Maximum number of daily time bands 

The heating programme provides for 6 daily time bands for temperature levels, numbered from 1 to 6. If 

necessary, the time bands can be reduced to a minimum of two.

1.  Keep the button      pressed for 3 seconds.

2.  The display shows the CU parameter..

3.  Press the button     4 times. 

4.  The display shows parameter P3.

  Use the buttons        to modify the number of daily time bands from 2 to 6.

5.  Press any other button to exit the menu.

Heating minimum temperature 

Follow the instructions given below to set the minimum heating circuit water temperature in 1°C steps.

1.  Keep the button    pressed for 3 seconds.

2.  The display shows the CU parameter.

3.  Press the button     5 times.

4.  The display shows parameter P4.

  Use the buttons          to adjust the parameter in 1°C increments. By keeping the button pressed the 

value will change rapidly.

5.  Press any other button to exit the menu.

System filling

This function manages the operation mode of the electric device for filling the water circuit in a certain 

model boiler

1.  Keep the button    pressed for 3 seconds.

2.  The display shows the CU parameter.

3.  Press the button     6 times.

4.  The display shows parameter P5.

  Set to 0  using the buttons          to deactivate the electric filling device. Set to 1 using the buttons     

  to activate Automatic system filling

5.  Press any other button to exit the menù. 

Important:

Set the boiler control card to manual filling. In manual mode, if the sensor installed in the boiler detected 

insufficent pressure, the bar icon will flash on the display: press the Reset button to activate the special 

solenoid valve. During manual or automatic. Once the nominal pressure is restored, the remote control will 

return to the normal display.

Temperature Unit of measure selection

Follow the instructions given below to use the Remote Control in °C or in °F.

1.  Keep the button     pressed for 3 seconds.

2.  The display shows the CU parameter.

3.  Press the button    7 times.

4.  The display shows parameter P6.

  Set to 0 using the buttons to select °C. Set to 1 using the buttons 

 to select °F

5. Press any other button to exit the menu

Room temperature reading corerction 

Follow the instructions given below to correct the room temperature reading between -2°C and +2°C in 

0.1°C steps.

1.  Keep the button     pressed for 3 seconds.

2.  The display shows the CU parameter.

3.  Press the button    8 times.

4.  The display shows parameter P7

  Set to 0 using the buttons            to adjust the parameter in 0.1°C increments.

5.  Press any other button to exit the menu

Содержание EASYr

Страница 1: ...E N G L I S H REMOTE CONTROL ROOM THERMOSTAT Wireless INSTALLATION SERVICING AND USER MANUAL...

Страница 2: ...e instructions contained in the manuals supplied with the boiler Index 1 Genera features 3 2 Package Contents 3 3 Description buttons and symbols 3 4 Application 5 5 Installation 6 6 Easy User Guide 7...

Страница 3: ...ogramming 0 Deactivated P2 Pre Heating Function 0 Deactivated P3 Max number of daily time bands 6 P4 Heating min temperature P5 Filling the system 0 Deactivated P6 Temperature unit of measure selectio...

Страница 4: ...Manual room temperature increase button BRIDGE 1 TEST mode button 2 LED behind the button DISPLAY KEY 11 Heating programme time bands 12 Day of week 13 Holiday function button copy heating DHW program...

Страница 5: ...5 E N G L I S H Connect the Bridge to the TA1 OT ter minals of the boiler after removing the jumper from TA2 4 Application Bridge can be hidden inside the boiler...

Страница 6: ...RF Bridge by prising with a screwdriver at A e B Then fix the back of the bridge to the wall with the set of screws supplied running the two wires inside the rectangular hole at the bottom near the t...

Страница 7: ...ediately the search of synchrony This is showed by the symbol flashing for max 2 minu tes and when it stops the synchrony has occurred lf there is no communlcation and the error E94 appears the system...

Страница 8: ...Control will function according to the automatic weekly programme displaying the 6 time bands the time band active at that moment is di splayed in a box If the box is not shown this means that the cur...

Страница 9: ...utes increments By keeping the button presses the hours will change rapidly 3 Press the button The room temperature inside the house starts flashing use the buttons to change the temperature level in...

Страница 10: ...utton associated with a different operation mode Telephone contact input GSM Normal Remote Control operation is ensured as long as the telephone contact remains open The closing of this contact indica...

Страница 11: ...button pressed for 3 seconds 2 The display shows the CU parameter Press the buttons to modify the compen sation curve by increments of 1 unit By keeping the button pressed the value will change rapidl...

Страница 12: ...same day so that the room temperature set by the user is reached at the start of the programmed time band The Remote Control calculates an initial hypothetical Pre activation time if the programmed r...

Страница 13: ...The display shows parameter P5 Set to 0 using the buttons to deactivate the electric filling device Set to 1 using the buttons to activate Automatic system filling 5 Press any other button to exit the...

Страница 14: ...display activates fault E94 and the symbol once the power is restored it is necessary to wait 15 minutes After which the symbol becames fixed and RF communication is avaible again Diagnostic The remo...

Страница 15: ...15 E N G L I S H...

Страница 16: ...erves the right to bring those changes that it will hold necessary to it own products or profits without jeopardizing its essential characteristics 46033 casteldario mantova italia tel 39 0376 57001 f...

Отзывы: