User parameter Editing

Sliding Temperature - Compensation Curve

By installing the external probe (optional), the control system can work with a Sliding Temperature. The 

external probe must be connected to the boiler card: refer to the relevant handbook for details. In this mode, 

the heating system temperature is adjusted according to the outside weather conditions in order to ensure 

high comfort and energy saving throughout the year. In particular, as the external temperature increases 

the system delivery temperature decreases according to a specific compensation 

curve. With the Sliding 

Temperature adjustment the temperature set through the “Heating temperature adjustment” setting beco-

mes the maximum system delivery temperature. It is advisable to set a maximum value to allow system 

adjustment throughout its useful operating range.

The compensation curve can be set from 1 to 10 

according to the following graph.

1.  Keep the button    pressed for 3 seconds

2.  The display shows the CU parameter. 

  Press the buttons             to modify the compen- 

  sation curve by increments of 1 unit. By 

  keeping the button pressed the value will 

  change rapidly.

3.  Press any other button to exit the menu

Set the compensation curve to 0 to disable Sliding 

Temperature adjustment.

Sliding Temperature - Paralell Curve Offset

Once the Compensation curve has been set, parallel curve offset can be adjusted from 20 to 40 as shown 

in the following graphs:

The system must be adjusted at the time of installation by qualified personnel. Possible adjustments can in 

any case be made by the user to improve comfort. If the room temperature is lower than the required value, 

it is advisable to set a higher order curve and vice versa. Proceed by increasing or decreasing in steps of 

one and check the result in the room

1.  Keep the button     for 3 seconds.

2.  The display shows the CU parameter.

3.  Press the button     . 

4.  The display shows the OF parameter.

  Press the buttons            to modify parallel 

  curve offset in 1°C increments. By keeping 

  the button pressed the value will change rapidly

5.  Press any other button to exit the menu.

Содержание EASYr

Страница 1: ...E N G L I S H REMOTE CONTROL ROOM THERMOSTAT Wireless INSTALLATION SERVICING AND USER MANUAL...

Страница 2: ...e instructions contained in the manuals supplied with the boiler Index 1 Genera features 3 2 Package Contents 3 3 Description buttons and symbols 3 4 Application 5 5 Installation 6 6 Easy User Guide 7...

Страница 3: ...ogramming 0 Deactivated P2 Pre Heating Function 0 Deactivated P3 Max number of daily time bands 6 P4 Heating min temperature P5 Filling the system 0 Deactivated P6 Temperature unit of measure selectio...

Страница 4: ...Manual room temperature increase button BRIDGE 1 TEST mode button 2 LED behind the button DISPLAY KEY 11 Heating programme time bands 12 Day of week 13 Holiday function button copy heating DHW program...

Страница 5: ...5 E N G L I S H Connect the Bridge to the TA1 OT ter minals of the boiler after removing the jumper from TA2 4 Application Bridge can be hidden inside the boiler...

Страница 6: ...RF Bridge by prising with a screwdriver at A e B Then fix the back of the bridge to the wall with the set of screws supplied running the two wires inside the rectangular hole at the bottom near the t...

Страница 7: ...ediately the search of synchrony This is showed by the symbol flashing for max 2 minu tes and when it stops the synchrony has occurred lf there is no communlcation and the error E94 appears the system...

Страница 8: ...Control will function according to the automatic weekly programme displaying the 6 time bands the time band active at that moment is di splayed in a box If the box is not shown this means that the cur...

Страница 9: ...utes increments By keeping the button presses the hours will change rapidly 3 Press the button The room temperature inside the house starts flashing use the buttons to change the temperature level in...

Страница 10: ...utton associated with a different operation mode Telephone contact input GSM Normal Remote Control operation is ensured as long as the telephone contact remains open The closing of this contact indica...

Страница 11: ...button pressed for 3 seconds 2 The display shows the CU parameter Press the buttons to modify the compen sation curve by increments of 1 unit By keeping the button pressed the value will change rapidl...

Страница 12: ...same day so that the room temperature set by the user is reached at the start of the programmed time band The Remote Control calculates an initial hypothetical Pre activation time if the programmed r...

Страница 13: ...The display shows parameter P5 Set to 0 using the buttons to deactivate the electric filling device Set to 1 using the buttons to activate Automatic system filling 5 Press any other button to exit the...

Страница 14: ...display activates fault E94 and the symbol once the power is restored it is necessary to wait 15 minutes After which the symbol becames fixed and RF communication is avaible again Diagnostic The remo...

Страница 15: ...15 E N G L I S H...

Страница 16: ...erves the right to bring those changes that it will hold necessary to it own products or profits without jeopardizing its essential characteristics 46033 casteldario mantova italia tel 39 0376 57001 f...

Отзывы: