background image

P o w e r S e r i e s   N e o   I n s t a l l a t i o n   G u i d e

3

Alarm Controller Current Calculation 

Maximum (Standby or Alarm) 

**See “Corbus Current Calculation Chart” below.

NOTE: 

For UL, ULC and Commercial Listed applications, the total standby and alarm cur-

rent cannot exceed 700mA. 

*These units draw current from the Corbus to power devices external to the module. This 

current must be added to the total Corbus current. See manufacturer's specifications for 

the current draw of each device.

Capacitance Limits

An increase in capacitance on the Corbus causes the system to slow down. The following 

chart indicates the total wire distance allowed for the capacitance rating of the wire used:

Table 1-3 Wire Capacitance

Zone Wiring

Power down the alarm controller and complete all zone wiring. Zones can be wired to 

supervise normally open devices (e.g., smoke detectors) or normally closed devices (e.g., 

door contacts). The alarm controller can also be programmed for SEOL or DEOL. 
Zone programming is done using the following programming sections: 

[001] selects zone definition

[013] Opt [1] for normally closed or EOL; Opt [2] for SEOL or DEOL

Observe the following guidelines when wiring zones:

For UL listed installations use SEOL or DEOL only

Minimum 22 AWG wire, maximum 18 AWG

Do not use shielded wire 

Do not exceed 100

 wire resistance. Refer to the chart below:

Table 1-4 Burglary Zone Wiring Chart

Aux Power Wiring

These terminals provide 

11.3-12.5VDC/700mA

 of current (shared with PGM outputs). 

Connect the positive side of any device to the AUX+ terminal, the negative side to GND. 

The AUX output is protected; if too much current is drawn from these terminals (wiring 

short) the output is temporarily shut off until the problem is corrected. 

NOTE: 

If using a 12V, 14Ah battery, maximum AUX capacity for 24-hour standby is 470mA.

PGM Wiring

PGMs switch to ground when activated from the alarm controller. Connect the positive 

side of the device to the AUX+ terminal and the negative side to a PGM terminal. 
PGM 1, 3, 4 supply up to 50mA; PGM 2 supplies up to 300mA.
A relay is required for current levels greater than 50mA or 300mA. PGM2 can also be 

used for 2-wire smoke detectors.

NOTE: 

Use SEOL resistors on Fire zones only.

Diagram 1-2: LED output with resistor and optional relay driver output.

UL Compatibility ID For FSA-210B Series is: FS200

NOTE: 

For ULC listed installations, use FSA-210A and FSA-410A series.

Single End-of-Line (SEOL) Resistor

When SEOL resistors are installed at the end of a zone loop, the alarm panel detects if the 

circuit is secure, open, or shorted. 

Diagram 1-3: SEOL Wiring

The SEOL resistor must be 

installed at the end of the loop for 

proper supervision.
To enable SEOL supervision, pro-

gram section [013], options [1] and 

[2] to OFF.

Double End of Line (DEOL) Resistors

When double end-of-line (DEOL) resistors are installed at the end of a zone loop, the sec-

ond resistor enables the panel to determine if the zone is in alarm, tampered or faulted. 

Diagram 1-4: DEOL Wiring 

To enable DEOL supervision, program section 

[013], option [1] to OFF and option [2] to ON.

Bell Wiring

These terminals supply 700mA of current at 10.4 - 12.5VDC for commercial/ residential 

installations. To comply with NFPA 72 Temporal Three Pattern requirements, section 

[013] Opt [8] must be ON.   Note that steady and pulsed alarms are also supported.

Diagram 1-5: Bell Wiring

The Bell output is supervised and power limited by 2A 

PTC. If unused, connect a 1000

 resistor across Bell+ and 

Bell- to prevent the panel from displaying a trouble.

Telephone Line Wiring

Wire the telephone connection terminals (TIP, Ring, T-1, R-1) to an RJ-31x connector as 

indicated in diagram 1.6. For connection of multiple devices to the telephone line, wire in 

the sequence indicated. Use 26 AWG wire minimum for wiring.

Diagram 1-6:Telephone Line 

Wiring

Telephone format is programmed 

in option [350]. 
Telephone call directions are 

programmed in options [311]-

[318].

AUX (700mA max. including 
PGM1/2/3/4)

Corbus (700mA max.)**

(Alt. Com: 125mA)

Total (must not exceed 700mA)

Table 1-2Corbus Current Calculation Chart

Item

Current (mA)

x

Quantity

Total (mA)

HS2LCD

105

x

HS2ICN

105

x

HS2LED

105

x

HS2LCDP

105

x

HS2ICNP

105

x

HS2LCDRF

50

x

HS2ICNRF

50

x

HS2ICNRFP

50

x

Current required for connected devices =

HSM2108*

30

x

HSM2208*

40

x

HSM2300/2204*

35

x

HSM2HOSTx

35

x

3G2080(R)/
TL2803G(R)/TL280(R)

125 (PCLINK)

Total Corbus Current =

Wire Capacitance per 1000’ (300m)

Total Corbus Wire Length

15nF

5300’/1616m

20nF

4000’/1220m

25nF

3200’/976m

30nF

2666’/810m

35nF

2280’/693m

10nF

2000’/608m

Wire Gauge

Maximum Length to EOL Resistor (ft/meters)

22

3000 / 914

20

4900 / 1493

19

6200 / 1889

18

7800 / 2377

Figures are based on maximum wiring resistance of 100



Ground Wiring

Connecting AC Power
(UL Listed Installations)

Diagram 1-7:Ground Installation

NOTE: 

Using an insulated green wire (minimum 

22AWG), connect the EGND terminal on the Corbus 

and the grounding wire from the building electrical 

installation to any of the available holes on the back or 

side of the metal cabinet. See the diagram attached to 

the cabinet for suggested GND point location and hard-

ware recommendations.

NOTE: 

Wire and installation hardware not included.

Primary: 120VAC/60Hz./0.33A
Secondary: 16.5VAC/40VA DSC 

PTD1640U, DSC PTC1640U Class 

2 transformer. 

NOTE: 

Use DSC PTD1640 for Cana-

dian installations.

For ULC S559 applications, Stan-

dex transformer (Model FTC3716) 

shall be employed for direct-wiring.

NOTE: 

For UL/ULC installations 

use only 60Hz

Batteries

A sealed, rechargeable, lead acid or 

gel type battery is required to meet 

UL requirements for power standby 

times. Refer to  Aux Loading and 

Battery Selection on page 15.

T-1

R-1
TIP

RING

RJ-31X

RED

GRN

BRN

GRA

Tighten nut to break paint and make 

good connection to the cabinet

firealarmresources.com

Содержание DSC PowerSeries neo

Страница 1: ...t Test the panel completely to ensure that all features and functions operate as programmed 901 Walk Test 904 000 Wireless Placement Test Modules Wireless keypads HS2LCDWFxUL HS2LCDWFPxUL HS2LCDWFPVxU...

Страница 2: ...lephone connection e Do not route any wiring over circuit boards f The installer must ensure that a readily accessible disconnect device is incorporated into the building for permanently connected ins...

Страница 3: ...sistors When double end of line DEOL resistors are installed at the end of a zone loop the sec ond resistor enables the panel to determine if the zone is in alarm tampered or faulted Diagram 1 4 DEOL...

Страница 4: ...quired Programming Once basic installation of the alarm panel is complete the following general configuration options can be set 000 Language Selection LCD keypads only Use this section to set the lan...

Страница 5: ...ication 9 Normally Closed EOL 10 Single EOL 11 Double EOL 12 Fast Normal Loop Response Trouble Detailed Trouble 01 Service Required 01 Bell circuit 02 RF jam detected 03 Aux supply trouble 04 Time and...

Страница 6: ...on PGM2 being used as a 2 wire smoke detector input This trouble is generated by a short on hardwired zones when DEOL is used Ensure a 2 2K EOL resistor is connected red red red Remove wire leads from...

Страница 7: ...led in the same enclosure and configured as primary or back up with AES 128 bit encryption Compliant with EN50136 1 1 EN50136 2 1 ATS2 requirements Trouble 10 Module Tamper Press 10 to determine speci...

Страница 8: ...03 Maintenance Code AAAA00 PGM Programming 007 PGM Programming 000 Main Bell Partition Assignment 1 Partition 1 2 Partition 2 3 Partition 3 4 Partition 4 5 Partition 5 6 Partition 6 7 Partition 7 8 Pa...

Страница 9: ...Thursday Friday Saturday 003 Auto Disarming Holiday Schedule Holiday 1 Holiday 2 Holiday 3 Holiday 4 004 Auto Arming Pre Alert 004 005 Auto Arming Postpone Timer 000 006 No Activity Arming Timer 000...

Страница 10: ...g 4 Pulse Dial After 5th Attempt 5 Parallel Communications 6 Alternate Dial 7 Reduced Dialing Attempts 8 Activity Delinquency 381 Communicator Option 2 1 Keypad Ringback 2 Bell Ringback 4 Closing Conf...

Страница 11: ...may not remove any proprietary notices marks or labels from the Software Product You shall institute reasonable measures to ensure compliance with the terms and conditions of this EULA b Separation of...

Страница 12: ...80 017 081 018 082 019 083 020 084 021 085 022 086 023 087 024 088 025 089 026 090 027 091 028 092 029 093 030 094 031 095 032 096 033 097 034 098 035 099 036 100 037 101 038 102 039 103 040 104 041 1...

Страница 13: ...Wireless Device Record Installer Defined Access Codes System Account Code Module Type Slot Serial Number Module Type Slot Serial Number Device Type Zone Serial Number Device Type Zone Serial Number 0...

Страница 14: ...Fire Installations section 001 fire zone shall be programmed as type 025 The entry delay shall not exceed 45 seconds refer to section 005 The exit delay shall not exceed 60 seconds refer to section 00...

Страница 15: ...s of time Also an intruder may cut the telephone line or defeat its operation by more sophisticated means which may be difficult to detect Insufficient Time There may be circumstances when the system...

Страница 16: ...entry and exit delays and bell time out for the system Note Combined entry delay and communications delay abort window shall not exceed 60s Range 30 sec to 4 min Default 30 sec Required programmable A...

Отзывы: