thermal input permanence time reduction of the gases in the combustion chamber reduction of oxygen concentration UNICAL to ...

Страница 6: ... Weight with packaging kg 307 348 55 65 72 85 TX N 65 TX N 85 1 Panel board 2 Smoke chamber cleaning door 3 Flame sight glass T1 C H flow T2 C H return T3 Expansion vessel connection T4 Boiler drain T5 Flue connection T6 Max burner blast tube dia DIMENSIONS TRIOPREX N Type T6 Ø mm fig 2 A mm 740 740 B mm 690 950 C mm 950 950 D mm 190 190 E mm 140 140 F mm 145 145 G mm 660 660 H mm 345 345 I mm 120...

Страница 7: ...5 322 408 475 Water side pressure drop m w c 0 06 0 08 0 08 0 10 0 10 0 18 0 17 0 20 0 22 0 35 0 32 0 53 5 5 7 5 12 16 9 12 12 5 17 5 9 12 15 21 Smoke side pressure drop mm w c Maximum boiler working pressure bar 5 5 5 5 5 5 Weight with packaging kg 426 503 564 621 812 906 93 110 127 150 157 185 191 225 255 300 323 380 TX N 110 TX N 150 TX N 185 TX N 225 TX N 300 TX N 380 DIMENSIONS TRIOPREX N Typ...

Страница 8: ...31 425 500 535 630 620 730 TX N 500 TX N 630 TX N 730 DIMENSIONS TRIOPREX N Type TX N 500 TX N 630 TX N 730 Hydraulic resistance for delta T 15K fig 8 1 Panel board 2 Smoke chamber cleaning door 3 Flame sight glass T1 C H flow T2 C H return T3 Expansion vessel connection T4 Boiler drain T5 Flue connection T6 Max burner blast tube dia CONNECTIONS A mm 920 920 920 B mm 1605 1800 1995 C mm 1645 1645 ...

Страница 9: ...iler working pressure bar 5 Weight with packaging kg 1581 714 840 DIMENSIONS TRIOPREX N Type Hydraulic resistance for delta T 15K fig 10 1 Panel board 2 Smoke chamber cleaning door 3 Flame sight glass T1 C H flow T2 C H return T3 Expansion vessel connection T4 Boiler drain T5 Flue connection T6 Max burner blast tube dia CONNECTIONS A mm 1122 B mm 2115 C mm 1432 D mm 190 E mm 195 F mm 195 G mm 1025...

Страница 10: ...60 1600 1615 1900 DIMENSIONS TRIOPREX N Type Hydraulic resistance for delta T 15K fig 12 1 Panel board 2 Smoke chamber cleaning door 3 Flame sight glass T1 C H flow T2 C H return T3 Expansion vessel connection T4 Boiler drain T5 Flue connection T6 Max burner blast tube dia CONNECTIONS A mm 1462 1462 1622 1622 B mm 2282 2652 2692 3014 C mm 1542 1542 1702 1702 D mm 190 190 190 190 E mm 230 230 260 2...

Страница 11: ... or brick of dimensions Q x R see dimensions table which must be flat level and of a suitable load bearing capacity to support the weight of the boiler when filled with water and any ancillary equipment Once the installation has been made the boiler must result perfectly horizontal and well stable to avoid vibrations and noise x Not shorter than the boiler body xx Sufficient to allow accessibility...

Страница 12: ...ted to fit in the feeding line to the boiler a water meter for small capacities 2 5 2 C H FLOW AND RETURN CONNECTIONS The dimensions of flow and return connections are shown for each boiler model in the table DIMENSIONS Before connecting the boiler to the C H system this one has to be throughly cleaned Make sure in the system there is a sufficient number of air venter When connecting flow and retu...

Страница 13: ...moke pipes at a too high temperature can cause important damages to the boiler The burner manufacturing companies are able to supply the flame dimensions developped by their burners More informations are given in the paragraph Commissioning 2 7 3 BURNER INSTALLATION Before fitting the burner it is necessary to verify the position of the tubulators inside the TX N 500 730 220 230 smoke pipes each p...

Страница 14: ... equipped with a 1 8 threaded connection pos 1 on which a pressure test nipple 9 mm dia is fitted This can be used with a silicon pipe for the measurement of the counterpressure in the combustion chamber At the place of this pressure test nipple which must be held a special microbore pipe pos 2 will connect the flame sightglass directly to the pressure room downstream the fan of the burner The air...

Страница 15: ...y of the casing for TX N 65 85 should be carried out in the following steps Refer to diagram on fig 18 19 for details A Fit the insulation blanket 1 onto the boiler shell and secure it in to place using the elasticated straps 2 provided ensuring that the metal clips grip in to the external surface of the insulation B Locate the side panels 3 and 4 with the lower bend inside the bottom L profiles a...

Страница 16: ... 10 11 12 2 6 8 3 9 9 7 5 1 2 1 5 5 3 4 TRIOPREX N 65 85 fig 18 fig 19 TRIOPREX N 65 85 1 Thermometer bulb 2 Working thermostat bulb 3 Minimum thermostat bulb 4 Safety thermostat bulb 5 Bulb retaining clip ...

Страница 17: ...anges TX N and TS 3 P before removing the precut insulation follow the instructions supplied with the insulation it self E After removal of the two side screws from the panel board rotate its cover frontwards and insert the cables and the capillaries of thermometer and thermostats through the slots on its base Fit the panel board to front upper panel 10 Fit the upper front panel 10 complete with t...

Страница 18: ...s suitable for two different boiler ranges TX N and TS 3 P before removing the precut insulation follow the instructions supplied with the insulation it self H Fit the rear insulation pos 16 and fix the rear lower panel pos 26 I Position the panels 12 and 19 between the side upper panels pos 8 and 17 L After removal of the two side screws from the panel board rotate its cover frontwards and insert...

Страница 19: ...19 TRIOPREX N 500 730 fig 22 fig 23 TRIOPREX N 500 730 1 Thermometer bulb 2 Working thermostat bulb 3 Minimum thermostat bulb 4 Safety thermostat bulb 5 Bulb retaining clip ...

Страница 20: ... the upper panel 9 complete with the panel board to the side upper panels 3 5 Guide the burner plug through the side cable clamp plate 16 on the preferred side and clamp the cable using the cable clamp supplied Fix the side cable clamp plates 16 to the casing side panels 3 5 Fit the cables leaving the boiler from the back side with the plastic screws of the cable clamps 15 F Insert the thermometer...

Страница 21: ...lowing sequence Ref to fig 26 pos 1 thermometer pos 2 working thermostat pos 3 high limit thermostat pos 4 minimum temperature thermostat It is recommended to introduce the bulbs up to the bottom of the bulb holder to have a better response Introduce then the contact spring pos 6 to improve the contact and secure the capillaries in position by the clip pos 5 1 Thermometer bulb 2 Working thermostat...

Страница 22: ...et easy access to the bulb holders B Position the side panels 3a 3b and 4a 4b with the lower bend inside the bottom L profiles and hook them to the screws fitted to the upper profiles To determine which one of the front side panels is the left or the right ensure that the cable clamp plates 5 are positioned facing toward the front edge C Open the combustion chamber door and fit the front insulatio...

Страница 23: ... on figs 30 and 31 When fitting the panel board the leads of the burner cable which has to be passed through the cable gland must be connected to the panel board terminal strip see wiring diagrams on figs 30 32 The seven pole plug and the cable must come out from the casing through the cable clamp plate pos 1 onto which the cable gland must be fixed fig 28 2 1 3 Unical TRIOPREX ...

Страница 24: ...rical supply line to the boiler a switch with fuses is to be foreseen 3 STANDARD PANEL BOARD fig 29 3 2 ELECTRICAL WIRING DIAGRAM FOR SINGLE PHASE BURNER AND PUMP Te11st stage working thermostat 60 C 90 C Te22nd stage working thermostat 54 C 84 C Tm Minimum thermostat 50 C Ts High limit thermostat 100 C Pi C H pump A Burner lockout warning lamp eventual Ph Phase 230V 50Hz N Neutral F1 General fuse...

Страница 25: ... direct zone C H system without mixing valve the flow sensor has not to be fitted the outer compensator controls only the pump of the C H system No 1 one zone C H system with mixing valve the flow sensor has to be fitted downstream the mixing valve the outer compensator controls the pump of the C H system No 2 two zone C H system one direct and one with mixing valve the outer compensator controls ...

Страница 26: ...x 4 A 4 4 G V 6 6 7 7 8 8 9 9 10 10 2nd stage Tm Minimum thermostat Ts High limit thermostat 100 C Vm2 Mixing valve for 2nd zone A Burner lockout warning lamp eventual B Hourmeter eventual 3 5 ELECTRICAL WIRING DIAGRAM FOR SINGLE PHASE BURNER AND PUMPS Ipi2 2nd C H pump switch Ipb D H W tank pump switch Pb D H W tank loading pump Pi1 C H pump for direct zone Pi2 C H pump for mixed zone Te Working ...

Страница 27: ... 08 RELAY FUNC 1 00 30 C 90 C RELAY TEMP 1 30 C 2K 10K HYST RELAY 1 5K 00 03 RELAY FUNC 2 00 00 01 OFF ON SCREED 00 OFF See explanation SCREED PROGR RETURN Default IV Value range Designation HOT WATER 00 01 OFF ON CP LOCK 01 ON 00 01 02 03 PARALLEL 00 00 C 50 C HS T DHW 20 C 5K 30K HYST DHW 5K 00 min 30 min DHW FOLLOWUP 00 min 00 01 OFF ON THERM INPUT 00 OFF 00 01 OFF ON CHARGE THROUGH 00 OFF Exit...

Страница 28: ... 00 24 00 OUT TEMP DEL 1 0K 50K SLOPE OFFSET 5K 00 01 OFF ON B HEAT SINK 01 ON Exit level using RETURN Default IV Value range Designation HEATING CIRCUIT 1 00 04 HC FUNCTION 00 00 03 PUMP MODE 00 5 25 MIXER OPEN not for HW circuit 16 5 25 MIXER CLOSE not for HW circuit 12 20 C 110 C MAX FLOW T 80 C 10 C 110 C MIN FLOW T 10 C 15 C 5 C FROST PROT 0 C 0 00 24 00 OUT TEMP DEL 1 0K 50K SLOPE OFFSET 5K ...

Страница 29: ...sensor code no required after input there is a restart of the controller RETURN end of INSTALLATION Start INSTALLATION Set value Save value and next value Start INSTALLATION Set value Save value and next value Acc to version GERMAN GERMAN 20 20 CONTRAST 0 Sensor weekday DISPLAY SEL Exit level using RETURN Default IV Value range Designation HOT WATER 00 01 OFF ON 1X DHW 00 OFF 10 C 70 C DHW TEMP 1 ...

Страница 30: ...1 02 OPTIMIZAT 00 0 00 3 00 h M OPT TIME 2 00 h 0 00 3 00 h ECONO OPTI 0 00 h 0000 9999 PC ENABLE 0000 Default IV Value range Designation HEATING CIRCUIT 2 MODE 5 C 40 C T ROOM DES 1 20 C 5 C 40 C T ROOM DES 2 20 C Exit level using RETURN 5 C 40 C T ROOM DES 3 20 C 5 C 40 C ECONO TEMP 10 C 5 C 40 C REDUCED TEMP 15 C 5 C 40 C T LIMIT DAY 19 C 5 C 40 C T LIMIT N 10 C 0 00 3 00 HEAT SLOPE 0 8 00 01 O...

Страница 31: ... Mo Tu We TH Fr 06 00 to 22 00 Sa Su 07 00 to 23 00 Value range Designation HEAT CIRCUIT 2 HEAT PROGRAM 1 FACTORY SETTING Mo Tu We TH Fr 06 00 to 08 00 16 00 to 22 00 Sa Su 07 00 to 23 00 HEAT PROGRAM 2 FACTORY SETTING Mo Tu We TH Fr 05 00 to 21 00 Sa Su 06 00 to 22 00 Value range Designation HOT WATER FACTORY SETTING Mo Tu We TH Fr 05 00 to 21 00 Sa Su 06 00 to 22 00 Value range Designation CIRCU...

Страница 32: ...The hydraulic schemas shown in the figs 34 35 are principle schemas in case of different system circuits contact please our after sale service dept which will supply you with all the necessary informations 3 7 ELECTRICAL AND HYDRAULIC CONNECTIONS OF C H fig 34 In a C H installation equipped with a D H W storage tank the hydraulic schema shown in fig 35 can be used 3 8 ELECTRICAL AND HYDRAULIC CONN...

Страница 33: ...ain that the turbulators are in all the smoke pipes The commissioning of the burner must be performed under the responsibility of a specialized and well trained burner technician authorised by the burner manufacturer In that occasion a commissioning report has to be filled out 4 fig 36 TX N 65 TX N 85 TX N 110 TX N 150 TX N 185 TX N 225 TX N 300 TX N 380 TX N 500 TX N 630 TX N 730 TX N 840 TX N 11...

Страница 34: ... H pump it will start to rotate as soon as the minimum water temperature thermostat detects 50 C Switch the burner ON Position the working thermostats of 1st and 2nd stages to the maximum setting to create a heat request During this phase check that There are no smoke leaks from the front door the burner plate and the chimney connection There is a draught at the chimney base between 2 and 4 mm w g...

Страница 35: ...iler and of the plant manometers flow and pressure switches expansion vessels and all the safety devices In this occasion it will be necessary to notice the quantity of reinstatement water used and decide also in base to its hardness an intervention of preventive descaling It must be considered that the calcium and magnesium salts dissolved in the raw water with repeated reinstatements can cause d...

Страница 36: ...ration of the outer compensator if fitted These openings never have to be obstructed Maintain the boiler house clean and dust free The boiler house is not a closet avoid to store any kind of materials Maintain the entry of the boiler house free and easy to reach in any moment Ascertain that the boiler house is endowed with efficient emergency lamp Open the front door Shake and remove the turbulato...

Страница 37: ...37 Note ...

Страница 38: ...38 Note ...

Страница 39: ...39 Note ...

Страница 40: ...om Unical AG declines any liability for the inaccuriaces that may appear due to errors in trascription or printing It also reserves the right to introduce those modifications to its products that it considers necesssary or useful without compromising the essential characteristics of the said products AG S P A ...

Отзывы: