PLT / PLX  Series

DIGITAL  DIFFERENTIAL  PRESSURE  TRANSMITTER

Copyright

2003.08  ULFA  TECHNOLOGY  CO.,LTD                                    http://www.ulfatech.com

4

Function

Setting  and  Calibration

Zero  setting  :

  Optimize  display  and  current  out  to

zero  automatically  by  front  key  pressed.

Peak  pressure  Measurement  :

  This  mode  is

display  for  peak  pressure  by  supplied  pressure.    And 
the  display  is  cleared  by  press  enter  key  in  the  peak
mode. 

Offset( p)  pressure  Measurement  :

  This

mode  is  display  the  changed  pressure  based  on  the
current  pressure.  Current  pressure  is  turned  into  "0" 
when  offset  mode  selected.  This  mode  does  not
concern  to  4-20mA  current  out  put.

Sampling  time  setting  :

  Sample  rate  is  0.1sec

of  this  product.  Sampling  time  is  measuring  time  by
sample  rate.  For  example,  if  setting  time  is  2  sec, 
PLT measures 20 times for 2 seconds and out to
display  and  4-20mA  out  put  by  average  of  20  times
measured  value.

Transmitter :

PLT  has 4-20mA current out put.

Span  (20mA)  range  can  be  changed  within  original 
range.

Communication(option)  :

            Measurement

pressure  can  be  sent  by  RS232  or  RS485  for  option 
specification.

ID  setting  :

  This  mode  set  identification  number

for  communication. 

Over  pressure warning  :

PLT displays warning

on LED for over pressure (positive  and negative).
Upper 4 elements of segment("

") blink for

warning  when  measurement  pressure  over  10%  for
high  pressure(factory  setting  value),  And  under  4
elements  of  segment("_  _  _  _")  blink  for  warning 
when  measurement  pressure  under  10%  for  low
pressure(factory  setting  value), 

Factory  setting  recovery  :

  The  parameters  are

changed  all  to  factory  setting  value  and  all  user
setting  value  is  cleared.

Hear  by  describe  key  function  and  setting  methode.

Please  read  this  section  carefully  for  the  correct  and 

optimum  use  of  this  product.

Key  functions

UP

-  Increase  setting  value

-  Offset  mode  set/reset

DOWN -  Decrease  setting  value

-  Peak  pressure  mode  set/reset

MODE -  Entering  into  the  setting  mode

-  Setting  item  circulation

ENTER

-  Save  setting  value

-  Clear  peak  value  in  the  peak  mode

-  Release  setting  mode

Peak  mode

Press  the  PEAK(down)

key  once  to  set  peak 

mode 

"PEA"  displayed  like  left 

while  press  peak  key

Press  the  ENTER  to 

reset  peak  value  and 

newly  start

Press  the  PEAK(down)

key  once  more  to  release 

peak  mode 

Offset  mode

Press  the 

P(UP)  key

once  to  set  offset  mode 

"dELt"  displayed  like  left 

while  press  P  key

Press  the 

P(UP)  key

once  more  to  release 

offset  mode 

 

P

PEAK

 

P

PEAK

 

P

PEAK

 

P

PEAK

PEAK

 

P

PEAK

 

P

PEAK

 

P

PEAK

 

P

Содержание JANITOR PLT Series

Страница 1: ...RANSMITTER Copyright 2003 08 ULFA TECHNOLOGY CO LTD http www ulfatech com 1 Instruction Manual Digital Differential Pressure Transmitter 1 General Specification 2 Installation 3 Wiring 4 Function 5 Setting Calibration 4 Digit Display 4 20mA Output ...

Страница 2: ... Connections 2 screw terminal block Display 4 Digit LED Warm up Time 15 minutes TRANSMITTER Connections 2 Screw terminal block Output Signal 4 20mADC limited at 30mADC Loop Resistance 0 1100 Zero Span Adj One touch Adjustable on Panel PERFORMANCE AT 23 Range Table Zero Output 4 mA Model No Range Resolution Full Span Output 20 mA Accuracy 0 25 FSO Includes Linearity Hysteresis Repeatability B15M 15...

Страница 3: ...g kit is provided with all PLT Series Pressure Transmitter 1 Select your site location mark the appropriate panel cutout and complete the necessary panel cut 2 Carefully insert the Pressure Transmitter through the hole from front of the panel 3 Carefully insert the mount ring through the body of PLT from back side 4 Insert the snap ring to the snap ring groove 5 Tightening four mount screw through...

Страница 4: ...on number for communication Over pressure warning PLT displays warning on LED for over pressure positive and negative Upper 4 elements of segment blink for warning when measurement pressure over 10 for high pressure factory setting value And under 4 elements of segment _ _ _ _ blink for warning when measurement pressure under 10 for low pressure factory setting value Factory setting recovery The p...

Страница 5: ...pling time setting It can be set 0 1 5 0 seconds by 0 1 sec resolution PLT reading pressure 0 1sec interval for a setting time and calculate average pressure to display and 4 20mA output ex setting time 2 sec PLT reading pressure 20 times for 2 seconds and calculate average of measured 20 data to display and 4 20mA current output This functions is useful to measure hunted pressure Press MODE key f...

Страница 6: ...e and exist in the setting mode Press MODE key for more than 3 seconds till appear Int on LED display Press MODE key once till appear FACt on LED display Press ENTER once to recall and exit to measure mode Press ENTER key for more than 3 seconds till appear SAvE on LED to recall and exist in the setting mode ID No setting ID number is use for address for communication to master It s concern to PLT...

Отзывы: