SIA False Alarm Reduction Installations: Quick Reference

Minimum required system consists of one Control unit model HS2128 or HS2064 or HS2032 or HS2016 and any one of the compatible listed keypads: HS2LCDRF9, HS2LCDRFP9, HS2ICNRF9, HS2ICNRFP9, HS2LCD, HS2LCDP, HS2ICN, 
HS2ICNP, HS2LED. 

The following wireless keys can also be used in SIA compatible installations: PG9929, PG9939,PG9949.

NOTE: 

For models PG9929 and PG9939, the panic/emergency key shall be disabled for SIA compliant installations.

For a list of the default values programmed when the unit is shipped from the factory, and for any other programming information, refer to the table below.

The following optional subassembly modules also bear the SIA CP-01-2010 classification and may be used if desired: HSM2108 zone expander, HSM2208 PGM output module, HSM2300 auxiliary power supply, HSM2204 output module, 

HSM2HOST9 2-way wireless transceiver, PG9901 indoor siren, PG9911 outdoor siren, and 3G2080(R)/ TL2803G(R)/ TL280(R) cellular and PSDN communication module.

Caution

For SIA FAR installations use only modules/devices that are listed on this page.

Fire Alarm Verification feature (Auto Verified Fire Zone type [025]) is not supported on 2-wire smoke detectors zones, model FSA-210B(T)(S)(ST)(LST)(R)(RT)(RD)(RST)(LRST). This feature may be enabled for 4-wire 

smoke detectors only (FSA-410B(T)(S)(ST)(LST)(R)(RT)(RST)(LRST) and wireless detectors PG9916/PG9926). The fire alarm delay is 60s.

Call Waiting Cancel (Section [382], Option 4) feature on a non-Call Waiting line will prevent successful communication to the supervising station.

All smoke detectors on the system must be tested annually by conducting the Installer Walk Test. Prior to exiting walk test mode, a sensor reset must be done on the system, [*][7][2], to reset all latching 4-wire smoke 

detectors. Refer to the installation instructions supplied with the detector for details.

Notes

Programming at installation may be subordinate to other UL requirements for the intended application.

Cross zones have the ability to individually protect the intended area (e.g. motion detectors which overlap).

Cross zoning is not recommended for line security Installations nor is it to be implemented on exit/entry zones.

This control panel has a communication delay of 30 seconds. It can be removed or increased up to 45 seconds by the end user in consultation with the installer.

The security system shall be installed with the sounding device activated and the communicator enabled for transmission using SIA or CID format.

ULC commercial burglary installations require DEOL resistors.

SIA Feature Programming Section

Comments

Range/Default

Requirement

Exit Time
[005]>[001], option 3

Access to Entry and Exit delays and Bell Time Out for the system.

Range

:

45- 255 seconds

Default:

 60 sec.

Required
(programmable)

Progress Annunciation/Disable - for Silent 
Exit
[014], option 6 ON

Enables audible exit beeps from the keypad for the duration of exit delay.

Individual keypads may be disabled

Default:

 Enabled

Allowed

Exit Delay Restart
[018], option 7

Opening a Delay zone door after it has already been opened and closed during an exit 
delay restarts the exit delay timer.

Default:

 Enabled

Required

Auto Stay Arm on Un-vacated Premises
[001]>[001]-[128] Zone type 05, 06,09

Function key: Forces the system to arm in Stay mode if the occupant does not exit the 
premises after pressing the Away function key.

If no exit after full arm

Default: 

Enabled

Required

Exit Time and Progress Annunciation/Disable 
or Remote Arming
[861]>[001]-[005], option 4

System times and audible exit beeps can be disabled when using the wireless key to 
stay arm the system. When away arming, audible exit beeps can not be disabled.

Default: 

Enabled

Allowed

Entry delay(s)
[005]>[001]-[008], options 1 and 2

Access to entry and exit delays and bell time out for the system

Note:

 Combined entry delay and communications delay (abort window) shall not 

exceed 60s.

Range: 

30 sec. to 4 min.

Default:

 30 sec.

Required 
(programmable)

Abort Window for Non-Fire zones
[002]>[001]-[128], option 7 ON

Access to zone attributes, i.e., swinger shutdown, transmission delay and cross zone. 
May be disabled by zone or zone type.

Default: 

Enabled

Required

Abort Window Time - for Non-Fire zones
[377]>[002], option 1

Access to the programmable delay before communicating alarms

Note:

 Combined entry delay and communications delay (abort window) shall not 

exceed 60 seconds.

Range:

 00 - 45 sec.

Default:

 30 sees

Required 
(programmable)

Abort Annunciation

An audible tone is generated when an alarm is aborted during the abort window.

Hard-coded ON

Required

Duress Feature
[*][5]> master code> user 2-95> 5> 2

When this feature is enabled, selected user codes send a duress reporting code to the 
central station when used to perform any function on the system. Section [019], option 
[6] must be enabled.

Default: 

N

Required

Cancel Window
[377]>[002], option 6

Access to the communications cancel window. Minimum duration must be 5 minutes.

Range:

 005-255

Default:

 005 

Cancel Annunciation
[308]>[001], option 8

Access to the reporting code for Alarm Canceled.

A Cancel was transmitted

Default: 

Enabled

Required

Cross Zoning
[042]>Selection 3, option 002 

Enables cross zoning for entire system. Zones can be enabled for cross zoning via zone 
attribute option 8 in sections [002][101] - [128].

Programming required

Default: 

Disabled

Required

Burglary Verification Timer
[005]>[000], option 3

Access to the programmable Cross Zone timer.

Range:

 000-255 sec.

Default: 

60 seconds

Allowed

Swinger Shutdown for Alarms
[377]>[001], option 1

Access to the swinger shutdown limit for zone alarms
For all non-fire zones, shut down at 1 to 6 trips.

Default: 

2 trips

Required
(programmable)

Swinger Shutdown Enable
[002]>[001] - [128], option 6 ON

Access to swinger shutdown, transmission delay and cross zone attributes. Zone attri-
bute option 6 (Swinger Shutdown enabled) is ON.

Non-police response zones

Default: 

Enabled

Allowed

24-Hr. Auto-verified Fire 
[001]>[001]-[128], Zone type 025 ON

Access to 24-Hr. Auto-verified Fire
Activates if Not restored within the specified time.

Must choose zone type for applica-
tion

Required

Call Waiting Cancel 
[382], option 4 OFF

Access to the dialing sequence used to disable call waiting. Call waiting string can be 
programmed in [034]

Depends on user phone line

Default: 

Disabled

Required

System Test:
[*][6] Master Code, option 4 

The system activates all keypad sounders, bells or sirens for 2 seconds and all keypad 
lights turn on. Refer to user manual

 (part no. 29008365).

Walk Test Mode:
[*][8][Installer code][901]

This mode is used to test each zone on the system for proper functionality.

Walk Test Communications 
[382], option 2

Enables communication of zone alarms while walk test is active.

Default:

 Disabled

Walk Test Start/ End Reporting Codes
[308][401], options 1 and 2

Access to the reporting codes for walk test start and end times.

© 2014 Tyco International Ltd. and its Respective Companies. All Rights Reserved.

The trademarks, logos, and service marks displayed on this document are registered in the United States [or other countries].  Any misuse of the trademarks is strictly prohibited and Tyco International Ltd. will aggressively enforce its intellec-

tual property rights to the fullest extent of the law, including pursuit of criminal prosecution wherever necessary. All trademarks not owned by Tyco International Ltd. are the property of their respective owners, and are used with permission or 

allowed under applicable laws.

Product offerings and specifications are subject to change without notice. Actual products may vary from photos. Not all products include all features. Availability varies by region; contact your sales representative.

Technical Support: 1-800-387-3630 (Can/US)

905-760-3000 (Intl.)  www.dsc.com

2 9 0 0 8 7 2 1 R0 0 1

firealarmresources.com

Содержание DSC PowerSeries neo

Страница 1: ...t Test the panel completely to ensure that all features and functions operate as programmed 901 Walk Test 904 000 Wireless Placement Test Modules Wireless keypads HS2LCDWFxUL HS2LCDWFPxUL HS2LCDWFPVxU...

Страница 2: ...lephone connection e Do not route any wiring over circuit boards f The installer must ensure that a readily accessible disconnect device is incorporated into the building for permanently connected ins...

Страница 3: ...sistors When double end of line DEOL resistors are installed at the end of a zone loop the sec ond resistor enables the panel to determine if the zone is in alarm tampered or faulted Diagram 1 4 DEOL...

Страница 4: ...quired Programming Once basic installation of the alarm panel is complete the following general configuration options can be set 000 Language Selection LCD keypads only Use this section to set the lan...

Страница 5: ...ication 9 Normally Closed EOL 10 Single EOL 11 Double EOL 12 Fast Normal Loop Response Trouble Detailed Trouble 01 Service Required 01 Bell circuit 02 RF jam detected 03 Aux supply trouble 04 Time and...

Страница 6: ...on PGM2 being used as a 2 wire smoke detector input This trouble is generated by a short on hardwired zones when DEOL is used Ensure a 2 2K EOL resistor is connected red red red Remove wire leads from...

Страница 7: ...led in the same enclosure and configured as primary or back up with AES 128 bit encryption Compliant with EN50136 1 1 EN50136 2 1 ATS2 requirements Trouble 10 Module Tamper Press 10 to determine speci...

Страница 8: ...03 Maintenance Code AAAA00 PGM Programming 007 PGM Programming 000 Main Bell Partition Assignment 1 Partition 1 2 Partition 2 3 Partition 3 4 Partition 4 5 Partition 5 6 Partition 6 7 Partition 7 8 Pa...

Страница 9: ...Thursday Friday Saturday 003 Auto Disarming Holiday Schedule Holiday 1 Holiday 2 Holiday 3 Holiday 4 004 Auto Arming Pre Alert 004 005 Auto Arming Postpone Timer 000 006 No Activity Arming Timer 000...

Страница 10: ...g 4 Pulse Dial After 5th Attempt 5 Parallel Communications 6 Alternate Dial 7 Reduced Dialing Attempts 8 Activity Delinquency 381 Communicator Option 2 1 Keypad Ringback 2 Bell Ringback 4 Closing Conf...

Страница 11: ...may not remove any proprietary notices marks or labels from the Software Product You shall institute reasonable measures to ensure compliance with the terms and conditions of this EULA b Separation of...

Страница 12: ...80 017 081 018 082 019 083 020 084 021 085 022 086 023 087 024 088 025 089 026 090 027 091 028 092 029 093 030 094 031 095 032 096 033 097 034 098 035 099 036 100 037 101 038 102 039 103 040 104 041 1...

Страница 13: ...Wireless Device Record Installer Defined Access Codes System Account Code Module Type Slot Serial Number Module Type Slot Serial Number Device Type Zone Serial Number Device Type Zone Serial Number 0...

Страница 14: ...Fire Installations section 001 fire zone shall be programmed as type 025 The entry delay shall not exceed 45 seconds refer to section 005 The exit delay shall not exceed 60 seconds refer to section 00...

Страница 15: ...s of time Also an intruder may cut the telephone line or defeat its operation by more sophisticated means which may be difficult to detect Insufficient Time There may be circumstances when the system...

Страница 16: ...entry and exit delays and bell time out for the system Note Combined entry delay and communications delay abort window shall not exceed 60s Range 30 sec to 4 min Default 30 sec Required programmable A...

Отзывы: