28
Default
IV
Value range
Designation
HEATING CIRCUIT 2
00 - 04
HC FUNCTION
00
00 , 03
PUMP MODE
00
5 - 25
MIXER OPEN
(not for HW circuit)
16
5 - 25
MIXER CLOSE
(not for HW circuit)
12
20 °C - 110 °C
MAX FLOW-T
45 °C
10 °C - 110 °C
MIN FLOW-T
10 °C
- - - -
(-15)°C - (5)°C
FROST PROT
0 °C
0:00 - 24:00
OUT-TEMP-DEL
1
0K - 50K
SLOPE OFFSET
5K
00 - 01 (OFF / ON)
B-HEAT SINK
01 = ON
Exit level using
RETURN
Default
IV
Value range
Designation
HEATING CIRCUIT 1
00 - 04
HC FUNCTION
00
00 , 03
PUMP MODE
00
5 - 25
MIXER OPEN
(not for HW circuit)
16
5 - 25
MIXER CLOSE
(not for HW circuit)
12
20 °C - 110 °C
MAX FLOW-T
80 °C
10 °C - 110 °C
MIN FLOW-T
10 °C
- - - -
(-15)°C - (5)°C
FROST PROT
0 °C
0:00 - 24:00
OUT-TEMP-DEL
1
0K - 50K
SLOPE OFFSET
5K
00 - 01 (OFF / ON)
B-HEAT SINK
01 = ON
Exit level using
RETURN