Maximum number of daily time bands
The heating programme provides for 6 daily time bands for temperature levels, numbered from 1 to 6. If
necessary, the time bands can be reduced to a minimum of two.
1. Keep the button pressed for 3 seconds.
2. The display shows the CU parameter..
3. Press the button 4 times.
4. The display shows parameter P3.
Use the buttons to modify the number of daily time bands from 2 to 6.
5. Press any other button to exit the menu.
Heating minimum temperature
Follow the instructions given below to set the minimum heating circuit water temperature in 1°C steps.
1. Keep the button pressed for 3 seconds.
2. The display shows the CU parameter.
3. Press the button 5 times.
4. The display shows parameter P4.
Use the buttons to adjust the parameter in 1°C increments. By keeping the button pressed the
value will change rapidly.
5. Press any other button to exit the menu.
System filling
This function manages the operation mode of the electric device for filling the water circuit in a certain
model boiler
1. Keep the button pressed for 3 seconds.
2. The display shows the CU parameter.
3. Press the button 6 times.
4. The display shows parameter P5.
Set to 0 using the buttons to deactivate the electric filling device. Set to 1 using the buttons
to activate Automatic system filling
5. Press any other button to exit the menù.
Important:
Set the boiler control card to manual filling. In manual mode, if the sensor installed in the boiler detected
insufficent pressure, the bar icon will flash on the display: press the Reset button to activate the special
solenoid valve. During manual or automatic. Once the nominal pressure is restored, the remote control will
return to the normal display.
Temperature Unit of measure selection
Follow the instructions given below to use the Remote Control in °C or in °F.
1. Keep the button pressed for 3 seconds.
2. The display shows the CU parameter.
3. Press the button 7 times.
4. The display shows parameter P6.
Set to 0 using the buttons to select °C. Set to 1 using the buttons
to select °F
5. Press any other button to exit the menu
Room temperature reading corerction
Follow the instructions given below to correct the room temperature reading between -2°C and +2°C in
0.1°C steps.
1. Keep the button pressed for 3 seconds.
2. The display shows the CU parameter.
3. Press the button 8 times.
4. The display shows parameter P7
Set to 0 using the buttons to adjust the parameter in 0.1°C increments.
5. Press any other button to exit the menu