background image

21

Installation instructions 

System filling and cold start-up

Once completed and verified the hydraulic system in all its 
parts, electrically connected to the electric panel all tools, mo-
tor, probes, etc. and verified that the boiler room components 
have been properly set-up, proceed with filling the system.

The system must be filled in a way that completely eliminates 
the air inside it.

The filling pump must connect the storage tank with the gen-
erator drain, which is normally the lowest point of the system. 

Once the oil is drained in the storage tank, activate the loading 
pump by means of which oil enters the system.
During loading the vent valves inserted in the various parts of 
the circuit, as well as all system shut-off valves, must be open.
This system is certainly the most rational since, when intro-
ducing oil in the lowest point, it facilitates the expulsion of the 
circuit air.

Filling can also be performed from the expansion vessel.
This, however, is not recommended because it can favour the 
formation of air pockets.
However, if wanting to use this system, it is necessary to be 
cautious and introduce the oil very slowly to allow the air to flow 
up through the liquid mass.

Whereas, top-ups are made through the vessel during the ad-
vanced drying of the oil.

The diathermic fluid is fed until it starts coming out from the 
various vents which will be immediately closed, so that the ex-
pansion vessel is filled for about 1/4 of its capacity.

Then the circulation pump is activated for a couple of minutes 
and switched off for another couple of minutes.

After filling the system, start the circulation pump for at least 
two hours without turning on the burner.

During this time, open the vents every so often and, if reserve 
pump present, alternate the operation of the circulation pumps, 
restoring the expansion vessel level.

This eliminates the remaining air pockets and removes the 
coarse dirt inside the circuit, which stop in the filter.

Do this until the air is completely bled.

After switching off, disassemble the filters and clean the bas-
kets.

During filling, continuously and thoroughly 
monitor the system to check for leaks in or-
der to avoid unnecessary waste and imme-
diately take steps without, as far as possi-
ble, having to empty the system.

When circulation has stabilised, the complete system filling is 
assured.

Hot start

After replacing the filter basket, hot start the system.

Start the circulation pump and then the burner with low flame. 
Heating must be gradual, not more than 50 K/h.

When the oil reaches 100°C, maintain the temperature con-
stant between 110 and 120°C until circulation is stabilised: at 
this temperature the water in the circuit evaporates. Occasion-
ally open the vents to evacuate the air and vapour bubbles.

Once the circulation has stabilised, gradually increase the tem-
perature (50 K/h) up to operating temperature.

Maintain the operating temperature for a few hours and thor-
oughly check the system (flange sealing, expansions, sup-
ports): make a note of all field values (pressures, temperatures, 
instrument calibrations).

In particular, check the pressure difference between generator 
oil inlet and outlet, comparing it with the technical specifica-
tions, to verify that the detected value and the differential pres-
sure switch calibration are correct.
The burner technician must calibrate the burner at the maxi-

mum output allowed by the generator (detectable from the rat-
ing plate), optimising the combustion parameters.

ALL PARAMETERS DETECTED UPON COMMISSIONING 
ARE ESSENTIAL FOR ASSESSING THE FUTURE OPERA-
TION OF THE SYSTEM.

Check the tightness of the gaskets of the door, 
burner plate, cleaning doors, generator/chimney 
fitting and hot-tighten to eliminate any smoke 
leakages.

After these operations, turn off the burner while running the 
circulation pump until the oil drops below 150°C.

Wait for the oil to cool (< 50°C) and check the cleanliness of 
the filter.

Содержание DIATHER Series

Страница 1: ...INSTRUCTIONS ON INSTALLATION USE AND MAINTENANCE D ATHER...

Страница 2: ...n C Pressione di prova Serpentino bar Data di prova idrostatica Max Design Coil Pressure Max Allowable Temperature Min Allowable Temperature Hydraulic Test Pressure Coil Hydraulic Test Date Superficie...

Страница 3: ...3 3 Supply conditions 12 3 4 Handling 12 3 5 Positioning in boiler room 13 3 6 Hydraulic system features and connections 14 3 7 Fuel supply 15 3 8 Connection to the flue 15 3 9 Burner assembly 16 3 1...

Страница 4: ...ertaking any maintenance carefully read the instructions and proce dures contained in this manual they provide important information regarding the safety of the system and the safety of persons ATTENT...

Страница 5: ...as can cause fatal intoxica tion Switch off the system Ventilate the place of installation Interventions on the system Close the fuel shut off valve and make sure that it cannot be opened accidentally...

Страница 6: ...0 C with a thermal gradient of 40 C between oil inlet and outlet NOTE The D ATHER boilers are CE marked accord ing to Directive 2014 68 UE category I Weld ing procedures and devices are approved and c...

