background image

P o w e r S e r i e s   N e o   I n s t a l l a t i o n   G u i d e

6

[02] Panel No Battery
The panel detects that no battery is 
present or that the battery is shorted.

• Verify battery is connected.
• Refer to troubleshooting steps for panel low 

battery.

[04] 4 High Current output 1-4 Low 
Battery (HSM2204)
HSM2204 battery less than 11.5VDC.
NOTE: This trouble condition will 
not clear until the battery voltage is 
12.5VDC min., under load.

• Charge battery. It may be low due to a long 

period without AC. 

• Replace battery if it is no longer able to hold a 

charge due to age.

[05] 4 High Current output 1-4 No 
Battery (HSM2204)
Enter 05 to view which HSM2204 
does not have a battery connected.

• Verify battery is connected.
• Refer to troubleshooting steps for panel low 

battery.

[7] Power Supply 1-4 Low Battery 
(HSM2300) 
Enter 07 to view which HSM2300 
has a battery voltage less than 11.5V.

• Charge battery. It may be low due to a long 

period without AC. 

• Replace battery if it is no longer able to hold a 

charge due to age.

[8] Power Supply 1-4 No Battery 
(HSM2300)
Enter 08 to view which HSM2300 
does not have a battery connected.

• Verify battery is connected.
• Refer to troubleshooting steps for panel low 

battery.

Trouble [3] Bus Voltage Trouble                     

Press [03] to determine specific trouble

Trouble

Troubleshooting

[01] HSM2HOST Bus Low Voltage
The 2-way wireless integration mod-

ule has detected a voltage less than 

6.3V on its aux input.

• Ensure voltage at module is higher than the doc-

umented limits. 

• Ensure wire run is not too long.
• Check voltage of panel battery.
• Trouble should clear when AC is re-applied and 

the battery has had time to charge.

• Disconnect AC and allow the panel to run on 

battery power. Ensure voltage at module is 
higher than the documented limits.

[02] Keypad 1-16 Bus Low Voltage
Enter 02 to view hardwired keypads 

with a bus voltage of less than 6.9V 

for ICON/LCD models that include a 

wireless transceiver, 7.7V for the 

ICON/LCD/LED models that do not.
[04] HSM2108 Bus Low Voltage
Enter 04 to view zone expanders that 

with a bus voltage of less than 5.9V.
[05] HSM2300 Bus Low Voltage
Enter 05 to view power supplies with 

a bus voltage of less than 6.9V.
[06] HSM2204 Bus Low Voltage
Enter 06 to view high current output 

modules that have detected a bus 

voltage of less than 6.9V.
[08] HSM2208 Bus Low Voltage
The low current output module has 

detected a voltage less than 5.9V on 

its aux input.

Trouble [4] AC Failure

Press [04] to determine specific trouble

Trouble

Troubleshooting

[01] Zone 1-128 AC
[05] HSM2300 AC 1-4
[06] HSM2204 1-4 AC
[07] Alarm Controller
An AC trouble has been detected on a 
device or module.

• Verify voltage measured across AC terminals is 

16-18VAC. Replace transformer if required.

Trouble [05] Device Faults     

Press [05] to determine specific trouble

Trouble

Troubleshooting

[01] Zone 1-128 faults
Wireless zones:
Enter [01] to view zones in fault. 
This trouble is generated by a zone 
wireless supervisory trouble.

• Ensure fire zones have a 5.6K resistor (green, 

blue, red) connected.

• Remove wire leads from Z and COM terminals 

and measure resistance of the wire leads: 

• Check for a short on DEOL zones or an 

open condition on SEOL fire zones.

• Connect a 5.6K resistor across the Z and COM 

terminals. Verify the trouble condition clears.

• Placement test a wireless device and re-locate it 

if bad results are received.

Hardwired zones:
Enter [01] to view zones in fault.
“Fire Zone” is displayed in the [*][2] 
menu if an open circuit is present on 
PGM2 being used as a 2-wire smoke 
detector input.
This trouble is generated by a short 
on hardwired zones when DEOL is 
used. 

• Ensure a 2.2K EOL resistor is connected (red, 

red, red).

• Remove wire leads from PGM2 and AUX+ ter-

minals and measure resistance of the wire leads:

• An open circuit indicates a break in the 

wiring or no resistor connected.

• Connect a 2.2K resistor across PGM2 and 

AUX+ terminals. Verify that trouble clears.

[02] Keypad 1-16 faults
Enter [02] to view keypads in fault. 
This trouble is caused by a wireless 
supervisory fault if the keypad is 
wireless.

• Placement test the wireless keypad and re-locate 

if needed.

[03] Siren 1-16 faults
This trouble is caused by a wireless 
supervisory fault on a wireless siren.

• See [02] Keypad 1-16 faults above.

[04] Repeater 1-8 faults
 This trouble is caused by a wireless 
supervisory fault on a wireless 
repeater, or by the repeater shutting 
down due to a loss of AC/DC power.

• See [02] Keypad 1-16 faults above.

Additional trouble conditions:
• Fire (2-W Smoke, PGX916, 

PGX926, PGX936)

• Gas (PGX923)
• Heat (PGX946)

• Freeze (PGX905)
• CO (PGX913) 
• Probe Disconnected (PGX905) 

Trouble [6] Device Low Battery        

 Press [06] to toggle through specific 
devices with low battery trouble

Trouble

Troubleshooting

[01] Zones 1-128
[02] keypad 1-16
[03] Siren 1-16
[04] Repeater 1-8
[05] User 1-95 
One or more wireless devices has a 
low battery.
NOTE: The event is not logged to the 
event buffer until the wireless device 
low battery delay time expires.
Programming section 

[377]

, Opt 

002.

• Verify zone operation.
• Verify that tamper and low battery condition is 

cleared and reported.

• View which device is in low battery though the 

[*][2] menu. 

Trouble [7] Device Tamper                  

Press [07] to determine specific trouble

Trouble

Troubleshooting

[01] Zone 1-128 tampers
[02] Keypad 1-16 tampers
[03] Siren 1-16 tampers
[04] Repeater 1-8 tampers

h

An open circuit is present on one or 
more zones with DEOL resistors 
enabled.

• Check that the tamper switch is securely 

attached to the wall.

• Remove the wire leads from I/O and COM and 

measure the resistance of the wire leads.

• Connect a 5.6K resistor (Green, Blue, Red) 

across the I/O and COM terminals. 

• Verify the trouble condition clears.

A tamper condition is present on one 

or more wireless devices.

• Ensure device cover is secure.
• Ensure device is correctly mounted for wall 

tamper operation.

• Trip, then restore the tamper. If tamper condi-

tion persists, replace wireless device.

Trouble [8] RF Delinquency

Press [08] to determine specific trouble

Trouble

Troubleshooting

[01] Zone 1-128 faults
[02] Keypad 1-16 faults
[03] Siren 1-16 faults
[04] Repeater 1-8 faults
HSM2HOST has not received

 

supervisory signal from a wireless 
device for 13 minutes. Arming dis-
abled until trouble acknowledged in 
[*][2] or the trouble is cleared.

• Open/close the device, press a key on the key-

pad or tamper/restore.

• Ensure the device is physically present.
• Check for device faults (e.g., low battery).
• Check the current signal strength and during the 

last 24 hours.

• Replace the battery.
• Replace the device.

Trouble [9] Module Supervisory           

Press [09] to determine specific zones with a 
tamper trouble

Trouble

Troubleshooting

[01] HSM2HOST
[02] Keypad 1-16
[04] HSM2108 1-15
[05] HSM2300 1-4
[06] HSM2204
[08] HSM2208 1-4
No supervisory response from 
enrolled module. 

• Modules are immediately enrolled and supervised. 

If a module is removed, or if the keypad slot is 
changed, module supervision must be reset.

• View the event buffer to identify the specific 

module(s) in trouble.

• To reset module supervision: 

• Enter programming section [902]. 
• Select auto or manual enrollment.

• Enter programming section [903] to identify 

modules connected to the Corbus.

firealarmresources.com

Содержание DSC PowerSeries neo

Страница 1: ...t Test the panel completely to ensure that all features and functions operate as programmed 901 Walk Test 904 000 Wireless Placement Test Modules Wireless keypads HS2LCDWFxUL HS2LCDWFPxUL HS2LCDWFPVxU...

Страница 2: ...lephone connection e Do not route any wiring over circuit boards f The installer must ensure that a readily accessible disconnect device is incorporated into the building for permanently connected ins...

Страница 3: ...sistors When double end of line DEOL resistors are installed at the end of a zone loop the sec ond resistor enables the panel to determine if the zone is in alarm tampered or faulted Diagram 1 4 DEOL...

Страница 4: ...quired Programming Once basic installation of the alarm panel is complete the following general configuration options can be set 000 Language Selection LCD keypads only Use this section to set the lan...

Страница 5: ...ication 9 Normally Closed EOL 10 Single EOL 11 Double EOL 12 Fast Normal Loop Response Trouble Detailed Trouble 01 Service Required 01 Bell circuit 02 RF jam detected 03 Aux supply trouble 04 Time and...

Страница 6: ...on PGM2 being used as a 2 wire smoke detector input This trouble is generated by a short on hardwired zones when DEOL is used Ensure a 2 2K EOL resistor is connected red red red Remove wire leads from...

Страница 7: ...led in the same enclosure and configured as primary or back up with AES 128 bit encryption Compliant with EN50136 1 1 EN50136 2 1 ATS2 requirements Trouble 10 Module Tamper Press 10 to determine speci...

Страница 8: ...03 Maintenance Code AAAA00 PGM Programming 007 PGM Programming 000 Main Bell Partition Assignment 1 Partition 1 2 Partition 2 3 Partition 3 4 Partition 4 5 Partition 5 6 Partition 6 7 Partition 7 8 Pa...

Страница 9: ...Thursday Friday Saturday 003 Auto Disarming Holiday Schedule Holiday 1 Holiday 2 Holiday 3 Holiday 4 004 Auto Arming Pre Alert 004 005 Auto Arming Postpone Timer 000 006 No Activity Arming Timer 000...

Страница 10: ...g 4 Pulse Dial After 5th Attempt 5 Parallel Communications 6 Alternate Dial 7 Reduced Dialing Attempts 8 Activity Delinquency 381 Communicator Option 2 1 Keypad Ringback 2 Bell Ringback 4 Closing Conf...

Страница 11: ...may not remove any proprietary notices marks or labels from the Software Product You shall institute reasonable measures to ensure compliance with the terms and conditions of this EULA b Separation of...

Страница 12: ...80 017 081 018 082 019 083 020 084 021 085 022 086 023 087 024 088 025 089 026 090 027 091 028 092 029 093 030 094 031 095 032 096 033 097 034 098 035 099 036 100 037 101 038 102 039 103 040 104 041 1...

Страница 13: ...Wireless Device Record Installer Defined Access Codes System Account Code Module Type Slot Serial Number Module Type Slot Serial Number Device Type Zone Serial Number Device Type Zone Serial Number 0...

Страница 14: ...Fire Installations section 001 fire zone shall be programmed as type 025 The entry delay shall not exceed 45 seconds refer to section 005 The exit delay shall not exceed 60 seconds refer to section 00...

Страница 15: ...s of time Also an intruder may cut the telephone line or defeat its operation by more sophisticated means which may be difficult to detect Insufficient Time There may be circumstances when the system...

Страница 16: ...entry and exit delays and bell time out for the system Note Combined entry delay and communications delay abort window shall not exceed 60s Range 30 sec to 4 min Default 30 sec Required programmable A...

Отзывы: