10. PERFORM STARTUP ChECkS AND ADjUSTMENTS
FAILURE TO PERFORM THESE
CHECKS of the boiler's combustion and
safety systems may result in serious property
damage, injury, or death.
IF YOU SMELL GAS, STOP and repair
the leak. Lighting the boiler when gas is
leaking may cause explosion or fire.
Follow the checklist below:
1.
Verify that the venting, water piping, gas
piping, and electrical systems are properly
installed and checked.
2.
Apply power to the boiler.
3.
Adjust zone thermostat to maximum setting.
4.
Allow gas line to purge of air.
q
Boiler lights cleanly within 60 seconds.
5.
Adjust gas input rate. See
Appendix F –
Adjusting Gas Input Rate.
Check main
burner and pilot flames. See Figures 10-a
and 10-c.
10-a
q
Pilot and main burner flames appear
clean and blue.
6.
Disconnect pilot lead wires from gas valve
(Figure 10-b).
q
Boiler shuts off.
7.
Reconnect pilot lead wires to gas valve.
q
Boiler restarts.
8.
Adjust zone thermostat to minimum setting.
q
Boiler shuts off.
9.
Adjust zone thermostat to maximum setting.
10.
Observe temperature gage as boiler heats.
11.
Adjust the high limit setting to its minimum
level (see "Programming High Limit" in
Section 8).
q
Boiler shuts off when temperature gage
reads within 15°F of high limit setting.
10-c
Содержание ENHANCED 2 Series
Страница 21: ...21 Annual Maintenance Checklist continued Operating Instructions VR8204 and VR8304 Gas Valves AM 2 ...
Страница 34: ...34 Internal Wiring Figure IW 1 Wiring Diagram ...
Страница 35: ...35 Internal Wiring continued Figure IW 2 Wiring Schematic ...
Страница 57: ...57 ...
Страница 58: ...58 ...
Страница 59: ...59 ...
Страница 60: ...60 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...