System manager operating instructions

17

35

33

Heating temperature control

Temperature is adjusted between a minimum of 0°C and 
a maximum of 90°C.

For the heating controller to work properly, the knob of 
the working thermostat MUST be at the MAX full-scale 
(to the “right”).
As far as the working temperature setting is concerned, 
see  the  paragraph  “PROGRAMMING THE  HEATING 
CONTROLLER”.

The value set will appear on the heating controller display. 

Resetting safety thermostat

IMPORTANT: The safety thermostat is located below 
the cap indicated in the figure to the side. To access it 
when the boiler blocks, unscrew the plastic cap with 
a screwdriver; after having reset the boiler, put the 
plastic cap back on. 

The safety thermostat can be triggered when the boiler 
overheats.
This can be solved first of all by lowering the working 
temperature of the boiler.

If the safety device of the boiler continues 
to trigger, do not try to restore operation of 
the boiler on your own. 
Contact an Authorised Assistance Centre. 

Содержание PANEL BOARD MODULATING MASTER

Страница 1: ...G CASCADE DUAL STAGE CASCADE C OK 1 2 1 2 1s C C C BUS ID 1 2 11 Mod Run 2 1 31 42 11 41 12 13 32 14 15 16 17 35 33 34 18 19 20 21 22 23 21 0 20 Servizio Data Ora Vacanze Visual Inf Utente Progr Tempo...

Страница 2: ...TREATMENT The hardness of the supplied water conditions the frequency at which the domestic hot water exchanger must be cleaned If the water has a hardness greater than 15 f we recommend using water s...

Страница 3: ...STEM MANAGER by installer maintenance technician 5 SAFETY WARNINGS Attention The appliance must be installed adjusted and maintained by professionally qualified personnel in compliance with standards...

Страница 4: ...is powered electrically green indicator light on and is set up for the production of hot water for heating Burner switch This switch connects and disconnects power to the burner With the switch at 0 t...

Страница 5: ...afety thermostat in the boiler will trigger when the maximum temperature is reached with the consequent need to be rearmed Mixed zone system pump switch This switch connects and disconnects power to t...

Страница 6: ...ear on the heating controller display Resetting safety thermostat IMPORTANT The safety thermostat is located below the cap indicated in the figure to the side To access it when the boiler blocks unscr...

Страница 7: ...green indicator light on and is set up for the production of hot water for heating Burner switch This switch connects and disconnects power to the burner of the boiler n 1 With the switch at 0 the bur...

Страница 8: ...owered electrically With the switch at II the system pump is powered electrically and is ready to run IMPORTANT the system pump must always be ready to run before switching the burner on to allow heat...

Страница 9: ...the heating controller display Resetting safety thermostat of boiler n 1 IMPORTANT The safety thermostat is located below the cap indicated in the figure to the side To access it when the boiler block...

Страница 10: ...the production of hot water for heating Burner switch This switch connects and disconnects power to the burner of the boiler n 2 With the switch at 0 the burner of the boiler n 2 is not powered elect...

Страница 11: ...mostat MUST be at the MAX full scale to the right As far as the working temperature setting is concerned see the paragraph PROGRAMMING THE HEATING CONTROLLER The value set will appear on the heating c...

Страница 12: ...ue save the value and activate next value open level change the value save the value Depending on implementation ITALIAN ITALIAN 20 20 CONTRAST 0 Sensor day CHOICE OF READING HS 01 HS 02 SELECTION PRO...

Страница 13: ...ON 00 0 00 3 00 h MINIMUM OPENING TIME 2 00 h 0 00 3 00 h REDUCTION OPTIMISATION 00 00 00 h 0000 9999 PC ENABLE 0000 Default Individual values Value range Description PROGRAMMING HEATING CIRCUIT 2 SER...

Страница 14: ...d Sunday from 07 00 to 23 00 Value range Description PROGRAMMING TIMER HEATING CIRCUIT 2 HEATING CIRCUIT 1 PROGRAM DEFAULT SETTINGS Monday Tuesday Wednesday Thursday Friday from 06 00 to 08 00 from 16...

Страница 15: ...I the boiler is powered electrically green indicator light on and is set up for the production of hot water for heating Burner switch This switch connects and disconnects power to the burner With the...

Страница 16: ...afety thermostat in the boiler will trigger when the maximum temperature is reached with the consequent need to be rearmed Mixed zone system pump switch This switch connects and disconnects power to t...

Страница 17: ...pear on the heating controller display Resetting safety thermostat IMPORTANT The safety thermostat is located below the cap indicated in the figure to the side To access it when the boiler blocks unsc...

Страница 18: ...green indicator light on and is set up for the production of hot water for heating Burner switch This switch connects and disconnects power to the burner of the boiler n 1 With the switch at 0 the bur...

Страница 19: ...owered electrically With the switch at II the system pump is powered electrically and is ready to run IMPORTANT the system pump must always be ready to run before switching the burner on to allow heat...

Страница 20: ...the heating controller display Resetting safety thermostat of boiler n 1 IMPORTANT The safety thermostat is located below the cap indicated in the figure to the side To access it when the boiler bloc...

Страница 21: ...the production of hot water for heating Burner switch This switch connects and disconnects power to the burner of the boiler n 2 With the switch at 0 the burner of the boiler n 2 is not powered elect...

Страница 22: ...mostat MUST be at the MAX full scale to the right As far as the working temperature setting is concerned see the paragraph PROGRAMMING THE HEATING CONTROLLER The value set will appear on the heating c...

Страница 23: ...ue save the value and activate next value open level change the value save the value Depending on implementation ITALIAN ITALIAN 20 20 CONTRAST 0 Sensor day CHOICE OF READING HS 01 HS 02 SELECTION PRO...

Страница 24: ...ON 00 0 00 3 00 h MINIMUM OPENING TIME 2 00 h 0 00 3 00 h REDUCTION OPTIMISATION 00 00 00 h 0000 9999 PC ENABLE 0000 Default Individual values Value range Description PROGRAMMING HEATING CIRCUIT 2 SER...

Страница 25: ...d Sunday from 07 00 to 23 00 Value range Description PROGRAMMING TIMER HEATING CIRCUIT 2 HEATING CIRCUIT 1 PROGRAM DEFAULT SETTINGS Monday Tuesday Wednesday Thursday Friday from 06 00 to 08 00 from 16...

Страница 26: ...erify water pressure in the boiler When the pressure drops below 1 bar it should be restored with the boiler cold until it reaches the static pressure relative to the highest point of the system by gr...

Страница 27: ...Remarks...

Страница 28: ...rrors It also reserves the right to modify its products as deemed necessary or useful without jeopardising their essential features 46033 casteldario mantova italia tel 39 0376 57001 fax 39 0376 66055...

Отзывы: