45
Residual risks from Risks Analysis pursuant to the European Directive 97/23/EC - PED
EVENT CAUSE 21 GASKETS Severity Event: D
No tightness of the gaskets on water and steam sids
EFFECT - CONSEQUENCE
- Leakage of water or steam from the flanged junctions and from manholes present
RISK - DANGER
Risk of burns due to the steam
Risk of flooding of the boiler room
Risk of electrical short circuit of powered parts
SOLUTION - PREVENTION
- It is necessary to check at start-up and periodically the tightness of all the gaskets
- It is necessary to use a material that is suitable in terms of temperature, pressure, fluid
- Carefully keep to that indicated in the use and maintenance manual
EVENT CAUSE 22
ATMOSPHERIC CONDITIONS
Severity Event: C
Keeping the generator in unsuitable weather conditions during transport and / or in the boiler room. These conditions refer to the
minimum temperature and to the effects produced by rainwater
EFFECT - CONSEQUENCE
If the temperature is lower than that indicated in the project, they can cause fragile breakages in welds.
Rainwater may damage or corrode the generator structure from the outside
RISK - DANGER
Burst of the generator
SOLUTION - PREVENTION
- Protect the generator from adverse weather conditions
- Keep to that indicated in the use and maintenance manual
- Check that the temperature to which the boiler may be subjected, in the expected life cycle, is in compliance with the minimum
allowable of the project
EVENT
CAUSE
23 INSTALLATION
Severity
Event:
C
Incorrect installation: Hydraulic structures Electrical works Chimney
EFFECT - CONSEQUENCE
- Hydraulic: steam escaping
- Electric: electrical dispersion / failed operation of the safety devices of the generator
- Chimney: combustion products dispersed in the boiler room
RISK - DANGER
- Hydraulic: general burns
- Electric: electrocution / explosion of the generator
- Poisoning due to toxic combustion fumes (carbon monoxide) in boiler room
SOLUTION - PREVENTION
- Check the correct connection of the hydraulic connections
- Check the correct connection of the electrical parts
- Correctly fix the chimney
- Check the correct functioning of the generator
- Keep to that indicated in the use and maintenance manual
Содержание BAHR'UNO
Страница 1: ...BAHR UNO INSTRUCTIONS ON INSTALLATION USE AND MAINTENANCE ...