DIGITAL  DIFFERENTIAL  PRESSURE  TRANSMITTER

Copyright

2003.08  ULFA  TECHNOLOGY  CO.,LTD                                    http://www.ulfatech.com

5

User  setting  mode

Zero  setting

Entering  User  setting  mode  :

  Press

MODE  key  for  more  than  3seconds  till  appear  "I  n  t" 

on  LED into the  user setting mode. Press the

MODE  key  once  in  user  setting  mode  to  change

setting  item.  The  setting  item  circulate  "  I  n  t  " 

"  PoFS  " 

"  P  4  " 

"  P20  " 

"  Id  " 

"  FACt

"

"  I  n  t  "    while  mode  key  press  repeated.

Each  item  setting  methode  is  refer  to  next  pages.

Save

  :

  If  you  complete  your  setting  in  the  each 

mode,  Press  ENTER  once  to  save  and  exit  to

measure  mode. 

Press  ENTER  for  more  than  3  seconds  to  save  and 

exist  in  the  setting  mode.

Release  User  setting  mode  :

Press  ENTER  once  to  save  and  exit  to  measure

mode.

If  you  are  not  operate  this  instrument  for  about  1 

minute,  It's  released  user  setting  mode  automatically

and  return  to  measuring  mode.

Optimize  zero  to  display  and  current  out  automatically
by  front  key  pressed.

CAUTION  :  Release  pressure  port  free  before

              zero  set

Press  MODE  for  more 

than  3  seconds  till 

appear "Int" on LED

display
Press  MODE  key  once 

till  appear  "PoFS"  on 

LED display.
Press  ENTER  once  to 

set  zero  and  exit  to 

measure  mode.  "PoFS" 

blink  for  about  5  seconds 

to  calculate  zero.
Press  ENTER  key  for 

more  than  5  seconds  till 

appear "SAvE" on LED

display  to  save  and  exist 

in  the  setting  mode.

Sampling  time  setting

It  can  be  set  0.1~5.0  seconds  by  0.1  sec  resolution. 

PLT reading pressure 0.1sec interval for a setting

time  and  calculate  average  pressure  to  display  and 

4-20mA  output.

(ex)  setting  time  :  2  sec

PLT reading  pressure 20  times for 2  seconds

    and  calculate  average  of  measured  20  data  to

    display    and  4-20mA  current  output.

This  functions  is  useful  to  measure  hunted  pressure

Press  MODE  key  for 

more  than  3  seconds  till 

appear  "Int" on  LED

display  like  left.

Release  MODE  key  then 

appear  current  set  time 

on  LED display (default

set  time  is  0.5  sec)

Set  your  sampling  time 

use  up/down  key
Press  ENTER  once  to 

save  and  exit  to  measure 

mode. 
Press  ENTER  key  for 

more  than  3  seconds  till 

appear  "SAvE"  on  display 

to  save  and  exist  in  the 

sampling  time  setting

mode

4mA  current  setting

This  function  is  set  pressure  level  to  4mA  current  out. 

Generally  pressure  zero  is  setting  to  4mA  current  out.

By  the  way,  negative  pressure  is  setting  in  another

case. PLT can  be set any pressure  level to  4mA

current  out  between  low  and  high  pressure  range.

Low  and  high  pressure  ranges  are  setting  in  factory.   

Press  MODE  key  for 

more  than  3  seconds  till 

appear "Int" on LED

display.

Press  MODE  key  once 

till appear "P4" on   LED

display.

Set  your  pressure  level 

to  4mA  out  use  up/down 

key 

Press  ENTER  once  to 

save  and  exit  to  measure 

mode. 

Press  ENTER  key  for 

more  than  3  seconds  till 

appear "SAvE" on LED

display  to  save  and  exist 

in  the  setting  mode

PEAK

 

P

PEAK

 

P

PEAK

 

P

PEAK

 

P

PEAK

 

P

PEAK

 

P

PEAK

 

P

PEAK

 

P

PEAK

 

P

PEAK

 

P

PEAK

 

P

PEAK

 

P

PEAK

 

P

PEAK

 

P

PEAK

 

P

Содержание JANITOR PLT Series

Страница 1: ...RANSMITTER Copyright 2003 08 ULFA TECHNOLOGY CO LTD http www ulfatech com 1 Instruction Manual Digital Differential Pressure Transmitter 1 General Specification 2 Installation 3 Wiring 4 Function 5 Setting Calibration 4 Digit Display 4 20mA Output ...

Страница 2: ... Connections 2 screw terminal block Display 4 Digit LED Warm up Time 15 minutes TRANSMITTER Connections 2 Screw terminal block Output Signal 4 20mADC limited at 30mADC Loop Resistance 0 1100 Zero Span Adj One touch Adjustable on Panel PERFORMANCE AT 23 Range Table Zero Output 4 mA Model No Range Resolution Full Span Output 20 mA Accuracy 0 25 FSO Includes Linearity Hysteresis Repeatability B15M 15...

Страница 3: ...g kit is provided with all PLT Series Pressure Transmitter 1 Select your site location mark the appropriate panel cutout and complete the necessary panel cut 2 Carefully insert the Pressure Transmitter through the hole from front of the panel 3 Carefully insert the mount ring through the body of PLT from back side 4 Insert the snap ring to the snap ring groove 5 Tightening four mount screw through...

Страница 4: ...on number for communication Over pressure warning PLT displays warning on LED for over pressure positive and negative Upper 4 elements of segment blink for warning when measurement pressure over 10 for high pressure factory setting value And under 4 elements of segment _ _ _ _ blink for warning when measurement pressure under 10 for low pressure factory setting value Factory setting recovery The p...

Страница 5: ...pling time setting It can be set 0 1 5 0 seconds by 0 1 sec resolution PLT reading pressure 0 1sec interval for a setting time and calculate average pressure to display and 4 20mA output ex setting time 2 sec PLT reading pressure 20 times for 2 seconds and calculate average of measured 20 data to display and 4 20mA current output This functions is useful to measure hunted pressure Press MODE key f...

Страница 6: ...e and exist in the setting mode Press MODE key for more than 3 seconds till appear Int on LED display Press MODE key once till appear FACt on LED display Press ENTER once to recall and exit to measure mode Press ENTER key for more than 3 seconds till appear SAvE on LED to recall and exist in the setting mode ID No setting ID number is use for address for communication to master It s concern to PLT...

Отзывы: