17
(11)Do not put any article made of the metal conductive material together with the battery or assemble it into
the battery box.
(12)Install it according to the selected installation mode:
Installation of standard cabinet (rack): Install the matching hanger for the battery pack and fix them
in the standard cabinet and the tray protection is added for the battery box.
Installation of wall-mounted box: Prior to installation, please ensure that the wall complies with the
wall-mounted requirements; according to the location in the design plan, install the special wall-mounted
box of the lithium battery; the battery pack is fixed in the wall-mounted box in a hanger manner.
Installation of integrated indoor and outdoor cabinets (boxes): Install them according to the
installation specification for the customized integrated cabinet (box).
4-7. Operation Instruction for Installation
1) Prior to installation, please check whether the battery is normal.
Press the reset key RST on the front panel for 3S for startup. During startup, 4 capacity indicator
lights on the front panel, ALM alarm indicator light (red) and RUN running indicator light light up. Check
whether all indicator lights light up normally; then the ALM alarm indicator light goes out, the RUN
running indicator light lights up and the capacity indicator light lights up according to the capacity.
If the ALM alarm indicator light flashes after startup, it means that the battery has an alarm. The
newly installed battery seldom has alarm. The common alarm is the battery undervoltage alarm (which is
resulted from non-use of the battery for a long time). Such case may be removed after the battery is
charged for 30min; if the alarm may not be removed, please press the reset key RST for 10S, until all
LEDs light up for reset, execute the battery reset operation and confirm whether the alarm is removed. If
the alarm is removed, the battery may be used normally. Otherwise the battery shall be reworked.
2) For the battery which is normal after detection, please press the reset key RST for3S
to execute the battery ON/OFF operation.
Instructions of
manual
operation of
the reset key
RST
Startup
In the OFF state of BMS, press the key for 3S for
startup;
Shutdown
In the non-standby state of BMS, press the key for
3S for shutdown;
Reset
In the non-standby state of BMS, press the key for
10S, until all LEDs light up for reset.