52
NT UF 811 CO GB (c) / March 2014
Fault:
Depending on the polarity chosen (NO: normally open, NC: normally closed), the relay state
changes when the associated fault occurs.
In the example, the variable selected is "general Q". This means
that the relay closes when the flow meter is not measuring a flow
and remains open otherwise.
Direction:
Depending on the polarity chosen (NO: normally open, NC: normally closed), the relay
state changes when the sign ( or -) of the associated dimension changes.
Threshold:
Depending on the polarity chosen (NO: normally open, NC: normally closed) and the
direction in which the threshold is crossed, the relay takes one state if the value is greater than the
indicated threshold. The relay switches to the opposite state if the value concerned is lower than the
threshold.
Comment:
In order to restrict the relay backlash when the dimension concerned fluctuates around
the threshold, hysteresis must be defined.
The diagram below illustrates this principle with hysteresis at 2% and the threshold crossed in the
ascending direction:
Frequency:
The frequency at which the relay is opened and closed depends on a value to be
defined. Example: high flow, high frequency, low flow, low frequency.
The following must be defined:
o
the parameter that the output represents.
Select the dimension that you wish to associate with the
analogue output using the chapter headers (function) and
the chapter items (value).
o
the value corresponding to 0 Hz.
o
the value corresponding to 1 kHz.
o
the value in the event of a fault.
On
On
Off
Содержание Uf 811 CO
Страница 4: ...4 NT UF 811 CO GB c March 2014 CHAPTER 1 OVERVIEW...
Страница 11: ...11 NT UF 811 CO GB c March 2014 CHAPTER 2 SAFETY INSTRUCTIONS...
Страница 14: ...14 NT UF 811 CO GB c March 2014 CHAPTER 3 INSTALLATION AND WIRING...
Страница 28: ...28 NT UF 811 CO GB c March 2014 CHAPTER 4 IMPLEMENTING A MEASURING POINT...
Страница 32: ...32 NT UF 811 CO GB c March 2014 CHAPTER 5 USING AND CONFIGURING THE Uf 811...
Страница 65: ...65 NT UF 811 CO GB c March 2014 CHAPTER 6 FUNCTION ENGINE...
Страница 67: ...67 NT UF 811 CO GB c March 2014 CHAPTER 7 PC SOFTWARE...
Страница 83: ...83 NT UF 811 CO GB c March 2014 Appendix I Characteristic echo signals...
Страница 86: ...86 NT UF 811 CO GB c March 2014 Appendix II Speed of sound in water...