Страница 7: ...ate carefully follow its manufacturer s instructions provided with the generator documentation Following the intervention restore the pressure switch at a pres sure of 0 3 bar higher than the calibrat...

Страница 8: ...nection pipe to the expansion vessel must be free of shut offs must be such to prevent convective motions of the oil must not be insulated DIATHERMIC OIL COLLECTION TANK It is a simple container with...

Страница 9: ...0 260 700 1260 2480 1520 800 1270 1060 780 728 416 65 20 300 280 930 1370 3170 1620 900 1500 1160 840 808 436 80 20 350 280 1160 1540 3350 1790 1000 1780 1320 920 940 450 100 25 350 280 1500 1670 3630...

Страница 10: ...0 14 8 19 2 21 2 22 4 31 8 44 2 54 6 59 0 72 8 102 2 104 4 156 4 189 6 Coil Volume Volume Serpentino l 40 84 130 232 245 201 285 518 639 692 853 1592 1629 2464 2970 Max Coil Design Pressure Pressione...

Страница 11: ...ding to good practice rules 3 2 INSTALLATION STANDARDS It must be installed by a professionally qualified technician who shall assume the responsibility of respecting all local and or national laws pu...

Страница 12: ...mage during transport or handling For their assembly refer to the instructions supplied with the documentation provided with the generator itself 3 4 HANDLING The D ATHER generators are equipped with...

Страница 13: ...the front of the generator verify that with the door open at 90 the distance between the door and the adja cent wall is at least equal to the length of the burner b On the two sides of the generator 0...

Страница 14: ...this means that from the room temperature 20 C to a work temperature of 270 C ten metres of pipes stretch by 30 mm If not compensated the expansions cause tremendous efforts on the system components T...

Страница 15: ...ns normally the need for them to work in conditions of depression and this requires an adequate sizing The need for depression on the chimney is justified by safety reasons to avoid smoke filtrations...

Страница 16: ...rnace otherwise com bustion anomalies may occur with the risk of seriously damaging the generator If the burner is provided with air intake connect it with a rubber hose to the intake on the flame ind...

Страница 17: ...3 11 ELECTRICAL CONNECTIONS General warnings Have the electrical system checked by per sonnel professionally qualified according to law attesting the adequacy of the electrical system to the power loa...

Страница 18: ...PLAN RESET RESET ALLARME LIVELLO MIN OLIO ALARM MIN LEVEL OIL RESET RESET ALLARME CIRCOLAZIONE OLIO ALARM OIL CIRCULATION RESET ALLARME TEMPERATURA OLIO ALARM TEMPERATURE OIL RESET TACITAZIONE SIRENA...

Страница 19: ...K 10 BUZZER 11 EMERGENCY 13 CIRCULATION PUMP 1 ON 14 CIRCULATION PUMP 1 START OFF STOP START The pump starts running and gives consent to the burner OFF The pump stops running when the oil s temperatu...

Страница 20: ...n line compliant with the applicable standards in force Are the ventilation conditions and minimum distances to perform any maintenance guaranteed Are the refractory coverings intact is the furnace fr...

Страница 21: ...es the remaining air pockets and removes the coarse dirt inside the circuit which stop in the filter Do this until the air is completely bled After switching off disassemble the filters and clean the...

Страница 22: ...rculation pump must remain in motion until the oil temperature drops below 150 C ATTENTION After calibrating the burner check that the flame does not touch the bottom of the coil otherwise the cement...

Страница 23: ...RATURE TEMPERATURA RITORNO OLIO OIL RETURN TEMPERATURE RESET ALLARME SICUREZZE IMPIANTO ALARM SAFETY PLAN RESET RESET ALLARME LIVELLO MIN OLIO ALARM MIN LEVEL OIL RESET RESET ALLARME CIRCOLAZIONE OLIO...

Страница 24: ...fter a period of inactivity it is necessary to repeat the previously described start up procedures Immediately remove any unburned gas leaks by replacing the worn seal gaskets It is forbidden because...

Страница 25: ...ness of the fuel supply system this check is very important especially when using gaseous fuels After having performed maintenance and cleaning operations repeat the preliminary checks to switch on ch...

Страница 26: ...clogging of the chimney and cleanliness of the burner air path dust check sealing of the fuel supply system if gas check sealing of the flue gas circuit door burner plate cleaning door generator chimn...

Страница 27: ...in Oil overflowing from expansion vessel Remedy check that the electrical consumption of the motor in particular that the power absorbed by the pump is correct check the joint alignment check the init...

Страница 28: ...more it reserves the right to modify its products as deemed necessary or useful without affecting their essential features 46033 casteldario mantova Italy tel 39 0376 57001 telefax 39 0376 660556 info...

Отзывы: