107750-01 - 9/17
VII. Venting
C. Design Requirements Unique to Vertical Venting Systems (continued)
Table 7.14: Equivalent Length of Flex Pipe
Equivalent Length (ft)
Flex Vent (1 ft):
3" DuraVent PolyPro Flex
2.0 ft
3" Centrotherm InnoFlue Flex
2.3 ft
3" Selkirk Polyflue
2.3 ft
3" DuraVent FasNSeal Flex
1.0 ft
4" DuraVent Poly Pro Flex
2.0 ft
4" Centrotherm InnoFlue Flex
2.3 ft
4" Selkirk Polyflue
2.3 ft
B-Vent Air Chase (1ft):
3" Flex Vent in 6" (or larger) B-Vent
1.0 ft
4" Flex Vent in 6" (or larger) B-Vent
1.0 ft
Note: Up to four 45 degree bends may be made in flex pipe or air chase.
These bends are not counted when figuring equivalent length.
Содержание ASPEN ASPN-320
Страница 11: ...11 107750 01 9 17 IV Locating the Boiler continued Figure 4 1 Minimum Clearances To Combustible Construction ...
Страница 13: ...13 107750 01 9 17 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued ...
Страница 88: ...88 107750 01 9 17 Figure 10 4 Proper Installation of Header Sensor X Wiring continued ...
Страница 89: ...89 107750 01 9 17 Figure 10 5 Internal Wiring Ladder Diagram X Wiring continued ...
Страница 90: ...90 107750 01 9 17 X Wiring continued CONDENSATE FLOAT SWITCH ...
Страница 91: ...91 107750 01 9 17 X Wiring continued Figure 10 6 Internal Wiring Connections Diagram ...
Страница 100: ...100 107750 01 9 17 Operating Instructions XI Start Up and Checkout continued ...
Страница 145: ...145 107750 01 9 17 XV Service Parts continued ...
Страница 147: ...147 107750 01 9 17 XV Service Parts continued All Models ...
Страница 149: ...149 107750 01 9 17 XV Service Parts continued All Models ...
Страница 151: ...151 107750 01 9 17 XV Service Parts continued All models ...
Страница 157: ...157 107750 01 9 17 ...
Страница 158: ...158 107750 01 9 17 ...
Страница 159: ...159 107750 01 9 17 ...
Страница 160: ...160 107750 01 9 17 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...