77
107362-01 - 8/17
IX. System Piping
(continued)
Table 9.5a: Recommended T
aco Circulators for 60 Equivalent ft. Boiler Loop Piping
Boiler Model
Minimum Pipe Size
(in.)
∆T
= 35°F
∆T
= 30°F
∆T
= 25°F
∆T
= 20°F
Flow
(GPM)
Boiler &
Piping Head
Loss
(ft)
Circulator
Model
Flow
(GPM)
Boiler &
Piping Head
Loss
(ft)
Circulator
Model
Flow
(GPM)
Boiler &
Piping Head
Loss
(ft)
Circulator
Model
Flow
(GPM)
Boiler &
Piping
Head Loss
(ft)
Circulator
Model
ASPN-85
1
4.5
1.5
007/007e
5.3
1.9
007/007e
6.3
2.6
007/007e
7.9
3.9
007
ASPN-1
10
1
5.8
2.3
007/007e
6.8
3.0
007/007e
8.2
4.2
007/007e
10.2
6.3
007
ASPN-155
1
8.2
4.2
007/007e
9.6
5.6
007/007e
11.5
7.8
0010
14.4
11.9
001
1
ASPNC-155
1
8.2
6.4
007/007e
9.6
8.7
0010
11.5
12.4
001
1
14.4
19.3
0013
ASPN-205
1¼
10.9
2.0
007/007e
12.7
2.7
007/007e
15.3
3.7
0010
19.1
5.6
001
1
ASPN-270
1¼
14.3
3.5
0010
16.7
4.6
0010
20.1
6.4
001
1
25.1
9.7
0013
Table 9.5b: Recommended Grundfos Circulators for 60 Equivalent ft. Boiler Loop Piping
Boiler Model
Minimum
Pipe Size
(in.)
∆T
= 35°F
∆T
= 30°F
∆T
= 25°F
∆T
= 20°F
Flow
(GPM)
Boiler &
Piping
Head Loss
(ft)
Circulator
Model
Flow
(GPM)
Boiler &
Piping
Head Loss
(ft)
Circulator
Model
Flow
(GPM)
Boiler &
Piping
Head Loss
(ft)
Circulator
Model
Flow
(GPM)
Boiler &
Piping
Head Loss
(ft)
Circulator
Model
ASPN-85
1
4.5
1.5
UPS 15-58,
Spd. 1
5.3
1.9
UPS 15-58,
Spd. 1
6.3
2.6
UPS 15-58,
Spd. 1
7.9
3.9
UPS 15-58,
Spd. 2
ASPN-1
10
1
5.8
2.3
UPS 15-58,
Spd. 1
6.8
3.0
UPS 15-58,
Spd. 1
8.2
4.2
UPS 15-58,
Spd. 2
10.2
6.3
UPS 15-58,
Spd. 3
ASPN-155
1
8.2
4.2
UPS 15-58,
Spd. 2
9.6
5.6
UPS 15-58,
Spd. 2
11.5
7.8
UPS 15-58,
Spd. 3
14.4
11.9
UPS 26-99,
Spd. 2
ASPNC-155
1
8.2
6.4
UPS 15-58,
Spd. 2
9.6
8.7
UPS 15-58,
Spd. 3
11.5
12.4
UPS 26-99,
Spd. 2
14.4
19.3
UPS 26-99,
Spd. 3
ASPN-205
1¼
10.9
2.0
UPS 15-58,
Spd. 2
12.7
2.7
UPS 15-58,
Spd. 2
15.3
3.7
UPS 26-99,
Spd. 1
19.1
5.6
UPS 26-99,
Spd. 2
ASPN-270
1¼
14.3
3.5
UPS 26-99,
Spd. 1
16.7
4.6
UPS 26-99,
Spd. 2
20.1
6.4
UPS 26-99,
Spd. 2
25.1
9.7
UPS 26-99,
Spd. 3
Содержание ASPEN ASPN-085
Страница 13: ...13 107362 01 8 17 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued...
Страница 94: ...94 107362 01 8 17 Figure 10 5 Internal Wiring Ladder Diagram X Wiring continued...
Страница 95: ...95 107362 01 8 17 PAGE LEFT INTENTIONALLY BLANK...
Страница 96: ...96 107362 01 8 17 X Wiring continued CONDENSATE FLOAT SWITCH...
Страница 97: ...97 107362 01 8 17 X Wiring continued Figure 10 6 Internal Wiring Connections Diagram...
Страница 106: ...106 107362 01 8 17 Operating Instructions XI Start Up and Checkout continued...
Страница 156: ...156 107362 01 8 17 XV Service Parts continued 3J 3I 3E 3B 3A 3C 3F 3H 3G 3D 3A 3C 3D 3K 3E All Models...
Страница 158: ...158 107362 01 8 17 4F 4F 4F 4F 4G 4G 4B 4A 4C 4E 4D 4B 4B 4B XV Service Parts continued All Models...
Страница 160: ...160 107362 01 8 17 XV Service Parts continued All models 5G 5F 5B 5A 5D 5E 5C 5D...
Страница 179: ...179 107362 01 8 17...
Страница 180: ...180 107362 01 8 17 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net...